Low Volt Disconnect Module Up To 30 A LVD Series
•
THE XPERTS IN POWER
Up To 30 A Maximum Current • Deep Discharge Pre-Warning Alarm • Din Rail Mounting • Automatic Reset • 12, 24 & 48 VDC
Specification
Input
Operating Voltage Range • -25% to +30% output voltage
Environmental
Operating Temperature Storage Temperature Humidity • • • 0 °C to +50 °C (40 °C ambient plus +10 °C rise inside enclosure) -40 °C to +85 °C 90% non-condensing
Output
LVD Relay Contacts • 1 pole changeover - See Table for current rating -35 to +10% output voltage (user adjustable) -35 to +10% output voltage (user adjustable)
LVD Alarm Set Range • Pre-Warning Disconnect •
LVD SERIES Output Voltage Output Current 30 A 20 A 10 A Model Number LVD12 LVD24 LVD48
General
Alarm Relay Contacts • Screw Terminal Sizes • 1 pole changeover, 1 A 24 VDC Input - suitable for 1.0 mm2 cable, LVD - suitable for 2.5 mm2 cable, Alarms - suitable for 1mm2 cable DIN Rail
12 V 24 V 48 V
Mounting
•
Mechanical Details
SCHEMATIC PSU
F1
F2
LVD
NOTES: 1. All dimensions in mm. 2. Weight 0.11 Kg. 3. Alarm contacts shown in de-energised state.
NOTE: F2 - Max Rating 20 A
•
•
www.xpplc.com
sales@xpplc.com
Rev 2.0
很抱歉,暂时无法提供与“LVD24”相匹配的价格&库存,您可以联系我们找货