Data sheet
PROeco
PRO ECO 72W 24V 3A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
You are looking for a reliable power supply with basic
functions.
With PROeco we can offer you low-cost switch-mode
power supply units with
high efficiency and system capability. Let’s connect.
In the series production of machines, in particular, switchmode power supply units with
above-average performance values can deliver genuine
competitive advantages.
The low-cost PROeco series offers all the basic functions
and delivers impressively
high performance and flexibility.
Our PROeco switch-mode power supply units feature a
compact design, high
efficiency and are extremely easy to maintain. Thanks to
temperature protection,
short-circuit and overload resistance they can be
universally used in all
applications.
Wide-ranging safety functions and compatibility with our
diode and capacitance modules, together with UPS
components for setting up a
redundant power supply, characterise solutions with
PROeco.
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
PRO ECO 72W 24V 3A
1469470000
Power supply, switch-mode power supply unit, 24
V
4050118275711
1 pc(s).
Creation date October 8, 2018 5:04:50 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
1
Data sheet
PROeco
PRO ECO 72W 24V 3A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
34 mm
125 mm
100 mm
568 g
Width (inches)
Height (inches)
Depth (inches)
1.339 inch
4.921 inch
3.937 inch
70 °C
85 °C
-25 °C...70 °C
Operating temperature, min.
Storage temperature, min.
Storage temperature
-25 °C
-40 °C
-40 °C...85 °C
0,55 A @ 230 V AC / 1,04
A @ 110 V AC
Screw connection
80…370 V DC (Derating @
120 V DC)
47...63 Hz
max. 40 A
2 A / DI, safety fuse
6 A, Char. B, circuit breaker
2...4 A, Char. C, circuit
breaker
AC input voltage range
85…264 V AC (Derating @
100 V AC)
0,22 A @ 370 V DC / 0,68
A @ 120 V DC
unrestricted
3 A @ 55 °C, 2,25 A @ 70
°C
24 V
Yes
Yes
3 A at 55 °C
< 50 mVSS @ 24 V DC, IN
Connection system
Output power
Temperatures
Operating temperature, max.
Storage temperature, max.
Operating temperature
Input
AC current consumption
Connection system
DC input voltage range
Input frequency
Inrush current
Recommended back-up fuse
DC current consumption
Frequency range AC
Input fuse (internal)
Rated input voltage
Surge protection
47...63 Hz
Yes
100...240 V AC (widerange input)
Varistor
output
Capacitive load
Continuous output current @ URated
Output voltage
Overload protection
Protection against inverse voltage
Rated (nominal) output current @ UNom
Residual ripple, breaking spikes
Output voltage
Parallel connection option
Ramp-up time
Rated output voltage
Screw connection
72 W
22...28 V (adjustable via
potentiometer)
yes, max. 5
≤ 100 ms
24 V DC ± 1 %
Creation date October 8, 2018 5:04:50 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
2
Data sheet
PROeco
PRO ECO 72W 24V 3A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
General data
AC failure bridging time @ INom
Earth leakage current, max.
Indication
Max. perm. air humidity (operational)
Operating temperature
Power loss, idling
Protection against over-heating
Protection degree
> 100 ms @ 230 V AC / >
20 ms @ 115 V AC
3.5 mA
LED green (Uoutput >
21.6 V DC), LED yellow
(Ioutput > 90% IRated
typ. ), LED red (overload,
overtemperature, shortcircuit, Uoutput < 20.4 V
DC)
5 %…95 % RH
-25 °C...70 °C
4W
Yes
IP20
Degree of efficiency
Housing version
MTBF
87 %
Metal, corrosion resistant
> 500,000 h acc. to IEC
61709 (SN29500)
on terminal rail TS 35
> 0.5 @ 230 V AC / > 0.53
@ 115 V AC
9.5 W
Mounting position, installation notice
Power factor (approx.)
Power loss, nominal load
Protection against reverse voltages from
the load
30…35 V DC
Short-circuit protection
Yes
Noise emission acc. to EN55023
Interference immunity test acc. to
EMC / shock / vibration
Limiting of mains voltage harmonic
currents
Vibration resistance IEC 60068-2-6
Shock resistance IEC 60068-2-27
in accordance with EN
61000-3-2
1 g according to EN50178
15 g In all directions
Class B
EN 61000-4-2 (ESD),
EN 61000-4-3 (RS), EN
61000-4-4 (burst), EN
61000-4-5 (surge), EN
61000-4-6 (conducted),
EN61000-4-8 (Fields),
EN61000-4-11 (Dips)
Insulation coordination
Class of protection
Insulation voltage output / earth
Pollution severity
I, with PE connection
0.5 kV
2
Insulation voltage input / earth
Insulation voltage, input/output
2 kV
3 kV
For use with electronic equipment
Protective separation / protection
against electrical shock
Safety transformers for switch-mode
power supplies
Acc. to EN50178 /
VDE0160
VDE0100-410 / acc. to
DIN57100-410
Electrical safety (applied standards)
Electrical machine equipment
Protection against dangerous shock
currents
Safety extra-low voltage
Acc. to EN60204
Acc. to VDE0106-101
SELV acc. to EN60950,
PELV acc. to EN60204
nach EN61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max.
Conductor cross-section, flexible , min.
Conductor cross-section, rigid , min.
Number of terminals
Tightening torque, min.
12
0.5 mm²
0.5 mm²
3 for L/N/PE
0.5 Nm
Conductor cross-section, AWG/kcmil ,
min.
Conductor cross-section, rigid , max.
Connection system
Tightening torque, max.
Wire connection cross section, flexible
(input), max.
26
6 mm²
Screw connection
0.6 Nm
2.5 mm²
Creation date October 8, 2018 5:04:50 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
3
Data sheet
PROeco
PRO ECO 72W 24V 3A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max.
Conductor cross-section, flexible , max.
Conductor cross-section, rigid , max.
Connection system
Tightening torque, max.
12
2.5 mm²
6 mm²
Screw connection
0.6 Nm
Conductor cross-section, AWG/kcmil ,
min.
Conductor cross-section, flexible , min.
Conductor cross-section, rigid , min.
Number of terminals
Tightening torque, min.
26
0.5 mm²
0.5 mm²
5 (+,--,13,14)
0.5 Nm
Signalling
Contact load (NO contact)
Relay on/off
max. 30 V DC / 1 A
Output voltage >21.6 V
DC/