Data sheet
TFI-SERIES
TFIS 12-240VUC 2NO SD
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Product image
Timing relays are used in automation engineering in order
to compensate for malfunctions caused by high clock
rates.
Short pulses are extended and hence are reliably
identified by downstream control components.
Various timing functions such as make and break delays,
clock generator and star/delta switchover are available to
users.
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
TFIS 12-240VUC 2NO SD
2697270000
TFI-SERIES, Star-Delta Timer, Number of contacts:
2, NO contact, AgNi, Rated control voltage:
12...240 V UC -10 % / +10 %, Continuous
current: 3 A, Screw connection
4050118705270
1 pc(s).
Creation date September 17, 2020 11:18:12 PM CEST
Catalogue status 11.09.2020 / We reserve the right to make technical changes.
1
Data sheet
TFI-SERIES
TFIS 12-240VUC 2NO SD
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Height
Depth
Net weight
225 mm
67 mm
75 mm
83 g
Width (inches)
Height (inches)
Depth (inches)
5…95 % rel. humidity, no
condensation
-25 °C
-40 °C
-40 °C...70 °C
Operating temperature, max.
Storage temperature, max.
Operating temperature
8.858 inch
2.638 inch
2.953 inch
Temperatures
Humidity
Operating temperature, min.
Storage temperature, min.
Storage temperature
60 °C
70 °C
-25 °C...60 °C
Input
Rated control voltage
Status indicator
Setting tolerance
Min. pulse duration
Timing function
12...240 V UC - 10 % / +
10 %
LED green (U/t) flashes:
star-relay closed, time runs,
LED green (U/t) lights
permanently: delta-relay
closed, time runs, LED
yellow (R): star-relay closed
5%
100 ms
Star-delta start-up
Power rating
Repeat accuracy
500 mVA, 180 mW
< 0.5 % or ±5 ms
< 1 % (of scale-end value)
0.5 s - 10 s, 1.5 s - 30 s, 3
s - 60 s, 9 s - 180 s
Max. reset time after voltage interruption200 ms
Basic accuracy
Time ranges
Output
Rated switching voltage
Max. switching voltage, DC
AC switching capacity (resistive), max.
Min. switching power
250 V AC
30 V
750 VA
10 mA @ 12 V, 100 mA @
5V
Max. switching voltage, AC
Continuous current
DC switching capacity (resistive), max.
250 V
3A
90 W
Electrical service life, DC coil
100x103 switching cycles
(3 A at 250 VAC)
Contact data
Contact type
Mechanical service life
2 NO contact (AgNi)
20 x 106 switching cycles
General data
Rail
Mechanical switch position indicator
UL 94 flammability rating
TS 35
No
V-0
Test button
Colour
Resistance to vibration EN 61812-1
Surge voltage category
III
Protection degree
IP20
Creepage and clearance distance input –
output
≥ 3 mm
No
black
10 Hz...60 Hz: 0.15 mm,
60 Hz...150 Hz: 2 g
Insulation coordination
Rated voltage
Pollution severity
Dielectric strength, Input/Output
Impulse withstand voltage
300 V
2
1.6 kV
4 kV
Creation date September 17, 2020 11:18:12 PM CEST
Catalogue status 11.09.2020 / We reserve the right to make technical changes.
2
Data sheet
TFI-SERIES
TFIS 12-240VUC 2NO SD
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Further details of approvals / standards
Certificate no. (cULus)
E360862
Screw connection
1 Nm
0.5 mm²
8 mm
2.5 mm²
4 mm²
Stripping length, rated connection
Clamping range, rated connection
Clamping range, max.
Wire connection cross section AWG,
max.
Wire cross-section, solid, max.
Wire connection cross section, finely
stranded, max.
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, max.
Conductor cross-section, flexible, AEH
(DIN 46228-1), max.
Wire cross-section, finely stranded, two
clampable wires, max.
ETIM 7.0
eClass 9.1
EC001439
27-37-16-05
Connection data
Wire connection method
Tightening torque, max.
Clamping range, min.
Wire connection cross section AWG,
min.
Wire cross-section, solid, min.
Wire connection cross-section, finely
stranded, min.
Wire connection cross-section, finely
stranded with wire-end ferrules DIN
46228/4, min.
Conductor cross-section, flexible, AEH
(DIN 46228-1), min.
Wire connection cross section, finely
stranded, two clampable wires, min.
Blade size
AWG 20
0.5 mm²
0.5 mm²
0.5 mm²
0.5 mm²
0.5 mm²
size PH1
AWG 12
4 mm²
4 mm²
2.5 mm²
2.5 mm²
2.5 mm²
Classifications
ETIM 6.0
eClass 9.0
eClass 10.0
EC001439
27-37-16-05
27-37-16-05
Approvals
Approvals
ROHS
Conform
Downloads
Approval/Certificate/Document of
Conformity
Engineering Data
User Documentation
EU Konformitätserklärung / EU Declaration of Conformity
STEP
Beschreibung der Zeitfunktionen - Deutsch
Declaration of time functions - English
Beipackzettel / Package Insert – multilingual
Creation date September 17, 2020 11:18:12 PM CEST
Catalogue status 11.09.2020 / We reserve the right to make technical changes.
3
Data sheet
TFI-SERIES
TFIS 12-240VUC 2NO SD
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Wiring diagram
Dimensional drawing
Miscellaneous
Detailed drawing
Creation date September 17, 2020 11:18:12 PM CEST
Catalogue status 11.09.2020 / We reserve the right to make technical changes.
4
Data sheet
TFI-SERIES
TFIS 12-240VUC 2NO SD
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Graph
Time functions
Creation date September 17, 2020 11:18:12 PM CEST
Catalogue status 11.09.2020 / We reserve the right to make technical changes.
5
Data sheet
TFI-SERIES
TFIS 12-240VUC 2NO SD
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Drawings
Miscellaneous
Type codes
Creation date September 17, 2020 11:18:12 PM CEST
Catalogue status 11.09.2020 / We reserve the right to make technical changes.
6