Data sheet
OMNIMATE Power - series WGK
WGK 10 GY BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Product image
Similar to illustration
The WGK finger-proof-insulated enclosures are especially
suitable as industrial electronic enclosures for frequency
converters, power supplies or filter components which
offer a convenient and reliable form of connection
internally and externally. To match the wire guides to
the installation requirements in the best possible way,
Weidmüller offers two versions with horizontal (WGK)
and vertical (WGKV) outlet directions.
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
Product data
Packaging
WGK 10 GY BX
2439390000
OMNIMATE Power - series WGK, Feed-through
terminal, Rated cross-section: 10 mm², Wemid
(PA)
4050118468366
50 pc(s).
IEC: 500 V / 57 A / 0.5 - 16 mm²
UL: 300 V / 65 A / AWG 24 - AWG 6
Box
Creation date April 24, 2019 3:54:45 PM CEST
Catalogue status 12.04.2019 / We reserve the right to make technical changes.
1
Data sheet
OMNIMATE Power - series WGK
WGK 10 GY BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Net weight
19.587 g
OMNIMATE Power - series
WGK
180°
0.8 x 4.0
2.4 Nm
Wire connection method
Fitted by customer
Tightening torque, min.
Clamping screw
Touch-safe protection acc. to DIN VDE
0470
Colour code
UL 94 flammability rating
Contact surface
Storage temperature, max.
Operating temperature, min.
Temperature range, installation, min.
System parameters
Product family
Conductor outlet direction
Screwdriver blade
Tightening torque, max.
Stripping length
11 mm
Screw connection
No
1.2 Nm
M4
IP 20
Material data
Insulating material
Colour chart (similar)
Contact material
Storage temperature, min.
Max. relative humidity during storage
Operating temperature, max.
Temperature range, installation, max.
Wemid (PA)
RAL 7035
E-Cu
-25 °C
80 %
120 °C
120 °C
grey
V-0
tinned
55 °C
-50 °C
-25 °C
Conductors suitable for connection
Clamping range, min.
0.5 mm²
Clamping range, max.
16 mm²
Wire connection cross section AWG,
AWG 24
min.
Wire connection cross section AWG,
AWG 6
max.
Solid, min. H05(07) V-U
0.5 mm²
Solid, max. H05(07) V-U
16 mm²
Stranded, min. H07V-R
10 mm²
Stranded, max. H07V-R
16 mm²
Flexible, min. H05(07) V-K
0.5 mm²
Flexible, max. H05(07) V-K
10 mm²
w. wire end ferrule, DIN 46228 pt 1, min0.5 mm²
w. wire end ferrule, DIN 46228 pt 1,
10 mm²
max.
Clampable conductor
Cross-section for conductor connection
AEH
Cross-section for conductor connection
AEH
Cross-section for conductor connection
Max. clamping range
AEH
16 mm²
Type
nominal
Stripping length
Type
nominal
Stripping length
Type
nominal
Stripping length
fine-wired
0.5 mm²
nominal 10 mm
fine-wired
0.75 mm²
nominal 10 mm
fine-wired
1 mm²
nominal 10 mm
Creation date April 24, 2019 3:54:45 PM CEST
Catalogue status 12.04.2019 / We reserve the right to make technical changes.
2
Data sheet
OMNIMATE Power - series WGK
WGK 10 GY BX
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Rated data acc. to IEC
tested acc. to standard
Rated current, min. no. of poles
(Tu=20°C)
Rated voltage for surge voltage class /
pollution degree III/3
Rated voltage (Use group C / CSA)
Rated current (Use group C / CSA)
Wire cross-section, AWG, max.
Certificate No. (cURus)
300 V
65 A
AWG 24
Specifications are
maximum values, details see approval certificate.
E60693
Rated voltage (Use group C / UL 1059) 300 V
Rated current (Use group C / UL 1059) 65 A
Wire cross-section, AWG, max.
AWG 6
Box
125 mm
VPE length
VPE height
210 mm
80 mm
EC001283
27-14-11-34
eClass 6.2
eClass 9.1
27-14-11-34
27-14-11-34
IEC 60664-1, IEC 61984
Rated current, max. no. of poles
(Tu=20°C)
57 A
Rated impulse voltage for surge voltage
class/ contamination degree III/3
6 kV
57 A
500 V
Rated data acc. to CSA
Rated voltage (Use group B / CSA)
Rated current (Use group B / CSA)
Wire cross-section, AWG, min.
300 V
65 A
AWG 24
300 V
65 A
AWG 6
Rated data acc. to UL 1059
Institute (cURus)
Rated voltage (Use group B / UL 1059)
Rated current (Use group B / UL 1059)
Wire cross-section, AWG, min.
Reference to approval values
Packing
Packaging
VPE width
Classifications
ETIM 6.0
eClass 9.0
Notes
Notes
• Clearance and creepage distances to other components must be devised in accordance with the relevant
application standard. This can be achieved in the device by full encapsulation or by the use of additional
spacer plates.
• Rated data refer only to the component itself. Clearance and creepage distances to other components are to
be designed in accordance with the relevant application standards.
• Colours: SW = black; GN/YL = green/yellow; GY = grey
• Additional colours on request
• WGK: Rated voltage plastic walls: 1 - 4 mm = 500 V; metal walls: 1 - 2.5 mm = 400 V; metal walls: 2.5 4 mm = 250 V
Creation date April 24, 2019 3:54:45 PM CEST
Catalogue status 12.04.2019 / We reserve the right to make technical changes.
3
Data sheet
OMNIMATE Power - series WGK
WGK 10 GY BX
Technical data
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Approvals
Approvals
ROHS
Conform
Downloads
Approval/Certificate/Document of
Conformity
Brochure/Catalogue
Engineering Data
Declaration of the Manufacturer
FL DRIVES EN
MB DEVICE MANUF. EN
FL DRIVES DE
FL_BASE_STATION_EN
FL ELEVATOR EN
FL POWER SUPPLY EN
FL 72H SAMPLE SER EN
PO OMNIMATE EN
STEP
Creation date April 24, 2019 3:54:45 PM CEST
Catalogue status 12.04.2019 / We reserve the right to make technical changes.
4
Data sheet
OMNIMATE Power - series WGK
WGK 10 GY BX
Drawings
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Dimensional drawing
Graph
Creation date April 24, 2019 3:54:45 PM CEST
Catalogue status 12.04.2019 / We reserve the right to make technical changes.
5