Data sheet
TERMSERIES
TOP 24VDC 48VDC0.1A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Product image
Similar to illustration
TERMSERIES complete solid-state relay modules 3 to 48
V DC 0.1 A output versions consisting of
a solid-state relay and a base with AC/DC/UC input;
available in different designs:
• With screw and tension-clamp connection
• In 6.4 mm width
• Optionally with multiple-voltage input: 24 to 230 V UC
• With various protective circuits
in the input (free-wheel diode, RC element)
• Illuminated ejection lever
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
TOP 24VDC 48VDC0.1A
2618790000
TERMSERIES, solid-state relais, 1 NO contact
(Bipolar transistor), Rated control voltage: 24 V
DC ±20 % , Rated switching voltage: 0…48 V DC,
Continuous current: 100 mA, PUSH IN
4050118670042
10 pc(s).
Creation date May 6, 2020 6:38:10 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
1
Data sheet
TERMSERIES
TOP 24VDC 48VDC0.1A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
6.4 mm
89.4 mm
87.8 mm
27 g
Width (inches)
Height (inches)
Depth (inches)
5-95% relative humidity,
Tu = 40°C, without
condensation
-20 °C
-40 °C
-40 °C...70 °C
Operating temperature, max.
Storage temperature, max.
Operating temperature
3,765 Years
Connection cross-section AWG, min.
Type of conductor
0.252 inch
3.52 inch
3.457 inch
Temperatures
Humidity
Operating temperature, min.
Storage temperature, min.
Storage temperature
60 °C
70 °C
-20 °C...60 °C
Probability of failure
MTTF
Rated data UL
Ambient temperature (operational), max. 60 °C
Connection cross-section AWG, max.
AWG 14
Pollution severity level
2
AWG 26
rigid copper conductor,
flexible copper conductor
Control side
Rated control voltage
Power rating
Cut-in / dropout current
Protective circuit
Coil voltage of the replacement relay
24 V DC ±20 %
280 mW
4.8 mA / 3.2 mA DC
Free-wheeling diode,
Reverse polarity protection
24 V DC
Nominal control current
Cut-in / dropout voltage
Status indicator
Coil voltage of the replacement relay
deviating from the rated control voltage
10 mA DC ±20 %
14.5 V / 11.5 V DC
Green LED
Continuous current
Switch-off delay
Leakage current
Short-circuit-proof
max. switching frequency (DC control
voltage)
100 mA
< 600 µs
< 10 µA
No
1 NO contact (Bipolar
transistor)
TS 35
V-0
Colour
No
Load side
Rated switching voltage
Switch-on delay
Voltage drop at max. load
Min. switching current
Protective circuit, load side
0…48 V DC
< 50 µs
≤1V
500 µA
Free-wheeling diode
300 Hz
Contact data
Contact type
General data
Rail
UL 94 flammability rating
black
Creation date May 6, 2020 6:38:10 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
2
Data sheet
TERMSERIES
TOP 24VDC 48VDC0.1A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Insulation coordination
Rated voltage
Surge voltage category
300 V
Pollution severity
Clearance and creepage distances for
control side - load side
Dielectric strength to mounting rail
Protection degree
DIN EN 50178
E141197
Certificate No. (DNVGL)
TAA00001E5
PUSH IN
1.5 mm²
Stripping length, rated connection
Clamping range, min.
Wire connection cross section AWG,
min.
Wire cross-section, solid, min.
8 mm
0.14 mm²
0.14 mm²
Wire connection cross-section, finely
stranded, min.
0.14 mm²
Wire cross-section, finely stranded, min.
(AWG)
AWG 26
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min.
0.15 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), min.
0.15 mm²
Twin wire-end ferrules, min.
0.5 mm²
Blade size
0.4 x 2.0 mm
ETIM 7.0
eClass 9.1
EC001504
27-37-16-04
III
Dielectric strength for control side - load
2.5 kVeff
side
Impulse withstand voltage
6 kV (1.2/50 µs)
2
≥ 5.5 mm
4 kVeff / 1 Min.
IP20
Further details of approvals / standards
Standards
Certificate no. (cULus)
Connection data
Wire connection method
Clamping range, rated connection
Clamping range, max.
Wire connection cross section AWG,
max.
Wire cross-section, solid, max.
2.5 mm²
AWG 14
2.5 mm²
Wire connection cross section, finely
stranded, max.
2.5 mm²
Wire cross-section, finely stranded, max.
(AWG)
AWG 14
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max.
1.5 mm²
Conductor cross-section, flexible, AEH
(DIN 46228-1), max.
1.5 mm²
Twin wire-end ferrules, max.
1 mm²
AWG 26
Classifications
ETIM 6.0
eClass 9.0
eClass 10.0
EC001504
27-37-16-04
27-37-16-04
Approvals
Approvals
Downloads
Approval/Certificate/Document of
Conformity
Engineering Data
Engineering Data
User Documentation
EU Konformitätserklärung / EU Declaration of Conformity
EPLAN
STEP
Beipackzettel / Package Insert – multilingual
Creation date May 6, 2020 6:38:10 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
3
Data sheet
TERMSERIES
TOP 24VDC 48VDC0.1A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Wiring diagram
Dimensional drawing
Creation date May 6, 2020 6:38:10 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
4
Data sheet
TERMSERIES
TOP 24VDC 48VDC0.1A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Miscellaneous
Type codes
Creation date May 6, 2020 6:38:10 PM CEST
Catalogue status 01.05.2020 / We reserve the right to make technical changes.
5