Data sheet
PROtop
PRO TOP1 960W 48V 20A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
High-end power supplies must perform efficiently and
reliably, even in challenging industrial environments.
This requires high power reserves, a long service life and
optimal protection against overvoltage, vibration and
extreme temperature conditions.
New DCL technology gives PROtop an outstanding
dynamic range. This can be used for the reliable
triggering of circuit breakers or for powerful motor starts.
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
PRO TOP1 960W 48V 20A
2466920000
Power supply, switch-mode power supply unit, 48
48 V
4050118481600
1 pc(s).
Creation date December 27, 2018 6:38:49 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes.
1
Data sheet
PROtop
PRO TOP1 960W 48V 20A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
124 mm
130 mm
125 mm
3,382 g
Width (inches)
Height (inches)
Depth (inches)
4.882 inch
5.118 inch
4.921 inch
5...95 %, no condensation
-25 °C
-40 °C
-40 °C...85 °C
Operating temperature, max.
Storage temperature, max.
Operating temperature
70 °C
85 °C
-25 °C...70 °C
Lead 7439-92-1
85…277 V AC
80 ... 410 V DC
45…65 Hz
Connection system
Dielectric strength
Input fuse (internal)
Rated input voltage
Connection system
Output power
Output voltage
Protection against inverse voltage
Rated (nominal) output current @ UNom
Reserve capacity @ URated
Triggerable circuit breakers
Temperatures
Humidity at operating temperature
Operating temperature, min.
Storage temperature, min.
Storage temperature
Environmental Product Compliance
REACH SVHC
Input
AC input voltage range
DC input voltage range
Frequency range AC
Inrush current
Surge protection
max. 15 A
Varistor
PUSH IN
max. 300 V AC ≤ 15 s
Yes
100 - 240 V AC / 120 340 V DC
output
DCL - peak load reserve
Mains failure bridge-over time
Output voltage
Parallel connection option
Ramp-up time
Rated output voltage
Residual ripple, breaking spikes
150 % (5 s); 400 % (15
ms)
> 20 ms @ 115V AC/ 230
VAC
48 48 V
Passive Current Sharing
≤ 100 ms
48 V DC ± 1 %
< 100 mVPP
PUSH IN
960 W
45...56 V
Yes
20 A @ 60 °C
130% permanent at ≤
40°C
C2, C4, C6, B6, B10, B2,
B4
Creation date December 27, 2018 6:38:49 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes.
2
Data sheet
PROtop
PRO TOP1 960W 48V 20A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
General data
AC failure bridging time @ INom
Derating
Housing version
Mounting position, installation notice
Power factor (approx.)
Power loss, nominal load
Series switching capability
Surge voltage category
> 20 ms @ 230 V AC / >
20 ms @ 115 V AC
> 60°C (2.5% / 1°C)
Metal, corrosion resistant
Horizontal on DIN rail
TS 35, top and bottom
50 mm clearance for
free air flow, 10 mm
clearance to neighbouring
active subassemblies
with full load, 5 mm with
passive neighbouring
subassemblies, direct row
mounting with 90% rated
load
> 0.9
61.3 W
Yes
III
Degree of efficiency
Earth leakage current, max.
MTBF
Operating temperature
Power loss, idling
Protection degree
Short-circuit protection
Vibration resistance IEC 60068-2-6
Shock resistance IEC 60068-2-27
94%
3.5 mA
> 1.000.000 h according
IEC 1709 (SN29500)
-25 °C...70 °C
10 W
IP20
Yes, internal
EMC / shock / vibration
Noise emission in accordance with
EN55032
Interference immunity test acc. to
Class B
EN 55032:2015, EN
55024:2010/A1:2015,
EN 55035:2017, EN
61000-3-2:2014, EN
61000-3-3:2013, EN
61000-6-1:2007, EN
61000-6-2:2005, EN
61000-6-3:2007/
A1:2011, EN
61000-6-4:2007/
A1:2011
2.3 g (on DIN rail), 4 g
(with direct mounting)
30 g in all directions
Insulation coordination
Class of protection
Insulation voltage input / earth
Insulation voltage, input/output
Surge voltage category
I, with PE connection
4 kV
4 kV
III
Humidity at operating temperature
Insulation voltage output / earth
Pollution severity
5...95 %, no condensation
0.5 kV
2
For use with electronic equipment
Protective separation / protection
against electrical shock
Safety transformers for switch-mode
power supplies
Acc. to EN50178 /
VDE0160
VDE0100-410 / acc. to
DIN57100-410
Electrical safety (applied standards)
Electrical machine equipment
Protection against dangerous shock
currents
Safety extra-low voltage
Acc. to EN60204
Acc. to VDE0106-101
SELV acc. to EN60950,
PELV acc. to EN60204
nach EN61558-2-16
Creation date December 27, 2018 6:38:49 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes.
3
Data sheet
PROtop
PRO TOP1 960W 48V 20A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max.
Conductor cross-section, flexible , min.
Conductor cross-section, rigid , min.
Number of terminals
Wire connection cross section, flexible
(input), max.
4
0.75 mm²
0.75 mm²
3 for L/N/PE
16 mm²
Conductor cross-section, AWG/kcmil ,
min.
Conductor cross-section, rigid , max.
Connection system
Screwdriver blade
20
16 mm²
PUSH IN
0.6 x 3.5
Conductor cross-section, AWG/kcmil ,
min.
Conductor cross-section, flexible , min.
Conductor cross-section, rigid , min.
Number of terminals
20
0.75 mm²
0.75 mm²
5 (+ + / - - -)
Wire connection cross-section, flexible
(signal), min.
Wire cross-section, AWG/kcmil , max.
Wire cross-section, solid , max.
0.14 mm²
16
1.5 mm²
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max.
Conductor cross-section, flexible , max.
Conductor cross-section, rigid , max.
Connection system
Screwdriver blade
4
16 mm²
16 mm²
PUSH IN
0.6 x 3.5
Connection data (signal)
Wire connection cross-section, flexible
(signal), max.
Wire connection method
Wire cross-section, AWG/kcmil , min.
Wire cross-section, solid , min.
1.5 mm²
PUSH IN
26
0.14 mm²
Signalling
LED green/red
Green: Operation (failure-
free), Flashing green:
advance warning I>90%,
Green/red flashing: output
switched off (switchoff mode), Flashing red:
overload/error
Classifications
ETIM 6.0
eClass 9.1
EC002540
27-04-07-01
eClass 6.2
27-04-90-04
Product information
Descriptive text ordering data
Current technical data at catalog.weidmueller.com
Approvals
ROHS
Conform
Creation date December 27, 2018 6:38:49 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes.
4
Data sheet
PROtop
PRO TOP1 960W 48V 20A
Technical data
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Downloads
Approval/Certificate/Document of
Conformity
Engineering Data
Engineering Data
User Documentation
Declaration of Conformity
EPLAN
STEP
STEP
IS PRO TOP1 960W 48V 20A
Operating instructions
Creation date December 27, 2018 6:38:49 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes.
5
Data sheet
PROtop
PRO TOP1 960W 48V 20A
Drawings
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Creation date December 27, 2018 6:38:49 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes.
6