Data sheet
DPADCV 0-10V
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Modules in the DPA SERIES are used for monitoring
limit values. They can be configured for a wide variety of
industrial signals and feature two relay contacts for the
alarm function on the output side.
A potentiometer on the front side is used to custom
adjust the setpoints and deadbands.
The deadband reduces chatter from the alarm relay
during switching operations.
The reset point of the relay contact is individually
adjusted, in this case away from the hysteresis (setpoint).
In order to generate an alarm in the event of a power
outage, you should select the "energised" operational
status for one or both of the output relays.
A high/low-trip switching behaviour can also be set
independently for each channel.
The following analogue input signals can be processed
with the current DPA SERIES: temperature (thermocouple
and PT100 temperature sensors), AC/DC currents
and voltages, measuring wire and potentiometer
positions, resistances, differential currents and differential
resistances.
The monitoring components are enclosed in a rugged railmountable
metal housing and feature complete isolation at 2 kV.
General ordering data
Type
Order No.
Version
GTIN (EAN)
Qty.
DPADCV 0-10V
7940011718
Signal converter/disconnector, 0...10 V or 1...5 V
4032248564354
1 pc(s).
Creation date December 20, 2013 10:27:38 PM CET
Catalogue status / We reserve the right to make technical changes.
1
Data sheet
DPADCV 0-10V
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Dimensions and weights
Width
Depth
Net weight
46 mm
120 mm
424 g
Height
Weight
97 mm
424 g
0...90 % (no condensation)
-25 °C...+70 °C
Operating temperature
0 °C...+60 °C
24 V DC ± 10 %
1 MΩ (0...10 V) or 500 kΩ
(1...5 V)
Type
Input signal
DC voltage [> 500 mV]
Hysteresis
1...25 % of max. input
value
Voltage input
TS 35, TS 32
± 0.05 % of signal range
24 V DC ± 10 %
Screw connection
Long-term drift
Power consumption
Step response time
Temperature coefficient
0.1 % / 10.000 h
3 W @ 24 V DC
typ. 5 ms
< 0.04 % / °C
DIN EN 61326
2 kV input / output /
power supply
Impulse withstand voltage
Standards
4 kV (1.2/50 µs)
EC001774
27-21-09-90
UNSPSC
eClass 7.1
30-21-18-01
27-21-09-90
Temperatures
Humidity
Storage temperature
Input
Supply voltage
Input resistance
0...10 V or 1...5 V
Settings
Fine adjustment
Switching thresholds
Potentiometer, 20 turns
0...100 % of max. input
value
General data
Input/Output
Mounting rail
Repeat accuracy
Supply voltage
Type of connection
Insulation coordination
EMC standards
Insulation voltage
DIN EN 50178
Classifications
ETIM 3.0
eClass 6.2
Product information
Descriptive text technical data
PE connection direct on enclosure
Approvals
Approvals
ROHS
Conform
Creation date December 20, 2013 10:27:38 PM CET
Catalogue status / We reserve the right to make technical changes.
2
Data sheet
DPADCV 0-10V
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Downloads
Declaration of Conformity
K_460_07_11.pdf
Creation date December 20, 2013 10:27:38 PM CET
Catalogue status / We reserve the right to make technical changes.
3
Data sheet
DPADCV 0-10V
Drawings
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Electric symbol
Creation date December 20, 2013 10:27:39 PM CET
Catalogue status / We reserve the right to make technical changes.
4
很抱歉,暂时无法提供与“7940011718”相匹配的价格&库存,您可以联系我们找货
免费人工找货