AC-DC
175 Watts RCL175 Series
• • • • • • • 200 W Peak Rating
xppower.com
Up to 120 W Convection-cooled Industrial and Medical Approvals Low Leakage Current Class I & Class II Applications Flexible Design for Modified Standards Connector & Mechanical Options
Specification
Input
Input Voltage Input Frequency Input Current • 85-264 VAC (120-370 VDC) See note 3 • 47-63 Hz • 2.1 A max at 115 VAC 0.9 A max at 230 VAC Inrush Current • 17 A max at 115 VAC, 35 A max at 230 VAC, cold start at +25 °C Power Factor • Complies with EN61000-3-2 for Class A equipment Earth Leakage Current • 120 µA max at 115 VAC 200 µA max at 230 VAC Input Protection • 3.15 A line and neutral fused
General
Efficiency Isolation • 80-90% depending on model • 4000 VAC Input to Output 1500 VAC Input to Ground 1500 VAC Output to Ground open frame (For BF applications, consult sales office) 500 VAC Output to Ground U channel & covered • PFC 75 kHz typical, PWM 60 kHz typical • Power fail - open collector output referenced to 0 V sense • See Application Notes • See Application Notes • 385 kHrs typical at +25 °C per MIL-HDBK-217F
Switching Frequency Signals Remote Sense Remote On/Off MTBF
Output
Output Voltage Output Voltage Trim • See models and ratings table • ±10% output 1 via pot, outputs 2-4 track by same percentage Initial Set Accuracy • ±2% of nominal at 50% load Minimum Load • See models & ratings table Start Up Delay •