ECP130 Series
AC-DC Power Supplies
XP Power
130 Watts
• 100 W Convection/130 W Forced-cooled Ratings
• 2” by 3” Footprint
• Low 1.1” Profile
• High Efficiency, up to 95%
• Medical and ITE Approvals
• High Power Density
• Less than 0.5 W No Load Input Power
• 3 Year Warranty
The ECP130 series is designed to minimize the no load power consumption and maximize efficiency
Dimensions:
to facilitate equipment design to meet the latest environmental legislation. Approved for medical and
ECP130:
ITE applications, this range of single output AC-DC power supplies are packaged in a low profile
3.00 x 2.00 x 1.10” (76.2 x 50.8 x 28.0 mm)
1.1” height with a foot print of just 2” by 3”. The ECP130 provides up to 130 W force-cooled or |
100 W convection-cooled leading to very high power densities of 19.7 W/in3 or 15.1 W/in3 respectively.
The power supply contains two fuses and low leakage currents as required by medical applications and is safety approved to operate in a 70 °C
ambient. The low profile and safety approvals covering ITE and medical standards along with conducted emissions to EN55011/32 level B allow the
versatile ECP130 series to be used in a vast range of applications.
Models & Ratings
Output Current
Convection-cooled
Forced-cooled(1)
Output
Power
Output
Voltage
130 W
12.0 V
8.33 A
130 W
15.0 V
6.66 A
130 W
18.0 V
130 W
Efficiency(2)
Model Number(3)
10.83 A
93%
ECP130PS12
8.66 A
93%
ECP130PS15
5.55 A
7.22 A
93%
ECP130PS18
24.0 V
4.16 A
5.41 A
93%
ECP130PS24
130 W
28.0 V
3.57 A
4.64 A
93%
ECP130PS28
130 W
36.0 V
2.77 A
3.61 A
93%
ECP130PS36
130 W
48.0 V
2.08 A
2.70 A
93%
ECP130PS48
Notes
1. Requires 10 CFM.
2. Typical efficiency measured at full load and 230VAC input.
3. Add suffix ‘-S’ for input and output screw terminals e.g. ECP130PS24-S
Summary
Characteristic
Input Range
Minimum
Typical
Maximum
Units
Notes & Conditions
85
115/230
264
VAC
Derate load from 100% at 90 VAC to 85% at 85 VAC
0.5
W
%
230 VAC (see fig.1 & 2)
+70
°C
See derating curve (fig.3)
No Load Input Power
Efficiency
95
Operating Temperature
Safety Approvals
1
-30
ITE
IEC62368-1, UL62368-1, CSA 22.2 No.62368-1-11 Ed 2, EN62368-1, LVD
Medical
IEC60601-1 Ed 3.1 Including Risk Management, ANSI/AAMI ES60601-1 & CSA C22.2 No.6061-1:08, EN60601-1
www.xppower.com
ECP130 Series
AC-DC Power Supplies
XP Power
Input
Characteristic
Minimum
Typical
Maximum
Units
Notes & Conditions
85
115/230
264
VAC
Derate output from 100% at 90 VAC to 85% at 85 VAC
Input Frequency
47
50/60
63
Hz
Power Factor
0.8
Input Voltage - Operating
Input Current - Full Load
Inrush Current
Earth Leakage Current
1.3/0.65
A
115/230 VAC
120
A
230 VAC cold start, 25 ºC
115/230 VAC/50 Hz (Typ), 264 VAC/60 Hz (Max)
20/40
No load Input Power
Input Protection
Agency approval, 47-63 Hz
230 VAC, 100% load EN61000-3-2 class A
50
μA
0.5
W
F3.15 A/250 V Internal fuse fitted in line and neutral.
Output - Main Output
Characteristic
Minimum
Output Voltage
12
Typical
Initial Set Accuracy
Maximum
Units
Notes & Conditions
48
VDC
See Models and Ratings table
±1
%
50% load, 115/230 VAC
%
None
Output Voltage Adjustment
Minimum Load
0
Start Up Delay
Hold Up Time
2
10
15/11
A
No minimum load required
s
115/230 VAC full load.
ms
Min at full load, 115 VAC. Typical at 100W/ 130W
Drift
±0.02
%
After 20 min warm up
Line Regulation
±0.5
%
90-264 VAC
Load Regulation
±0.5
%
0-100% load.
Transient Response
4
%
Recovery within 1% in less than 500 μs
for a 50-75% and 75-50% load step
Over/Undershoot
7
%
Full load
Ripple & Noise
1
% pk-pk
Overvoltage Protection
110
140
%
Overload Protection
110
170
% I nom
0.02
%/˚C
Short Circuit Protection
95% (0 VAC), 8.3 ms
EN55035 (100 VAC)
EN55035 (240 VAC)
Dips and Interruptions
EN60601-1-2 (100 VAC)
EN60601-1-2 (240 VAC)
A
Dip 30% (70 VAC), 416 ms
A
Dip >95% (0 VAC), 4160 ms
Dip >95% (0 VAC), 10.0 ms
B
A
Dip 30% (168 VAC), 500 ms
A
Dip >95% (0 VAC), 5000 ms
B
Dip 100% (0 VAC), 10.0 ms
A
Dip 100% (0 VAC), 20 ms
A
Dip 60% (40 VAC), 100 ms
B
Dip 30% (70 VAC), 500 ms
A
Dip 100% (0 VAC), 5000 ms
B
Dip 100% (0 VAC), 10.0 ms
A
Dip 100% (0 VAC), 20 ms
A
Dip 60% (96 VAC), 100 ms
A
Dip 30% ( 168 VAC), 500 ms
A
Dip 100% (0 VAC), 5000 ms
B
www.xppower.com
Notes & Conditions
Performance criteria A
很抱歉,暂时无法提供与“ECP130PS12”相匹配的价格&库存,您可以联系我们找货