FCS60 Series
AC-DC Power Supplies
XP Power
60 Watts
• 60 W Convection Rating
• 2” by 4” Footprint
• Low 1.04” Profile
• High Efficiency
• Medical, ITE and Household Appliance Approvals
• Class I & Class II Installations
• High Power Density
• Less than 0.3 W No Load Input Power
• 3 Year Warranty
Dimensions:
The FCS60 series is designed to minimize the no load power consumption and maximize efficiency
to facilitate equipment design to meet the latest environmental legislation. Approved for medical and
FCS60:
ITE applications in either Class I or Class II installations, this range of single output AC-DC power supplies 2.00 x 4.00 x 1.04” (50.8 x 101.6 x 26.4 mm)
are packaged in a low profile 1.04” height with a foot print of just 2” by 4”. The FCS60 provides up to
60W convection-cooled and operates down to 80 VAC. The power supply features two AC line fuses and
low leakage currents required by medical applications. The low profile, low noise and safety approvals covering ITE and medical standards allows the
versatile FCS60 series to be used in a wide range of applications.
Models & Ratings
Output Power
60 W
60 W
60 W
60 W
60 W
60 W
Output Voltage
12.0 V
15.0 V
18.0 V
24.0 V
36.0 V
48.0 V
Output Current
5.00 A
4.00 A
3.33 A
2.50 A
1.67 A
1.25 A
Efficiency(1)
85%
85%
85%
85%
86%
86%
Model Number
FCS60US12
FCS60US15
FCS60US18
FCS60US24
FCS60US36
FCS60US48
Notes
1. Typical efficiency measured at full load and 230 VAC input.
Mechanical Details
4.0 (101.60)
3.75 (95.24)
ø0.134 (ø3.4)
thru in 4 positions
CON 1
Neutral
2
Line
1
2.0
(50.8)
CON 2
1
2
+VE
-VE
CN1 - Input Connector
Pin 1
Line
Pin 2
Not Fitted
Pin 3
Neutral
Mates with JST housing VHR-3N and JST
Series SVH-21T-P1.1 crimp terminals
Output Voltage
Adjustment
1.75
(44.4)
Mounting hole marked with
must be
connected to safety earth for class I
applications
0.125 (3.17)
0.125 (3.17)
CN2 - Output Connector
0.92
(23.4)
Notes
+Vout
Pin 2
-Vout
Mates with JST housing VHR-2N and JST
Series SVH-21T-P1.1 crimp terminals
0.12
(3.0)
1. All dimensions shown in inches (mm).
Tolerance: ±0.02 (0.5)
1
1.04
(26.4)
Pin 1
2. Weight: 0.25 lbs (112 g) approx.
www.xppower.com
FCS60 Series
AC-DC Power Supplies
XP Power
Summary
Characteristic
Minimum
Input Range
80
Typical
115/230
No Load Input Power
264
0.3
Efficiency
85
Operating Temperature
Safety Approvals
Maximum
Units
Notes & Conditions
VAC
Derate output from 100% at 90 VAC to 90% at 85 VAC and
80% at 80 VAC
W
%
230 VAC (see models and ratings table)
ITE
Medical
-25
+70
°C
See derating curve (fig.1)
IEC60950-1, IEC62368-1, EN62368-1, cUL62368-1
IEC60601-1 Ed 3.1 Including Risk Management, ANSI/AAMI ES60601-1 & CSA C22.2 No.6061-1:08, EN60601-1
Household
IEC60335-1
CE
Meets all applicable directives
UKCA
Meets all applicable legislation
Input
Characteristic
Minimum
Typical
Maximum
Units
Notes & Conditions
Derate output from 100% at 90 VAC to 90% at 85 VAC and
80% at 80 VAC
Input Voltage - Operating
80
115/230
264
VAC
Input Frequency
47
50/60
63
Hz
Power Factor
EN61000-3-2 class A
Input Current - Full Load
0.9/0.5
A
115/230 VAC
264 VAC cold start, 25 ºC
264 VAC/60 Hz
Inrush Current
60
A
Earth Leakage Current
270
μA
0.3
W
No load Input Power
Input Protection
Agency approval, 47-63 Hz
T3.15 A/250 A, 250 V Internal fuse fitted in line and neutral.
Output - Main Output
Characteristic
Minimum
Output Voltage
12
Typical
Initial Set Accuracy
Output Voltage Adjustment
Minimum Load
Units
Notes & Conditions
48
VDC
See Models and Ratings table
±1
%
±10
A
1
Output Rise Time
50% load, 115/230 VAC
%
0
Start Up Delay
Hold Up Time
Maximum
2
50
No minimum load required
s
ms
8.3/20
ms
Min at full load 115/230 VAC
Line Regulation
±0.5
%
90-264 VAC
Load Regulation
1
%
0-100% load.
Transient Response
4
%
Recovery within 1% in less than 500 μs
for a 50-75% and 75-50% load step
Over/Undershoot
5
%
Full load
Ripple & Noise
1.0
% pk-pk
20 MHz bandwidth
Overvoltage Protection
115
140
%Vnom
Continuous trip and restart (hiccup)
Overload Protection
110
160
% I nom
0.05
%/˚C
Maximum
Units
Short Circuit Protection
Continuous trip and restart (hiccup)
Temperature Coefficient
General
Characteristic
Minimum
Efficiency
Isolation: Input to Output
Input to Ground
Output to Ground
Typical
85
%
4000
VAC
2 MOPP
1500
VAC
1 MOPP
500
VAC
1 MOPP at output voltage
Power Density
Mean Time Between Failure
Weight
Notes & Conditions
115/230 VAC 100% load
7.2
500
W/in3
kHrs
0.25 (112)
MIL-HDBK-217F, Notice 2 +25 °C GB
lb(g)
www.xppower.com
2
FCS60 Series
AC-DC Power Supplies
XP Power
Environmental
Characteristic
Maximum
Units
Operating Temperature
Minimum
-25
+70
°C
Storage Temperature
-40
+85
°C
95
%RH
5000/4000
m
Humidity
Typical
5
Operating Altitude
Notes & Conditions
See derating curve, fig.1
Non-condensing
ITE/Medical
Shock
±3 x 30g shocks in each plane, total 18 shocks. 30g = 11ms (+/- 0.5msecs), half sine. Conforms to EN60068-2-27
Vibration
Single axis 10-500 Hz at 2g sweep and endurance at resonance in all 3 planes. Conforms to EN60068-2-6
Temperature Derating Curve
Figure 1
Output Load (W)
50
25
Some specification parameters
may not be met
60
0
-25 -20
0
+40 +50
Ambient Temperature (ºC)
+70
Notes