Data sheet
PROmax
PRO MAX 960W 24V 40A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
PROmax offers diverse solutions for demanding
automation.
Our high performance and durable PROmax switchmode power supply units are designed for especially
demanding requirements. PROmax reliably copes with
continuous overload of up to 20% or short-term peak
loads of 300% occurring with high control cabinet
temperatures.
High boost capability and full power are also made
possible in a wide temperature range. Our switch-mode
power supply units can be used around the world and
are also suitable for confined spaces thanks to their low
width.
Together with our uninterruptible DC USPs, the diode
modules or CAP modules, you can create a power supply
solution that is tailored to your requirements.
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
PRO MAX 960W 24V 40A
1478150000
Power supply, switch-mode power supply unit, 24
V
4050118286038
1 pc(s).
Creation date October 9, 2018 4:05:47 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
1
Data sheet
PROmax
PRO MAX 960W 24V 40A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
140 mm
130 mm
150 mm
3,900 g
Width (inches)
Height (inches)
Depth (inches)
5.512 inch
5.118 inch
5.905 inch
5...95 %, no condensation
-25 °C
-40 °C
-40 °C...85 °C
Operating temperature, max.
Storage temperature, max.
Operating temperature
70 °C
85 °C
-25 °C...70 °C
Temperatures
Humidity at operating temperature
Operating temperature, min.
Storage temperature, min.
Storage temperature
Input
AC current consumption
Connection system
DC input voltage range
Input fuse (internal)
Rated input voltage
Standby power consumption, max.
4,52A @ 230 VAC / 10A
@ 115 VAC
Screw connection
80...370 V DC
Yes
100...240 V AC (widerange input)
1W
AC input voltage range
DC current consumption
Frequency range AC
Inrush current
Recommended back-up fuse
Surge protection
85…277 V AC
2,8A @ 370 VDC / 10A @
120 VDC
45…65 Hz
max. 15 A
20 A, char. B circuit
breaker, 16 A, Char. C
circuit breaker
Varistor
output
Connection system
Output power
Output voltage
Protection against inverse voltage
Rated (nominal) output current @ UNom
Reserve capacity @ URated
Screw connection
960 W
22.5...29.5 V (adjustable
via potentiometer)
Yes
40 A @ 60 °C
48 A (1 min), 60 A (4s),
100…240 V AC
Continuous output current @ URated
Output voltage
Parallel connection option
Pulsed current capacity @ URated
Rated output voltage
Residual ripple, breaking spikes
48 A @ 45°C, 30 A @ 70°C
24 V
yes, max. 3
120 A (2ms)
24 V DC ± 1 %
< 50 mVss @ UNenn, Full
Load
Creation date October 9, 2018 4:05:47 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
2
Data sheet
PROmax
PRO MAX 960W 24V 40A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
General data
AC failure bridging time @ INom
Degree of efficiency
Earth leakage current, max.
MTBF
min. 20 ms
93%
3.5 mA
>500.000h (25°C, IEC
61709 (SN29500))
-25 °C...70 °C
5W
Operating temperature
Power loss, idling
Protection against reverse voltages from
the load
30…35 V DC
Series switching capability
Yes
Start-up
Surge voltage category
≥ -40 °C
III
Current limiting
Derating
Housing version
Mounting position, installation notice
Power factor (approx.)
Power loss, nominal load
Protection degree
Short-circuit protection
Status indication
> 120 % IN
> 60°C / 75% @ 70°C
Metal, corrosion resistant
Horizontal on TS35
mounting rail. 50 mm of
clearance at top & bottom
for air circ. Can mount side
by side with no space in
between.
