Data sheet
TERMSERIES
TRP 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Product image
Similar to illustration
TERMSERIES relay module, complete modules consisting
of
a relay and a base with AC/DC/UC coils,
available in different versions:
• With screw and tension-clamp connection
• AgNi contact, optionally with hard gold-plated contacts
• 1 and 2 COs
• Optionally with multiple-voltage input: 24...230 V UC
• With various protective circuits
in the input (free-wheel diode, RC element)
• Illuminated ejection lever
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
TRP 120VUC 2CO
2618570000
TERMSERIES, Relay module, Number of contacts:
2 CO contact AgNi, Rated control voltage: 120 V
UC ±10 %, Continuous current: 8 A, PUSH IN
4050118670264
10 pc(s).
Creation date May 6, 2020 6:22:54 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
1
Data sheet
TERMSERIES
TRP 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
12.8 mm
89.4 mm
87.8 mm
57.1 g
Width (inches)
Height (inches)
Depth (inches)
5-95% relative humidity,
Tu = 40°C, without
condensation
-40 °C
-40 °C
-40 °C...85 °C
Operating temperature, max.
Storage temperature, max.
Operating temperature
0.504 inch
3.52 inch
3.457 inch
Temperatures
Humidity
Operating temperature, min.
Storage temperature, min.
Storage temperature
60 °C
85 °C
-40 °C...60 °C
Rated data UL
Output current derating (ohmic)
Connection cross-section AWG, max.
Pollution severity level
6 A @ 60 °C, 8 A @ 50 °C
AWG 14
2
Connection cross-section AWG, min.
Type of conductor
Altitude
AWG 26
rigid copper conductor,
flexible copper conductor
≤ 2000 m, above sea level
Input
Rated control voltage
Rated current DC
Pull-in/drop-out voltage, typ.
Rated current AC
Power rating
Pull-in/drop-out current, typ.
Protective circuit
Coil voltage of the replacement relay
Max. switching voltage, AC
Continuous current
AC switching capacity (resistive), max.
Switch-on delay
Min. switching power
2 CO contact (AgNi)
Mechanical service life
30 x 106 switching cycles
TS 35
No
V-0
Test button
Colour
No
black
120 V UC ± 10 %
3.5 mA
83 V / 28 V AC
90 V / 22 V DC
Green LED
Status indicator
Coil voltage of the replacement relay
deviating from the rated control voltage Yes
3.5 mA
420 mVA / 420 mW
2.5 mA / 0.7 mA AC
2.6 mA / 0.58 mA DC
Rectifier
110 V DC
Output
Rated switching voltage
Max. switching voltage, DC
Inrush current
DC switching capacity (resistive), max.
Switch-off delay
250 V AC
250 V
15 A / 4 s
192 W @ 24 V
≤ 9 ms
Max. switching frequency at rated load 0.1 Hz
250 V
8A
2000 VA
< 11 ms
1 mA @ 24 V, 10 mA @ 10
V, 100 mA @ 5 V
Contact data
Contact type
General data
Rail
Mechanical switch position indicator
UL 94 flammability rating
Creation date May 6, 2020 6:22:54 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
2
Data sheet
TERMSERIES
TRP 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Insulation coordination
Rated voltage
Pollution severity
Dielectric strength, Input/Output
300 V
2
Dielectric strength of neighbouring
contacts
Dielectric strength to mounting rail
2.5 kVeff
4 kVeff / 1 Min.
1.2 kVeff / 5 s
Surge voltage category
III
Protection degree
IP20
Creepage and clearance distance input –
output
≥ 5.5 mm
Dielectric strength of open contact
1 kVeff / 1 min
Impulse withstand voltage
6 kV (1.2/50 µs)
Further details of approvals / standards
Standards
Certificate no. (cULus)
EN 50178, EN 55011, EN
61000-6-1, 2, 4
E141197
Certificate No. (DNVGL)
TAA00001E5
Connection data
Wire connection method
Clamping range, rated connection
Clamping range, max.
Wire connection cross section AWG,
max.
Wire cross-section, solid, max.
PUSH IN
1.5 mm²
2.5 mm²
AWG 14
2.5 mm²
Wire connection cross section, finely
stranded, max.
2.5 mm²
Wire cross-section, finely stranded, max.
(AWG)
AWG 14
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max.
1.5 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), max.
1.5 mm²
Twin wire-end ferrules, max.
1 mm²
Stripping length, rated connection
Clamping range, min.
Wire connection cross section AWG,
min.
Wire cross-section, solid, min.
8 mm
0.14 mm²
0.14 mm²
Wire connection cross-section, finely
stranded, min.
0.14 mm²
Wire cross-section, finely stranded, min.
(AWG)
AWG 26
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min.
0.15 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), min.
0.15 mm²
Twin wire-end ferrules, min.
0.5 mm²
Blade size
0.4 x 2.0 mm
ETIM 7.0
eClass 9.1
EC001437
27-37-16-01
AWG 26
Classifications
ETIM 6.0
eClass 9.0
eClass 10.0
EC001437
27-37-16-01
27-37-16-01
Approvals
Approvals
Downloads
Approval/Certificate/Document of
Conformity
Engineering Data
User Documentation
EU Konformitätserklärung / EU Declaration of Conformity
STEP
Beipackzettel / Package Insert – multilingual
Creation date May 6, 2020 6:22:54 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
3
Data sheet
TERMSERIES
TRP 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Wiring diagram
Graph
Graph
DC load limit curve
Resistive load
Dimensional drawing
Electrical service life230 V AC resistive load
230 V AC resistive load
Creation date May 6, 2020 6:22:54 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
4
Data sheet
TERMSERIES
TRP 120VUC 2CO
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Miscellaneous
Type codes
Creation date May 6, 2020 6:22:54 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
5