The SMP350 series provides a range of rugged, enclosed, 300 – 350W supplies with integral fan,
screw terminal connections and a wide operating temperature range of -40 °C to +70 °C ideally
suited to a wide range of industrial applications. The SMP350 series features high efficiency and class
B EMI emissions for ease of integration into the end application and offers remote On/Off to simplify
system control. Packaged in a 3.6” x 7” x 1.7” enclosure the series offers power densities up to 13
W/in3 providing a compact, high efficiency, low noise power solution.
Dimensions:
SMP350:
3.6 x 7.0 x 1.7” (91.4 x 177.8 x 43.1 mm)
Models & Ratings
Output Voltage V1
12.0 VDC
15.0 VDC
18.0 VDC
24.0 VDC
28.0 VDC
36.0 VDC
48.0 VDC
90-180 VAC
Output Current
Output Power
25.00 A
300 W
20.70 A
310 W
17.80 A
320 W
13.75 A
330 W
11.80 A
330 W
9.20 A
330 W
7.30 A
350 W
180-264 VAC
Output Current
Output Power
25.00 A
300 W
22.00 A
330 W
19.40 A
350 W
14.60 A
350 W
12.50 A
350 W
9.70 A
350 W
7.30 A
350 W
Model Number(1)
SMP350PS12
SMP350PS15
SMP350PS18
SMP350PS24
SMP350PS28
SMP350PS36
SMP350PS48
Notes
1. For reduced leakage current medical versions (125 W
90 VAC, 100% load
115 VAC/230 VAC when inhibited
230 VAC, cold start 25 °C
264 VAC/60 Hz. For reduced leakage current medical
versions (4
%
150
140
%
%
Trip and Restart
Cycle AC to reset
Thermal protection fitted
%/°C
s
%
After 20 minute warm up
115/230 VAC, full load
4 V to switch on
0.02
1
5
General
Characteristic
Efficiency
Isolation: Input to Output
Input to Ground
Output to Ground
Switching Frequency
Mean Time Between Failure
Power Density
Weight
Minimum
Typical
Maximum
Units
Notes & Conditions
87
4000
1500
1500
60
90
90
93
%
VAC
VAC
VAC
See figures 2 – 4 below
2 x MOPP
1 x MOPP
1 x MOPP
PFC
Main Converter
MIL-HDBK-217F, notice 2, +25 °C GB
200
150
kHz
13
kHrs
W/in3
lb (kg)
570
1.5 (0.68)
www.xppower.com
2
SMP350 Series
AC-DC Power Supplies
Efficiency Vs Load
Figure 2
100
12 V Models
Efficincy
E (%)
95
115VAC
90
230VAC
85
7
80
75
70
25
50
75
100
Load (%)
Figure 3
100
24 V Models
Efficiency (%)
95
90
115VAC
85
230VAC
80
1
75
70
25
50
7
Figure 4
100
L
100
48 V Models
75
Load (%)
Efficiency (%)
95
90
85
115VAC
80
230VAC
1
75
70
25
50
75
100
Load (%)
Environmental
Characteristic
3
Minimum
Typical
Maximum
Units
Operating Temperature
-40
+70
°C
°C
Notes & Conditions
Derate linearly above 50 °C to 50% of rated power at
70 °C, see fig 5
Storage Temperature
-40
+85
Operating Humidity
5
95
%
RH, non-condensing
Storage Humidity
5
95
%
RH, non-condensing
Shock
±3 x 30 g shocks in each plane, total 18 shocks. 30 g = 11 ms (±0.5 ms), half sine. Conforms to EN60068-2-27 & EN60068-2-47
Vibration
Single axis 10-500 Hz at 2 g sweep and endurance at resonance in all 3 plans. Conforms to EN60068-2-6
www.xppower.com
SMP350 Series
AC-DC Power Supplies
Thermal Derating Curve
Figure 5
50
0
-40
Some specification
parameters may not be met
Output Load (%)
100
-20
0
50
Ambient Temperature (ºC)
70
Signals & Controls
Notes & Conditions
Characteristic
Remote Sense
Compensates for 0.5 V total voltage drop
Inhibit
Remote On/Off (-R models)
(Standard on GCS350 models)
Enable
The inhibit lo (pin 4), should be pulled below 0.4 V to switch V1 & Vfan off. Open circuit or >4 V to
switch on (see fig. 6)
With the inhibit lo (pin 4) pulled low as detailed above, connecting inhibit hi (pin 5) to inhibit lo (pin 4)
