Data sheet
TERMSERIES
TRP 230VUC 1CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Product image
Similar to illustration
TERMSERIES relay module, complete modules consisting
of
a relay and a base with AC/DC/UC coils,
available in different versions:
• With screw and tension-clamp connection
• AgNi contact, optionally with hard gold-plated contacts
• 1 and 2 COs
• Optionally with multiple-voltage input: 24...230 V UC
• With various protective circuits
in the input (free-wheel diode, RC element)
• Illuminated ejection lever
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
TRP 230VUC 1CO
2618050000
TERMSERIES, Relay module, Number of contacts:
1 CO contact AgNi, Rated control voltage: 230 V
UC ±10%, Continuous current: 6 A, PUSH IN
4050118670783
10 pc(s).
Creation date May 5, 2020 9:57:40 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
1
Data sheet
TERMSERIES
TRP 230VUC 1CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
6.4 mm
89.4 mm
87.8 mm
29.5 g
Width (inches)
Height (inches)
Depth (inches)
5-95% relative humidity,
Tu = 40°C, without
condensation
-40 °C
-40 °C
-40 °C...85 °C
Operating temperature, max.
Storage temperature, max.
Operating temperature
Connection cross-section AWG, min.
Type of conductor
Altitude
Rated current AC
Power rating
Pull-in/drop-out current, typ.
Protective circuit
Coil voltage of the replacement relay
Max. switching voltage, AC
Continuous current
AC switching capacity (resistive), max.
Switch-on delay
Min. switching power
1 CO contact (AgNi)
Mechanical service life
5 x 106 switching cycles
TS 35
No
V-0
Test button
Colour
No
black
0.252 inch
3.52 inch
3.457 inch
Temperatures
Humidity
Operating temperature, min.
Storage temperature, min.
Storage temperature
60 °C
85 °C
-40 °C...60 °C
Rated data UL
Ambient temperature (operational), max. 60 °C
Connection cross-section AWG, max.
AWG 14
Pollution severity level
2
AWG 26
rigid copper conductor,
flexible copper conductor
≤ 2000 m, above sea level
Input
Rated control voltage
Rated current DC
Pull-in/drop-out voltage, typ.
230 V UC ± 10 %
2.9 mA
164 V / 87 V AC
166 V / 89 V DC
Green LED
Status indicator
Coil voltage of the replacement relay
deviating from the rated control voltage Yes
3.5 mA
670 mW, 805 mVA
2.4 mA / 0.9 mA AC
1.8 mA / 0.4 mA DC
Rectifier
60 V DC
Output
Rated switching voltage
Max. switching voltage, DC
Inrush current
DC switching capacity (resistive), max.
Switch-off delay
250 V AC
250 V
20 A / 20 ms
144 W @ 24 V
≤ 50 ms
Max. switching frequency at rated load 0.1 Hz
250 V
6A
1500 VA
≤ 15 ms
1 mA @ 24 V, 10 mA @ 12
V, 100 mA @ 5 V
Contact data
Contact type
General data
Rail
Mechanical switch position indicator
UL 94 flammability rating
Creation date May 5, 2020 9:57:40 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
2
Data sheet
TERMSERIES
TRP 230VUC 1CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Insulation coordination
Rated voltage
Pollution severity
Dielectric strength, Input/Output
Dielectric strength of open contact
Impulse withstand voltage
300 V
2
4 kVeff / 1 Min.
1 kVeff / 1 min
6 kV (1.2/50 µs)
Surge voltage category
III
Protection degree
IP20
Creepage and clearance distance input –
output
≥ 5.5 mm
Dielectric strength to mounting rail
4 kVeff / 1 Min.
Further details of approvals / standards
Standards
Certificate no. (cULus)
EN 50178, EN 55011, EN
61000-6-1, 2, 4
E141197
Certificate No. (DNVGL)
TAA00001E5
Connection data
Wire connection method
Clamping range, rated connection
Clamping range, max.
Wire connection cross section AWG,
max.
Wire cross-section, solid, max.
PUSH IN
1.5 mm²
2.5 mm²
AWG 14
2.5 mm²
Wire connection cross section, finely
stranded, max.
2.5 mm²
Wire cross-section, finely stranded, max.
(AWG)
AWG 14
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max.
1.5 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), max.
1.5 mm²
Twin wire-end ferrules, max.
1 mm²
Stripping length, rated connection
Clamping range, min.
Wire connection cross section AWG,
min.
Wire cross-section, solid, min.
8 mm
0.14 mm²
0.14 mm²
Wire connection cross-section, finely
stranded, min.
0.14 mm²
Wire cross-section, finely stranded, min.
(AWG)
AWG 26
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min.
0.15 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), min.
0.15 mm²
Twin wire-end ferrules, min.
0.5 mm²
Blade size
0.4 x 2.0 mm
ETIM 7.0
eClass 9.1
EC001437
27-37-16-01
AWG 26
Classifications
ETIM 6.0
eClass 9.0
eClass 10.0
EC001437
27-37-16-01
27-37-16-01
Approvals
Approvals
Downloads
Approval/Certificate/Document of
Conformity
Engineering Data
User Documentation
EU Konformitätserklärung / EU Declaration of Conformity
STEP
Beipackzettel / Package Insert – multilingual
Creation date May 5, 2020 9:57:40 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
3
Data sheet
TERMSERIES
TRP 230VUC 1CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Wiring diagram
Graph
Graph
DC load limit curve
Resistive load
Dimensional drawing
Electrical service life230 V AC resistive load
230 V AC resistive load
Creation date May 5, 2020 9:57:40 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
4
Data sheet
TERMSERIES
TRP 230VUC 1CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Miscellaneous
Type codes
Creation date May 5, 2020 9:57:40 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
5