Data sheet
ACT20P
ACT20P-AI-AO-DC-S
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 1429-0
Fax: +49 5231 14292083
www.weidmueller.com
ACT20P: The flexible solution
• Precise and highly functional signal converters
• Simple configuration via display (Pro DCDC II), FDT/
DTM software or DIP switch
• Release levers simplify handling
• More space in the control cabinet, from 12.5 mm wide
for two channels
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
ACT20P-AI-AO-DC-S
1477420000
ACT20P, Signal converter/insulator, Input, DC U/I
signals, Screw connection
4050118284959
1 pc(s).
Creation date October 30, 2017 9:25:46 PM CET
Catalogue status 20.10.2017 / We reserve the right to make technical changes.
1
Data sheet
ACT20P
ACT20P-AI-AO-DC-S
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 1429-0
Fax: +49 5231 14292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Weight
12.5 mm
117.2 mm
113.7 mm
80 g
Width (inches)
Height (inches)
Depth (inches)
Net weight
10...90 % (no
condensation)
-25 °C...70 °C
Operating temperature
0.492 inch
4.614 inch
4.476 inch
80 g
Temperatures
Humidity
Storage temperature
-20 °C...60 °C
Input
Number of inputs
Input voltage
Input current
Resolution
1
configurable, 0…11 V (min.
measurement range 2V)
configurable, 0…22 mA
(min. measurement range
4 mA)
3.5 µA / 1.76 mV per bit
Sensor supply
Input resistance, voltage
1
adjustable, 0...22 mA, min.
output range 4 mA
≤ 1kΩ
Output voltage, note
Input resistance, current
24 V DC
≥ 1 MΩ
100 Ω
Output
Number of outputs
Output current
load impedance current
load impedance voltage
Offset voltage
adjustable, 0...11 V, min.
output range 2V
≥ 500 kΩ
≤ 20 mV
General data
Configuration
Linearity
Mounting rail
Step response time
Temperature coefficient
DIP switch, Keys and LED
display
< ± 0.1 % of signal range,
Typ. ± 0.05 % of signal
range
TS 35
350 ms
< 0.05 % / °C
Galvanic isolation
Long-term drift
Power consumption, typ.
Supply voltage
Galvanic isolation
Insulation voltage
Standards
3-way isolator, between
input ⁄ output ⁄ supply
0.1 % / 10.000 h
3W
12...60 V DC
Insulation coordination
EMC standards
Impulse withstand voltage
Pollution severity
Surge voltage category
IEC 61326-1
4 kV (1.2/50 µs)
2
III
3-way isolator, between
input ⁄ output ⁄ supply
2 kV inputs / outputs
IEC 61326-1:2012, UL
61010-1:2012, 3rd
Edition
Creation date October 30, 2017 9:25:46 PM CET
Catalogue status 20.10.2017 / We reserve the right to make technical changes.
2
Data sheet
ACT20P
ACT20P-AI-AO-DC-S
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 1429-0
Fax: +49 5231 14292083
www.weidmueller.com
Technical data
Connection data
Type of connection
Tightening torque, max.
Clamping range, rated connection, min.
Wire connection cross section AWG,
min.
Screw connection
0.6 Nm
0.5 mm²
AWG 30
Tightening torque, min.
Clamping range, rated connection
Clamping range, rated connection, max.
Wire connection cross section AWG,
max.
0.4 Nm
1.5 mm²
2.5 mm²
eClass 6.2
27-21-01-20
AWG 14
Classifications
ETIM 6.0
eClass 9.1
EC002653
27-21-01-20
Approvals
Approvals
ROHS
Conform
Downloads
Approval/Certificate/Document of
Conformity
Brochure/Catalogue
User Documentation
Declaration of Conformity
Declaration of Conformity
CAT 4.1 ELECTR 16/17 EN
Instruction sheet
Creation date October 30, 2017 9:25:46 PM CET
Catalogue status 20.10.2017 / We reserve the right to make technical changes.
3
Data sheet
ACT20P
ACT20P-AI-AO-DC-S
Drawings
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 1429-0
Fax: +49 5231 14292083
www.weidmueller.com
terminal coding
Creation date October 30, 2017 9:25:46 PM CET
Catalogue status 20.10.2017 / We reserve the right to make technical changes.
4
很抱歉,暂时无法提供与“1477420000”相匹配的价格&库存,您可以联系我们找货