> 0.95 @ 230 V AC
72.3 W
IP20
Yes
LED red/green and relay
(≥21.6 V DC LED green,
relay on/ ≤20.6 LED red,
relay off)
EMC / shock / vibration
Noise emission acc. to EN55023
Interference immunity test acc. to
Vibration resistance IEC 60068-2-6
Class B
Shock resistance IEC 60068-2-27
EN 55024, EN 55022,
IEC61000-3-2,-3,
IEC61000-4-2,-3,-4,-5,-6,-8,-11
2.3 g
30 g in all directions
Insulation coordination
Class of protection
Insulation voltage input / earth
Insulation voltage, input/output
Surge voltage category
I, with PE connection
3.5 kV
4 kV
III
Humidity at operating temperature
Insulation voltage output / earth
Pollution severity
5...95 %, no condensation
0.5 kV
2
For use with electronic equipment
Protective separation / protection
against electrical shock
Safety transformers for switch-mode
power supplies
Acc. to EN50178 /
VDE0160
VDE0100-410 / acc. to
DIN57100-410
Electrical safety (applied standards)
Electrical machine equipment
Protection against dangerous shock
currents
Safety extra-low voltage
Acc. to EN60204
Acc. to VDE0106-101
SELV acc. to EN60950,
PELV acc. to EN60204,
IEC61204
nach EN61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max.
Conductor cross-section, flexible , min.
Conductor cross-section, rigid , min.
Number of terminals
Tightening torque, max.
Wire connection cross section, flexible
(input), max.
10
0.22 mm²
0.18 mm²
3 for L/N/PE
0.6 Nm
4 mm²
Conductor cross-section, AWG/kcmil ,
min.
Conductor cross-section, rigid , max.
Connection system
Screwdriver blade
Tightening torque, min.
26
6 mm²
Screw connection
0.8 x 4.0, PZ 1
0.5 Nm
Creation date October 9, 2018 4:05:47 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
3
Data sheet
PROmax
PRO MAX 960W 24V 40A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max.
Conductor cross-section, flexible , max.
Conductor cross-section, rigid , max.
Connection system
Screwdriver blade
Tightening torque, min.
Conductor cross-section, AWG/kcmil ,
min.
Conductor cross-section, flexible , min.
Conductor cross-section, rigid , min.
Number of terminals
Tightening torque, max.
Floating contact
Institute (GERMLLOYD)
Certificate No. (GERMLLOYD)
Institute (cULus)
Certificate no. (cULus)
Institute (cULusEX)
Certificate no. (cULusEX)
Institute (cURus)
Certificate No. (cURus)
8
16 mm²
16 mm²
Screw connection
1.0 x 5.5
1.2 Nm
22
0.5 mm²
0.5 mm²
8 (++,---,11,13,14)
1.5 Nm
Signalling
Contact load (NO contact)
Status indication
max. 30 V DC / 1 A
LED red/green and relay
(≥21.6 V DC LED green,
relay on/ ≤20.6 LED red,
relay off)
Yes
Approvals
TAA00000TT
E258476
E470829
E255651
Classifications
ETIM 5.0
eClass 6.2
eClass 8.1
eClass 9.1
EC002541
27-04-90-04
27-04-90-04
27-04-07-01
ETIM 6.0
eClass 7.1
eClass 9.0
EC002540
27-04-90-04
27-04-07-03
Product information
Descriptive text ordering data
The internal varistor found in a switch-mode power supply does not replace the need for surge protection within
a system.
Creation date October 9, 2018 4:05:47 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
4
Data sheet
PROmax
PRO MAX 960W 24V 40A
Technical data
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Approvals
Approvals
ROHS
Conform
Downloads
Approval/Certificate/Document of
Conformity
Brochure/Catalogue
Engineering Data
Engineering Data
User Documentation
DE_PA5200_160310_001.pdf
CAT 4.3 ELECTR 15/16 EN
EPLAN, WSCAD
STEP
Operating instructions
Operating instructions
Creation date October 9, 2018 4:05:47 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
5
Data sheet
PROmax
PRO MAX 960W 24V 40A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Electric symbol
Derating curve
Derating curve
Creation date October 9, 2018 4:05:47 PM CEST
Catalogue status 28.09.2018 / We reserve the right to make technical changes.
6