will enable V1 & V fan output. (see fig. 7)
Remote On/Off (Inhibit)
Remote On/Off (Enable)
Figure 6
Figure 7
POWER SUPPLY
POWER SUPPLY
Inhibit Hi
Pin 5
Inhibit Lo
Pin 4
Inhibit Lo
Pin 4
0V
0V
Signals Connector
Signals Connector
44
P
www.xppower.com
SMP350 Series
AC-DC Power Supplies
EMC: Emissions
Standard
Test Level
EN55011/32
Class B
Radiated
EN55011/32
Class A
Harmonic Fluctuations
EN61000-3-3
Phenomenon
Conducted
Criteria
Notes & Conditions
Notes & Conditions
EMC: Immunity
Phenomenon
Low Voltage PSU EMC
Standard
Test Level
Criteria
EN61204-3
High severity level
as below
Class A
All models
Harmonic Current
EN61000-3-3
Radiated
EN61000-4-3
3
A
EFT
EN61000-4-4
3
A
Surges
EN61000-4-5
Installation class 3
A
Conducted
EN61000-4-6
3
Dip 100% (0 VAC), 8.4ms
Dip 100% (0 VAC), 16.7ms
A
A
B
EN61000-4-11
(100 VAC)
Dip 60% (40 VAC), 200ms
B
Dip 30% (70 VAC), 500ms
B
Dip 20% (80 VAC), 5000ms
B
Int 100% (0 VAC), 5000ms
B
EN61000-4-11
(240 VAC)
Dips and Interruptions
EN60601-1-2
(100 VAC)
EN60601-1-2
(240 VAC)
SEMI F47 (100 VAC)
Class C
> 125 W
Dip 100% (0 VAC), 10ms
A
Dip 100% (0 VAC), 20ms
B
Dip 60% (96 VAC), 200ms
B
Dip 30% (168 VAC), 500ms
B
Dip 20% (192 VAC), 5000ms
B
Int 100% (0 VAC), 5000ms
B
Dip 100% (0 VAC), 10ms
A
Dip 60% (40 VAC), 100ms
A
Dip 30% (70 VAC), 500ms
A
Int 100% (0 VAC), 5000ms
B
Dip 100% (0 VAC), 10ms
A
Dip 60% (96 VAC), 100ms
A
Dip 30% (168 VAC), 500ms
A
Int 100% (0 VAC), 5000ms
B
Dip 33% (70 VAC), 500ms
A
Derate Power to 150 W
Safety Approvals
Safety Agency
CB Report
UL
TUV
Notes & Conditions
Information Technology
IEC62368-1 Ed 2
Information Technology
IEC60601-1 Ed 3 Including Risk Management
Medical
UL62368-1, CSA C22.2 No. 62368-1
Information Technology
ANSI/AAMI ES60601-1:2005 & CSA C22.2, No.60601-1:08
Medical
EN62368-1
Information Technology
EN60601-1/2006
Medical
CE
LVD & RoHS
Equipment Protection Class
Class I
See safety agency conditions of acceptibility for details
Means of Protection
Category
Primary to Secondary
5
Safety Standard
IEC60950-1:2005 Ed 2
2 x MOPP (Means of Patient Protection)
Primary to Earth
1 x MOPP (Means of Patient Protection)
Secondary to Earth
1 x MOPP (Means of Patient Protection)
IEC60601-1 Ed 3
www.xppower.com
SMP350 Series
AC-DC Power Supplies
Mechanical Details
0.12
(3.0)
7.0 (177.8)
Terminal Block TB1
7 x M3 Screw
0.28 (7.1)
0.33
(8.4)
3.6
(91.4)
Voltage
Adjust
0.59 (15.0)
0.32 (8.1)
2 x M3 x 0.5 THD
0.16 (4.0) max
screw penetration
1.70
(43.2)
1.09 (27.6)
1.20 (30.5)
0.58
(14.7)
5.35 (135.9)
1.20
(30.5)
5.35 (135.9)
2 x M3 x 0.5 THD
0.16 (4.0) max
screw penetration
2.44
(62.0)
Notes
1. All dimensions in inches (mm).
2. Tolerance .xx = ±0.02 (0.50); .xxx = ±0.01 (0.25)
3. Weight: 1.5 lbs (0.68 kg)
4. J4 mates with JST Housing Pn. PHDR-10VS and with JST SPHD-001T-P0.5 crimp terminals.
66
www.xppower.com
Terminal Block TB1
Pin
Function
1
Line
2
Neutral
3
Ground
4
+V1
5
+V1
6
-V
7
-V
Signal Connector J4
JST PN B10B-PHDSS
Pin
Function
1
+Sense
2
-Sense
3
XP Internal Use
4
Inhibit LO
5
Inhibit HI
6
N/C
7
N/C
8
N/C
9
N/C
10
N/C
02 Oct 17
很抱歉,暂时无法提供与“SMP350PS28”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 1+1032.67774
- 10+1011.16275
- 50+989.46032
- 国内价格 香港价格
- 1+918.324991+113.91779
- 5+890.768405+110.49941
- 10+863.2201010+107.08206
- 25+826.4767325+102.52406
- 100+771.36271100+95.68719