UCH600 Series
AC-DC Power Supplies
600 Watts
• Convection cooled
• Medical and ITE approvals
• Compact 5.0” by 8.0” footprint
• Suitable for BF applications
• 5 V standby and remote on/off
• 12 V fan output
• -20 °C to +70 °C operation
• High efficiency, up to 95%
Approved for medical and ITE applications, this range of convection cooled single output
AC/DC power supplies are packaged in an ultra compact foot print of just 5.0” by 8.0”.
The UCH600 provides up to 600 W convection-cooled leading to very high power density
of 9.5 W/in3.
Dimensions:
UCH600:
8.00 x 5.00 x 1.57” (203.2 x 127.0 x 40.0 mm)
A 12 V/0.6 A fan supply is included in the design to faciliate system cooling, if required, along with 5 V/1 A standby output. The power
supply contains two fuses and low leakage currents as required by medical applications and is safety approved to operate in a 70 °C
ambient. The low profile and safety approvals covering ITE and medical standards along with conducted emissions to EN55011/22 level B
allow the versatile UCH600 series to be used in a vast range of applications.
Models & Ratings
Output
Voltage
Output Current
12.0 V
50.0 A
24.0 V
25.0 A
36.0 V
16.6 A
48.0 V
12.5 A
Standby Output
Fan Output(2,4
5 V/1.0 A
5 V/1.0 A
5 V/1.0 A
5 V/1.0 A
Efficiency(1)
Model Number
12 V/0.6 A
93%
UCH600PS12
12 V/0.6 A
95%
UCH600PS24
12 V/0.6 A
95%
UCH600PS36
12 V/0.6 A
95%
UCH600PS48
Notes
1. Typical efficiencies measured at 100% load and 230 VAC input.
2. Typical voltage, actual regulated voltage will be in range of 11.4V to 12.6V.
3. Regulation of the fan output requires a minimum load of 10W on the main output.
Input
Characteristic
Minimum
Typical
Maximum
Units
Input Voltage - Operating
90
115/230
264
VAC
Input Frequency
47
50/60
63
Hz
Power Factor
Input Current - Full Load
>0.9
Earth Leakage Current
No load Input Power
Input Protection
1
230 VAC, 100% load. EN61000-3-2 class A, class C >150W
6.0/3.0
Inrush Current
80/140
Notes & Conditions
A
115/230 VAC
60
A
300
µA
230 VAC cold start, 25 ºC
115/230 VAC/50 Hz (Typ), 264 VAC/60 Hz (Max)
1.5
W
When main output is Inhibited
F12A/250 V Internal fuse fitted in line and neutral.
www.xppower.com
UCH600 Series
AC-DC Power Supplies
Output - Main Output
Characteristic
Minimum
Output Voltage - V1
Typical
12
Initial Set Accuracy
Minimum Load
Maximum
Units
Notes & Conditions
48
VDC
See Models and Ratings table
±1
%
50% load, 115/230 VAC
A
No minimum load required
s
115/230 VAC full load.
0
Start Up Delay
2
Hold Up Time
10
ms
Min at full load, 115 VAC.
Drift
±0.02
%
After 20 min warm up
Line Regulation
±0.5
%
90-264 VAC
Load Regulation
±0.5
%
0-100% load.
%
Recovery within 1% in less than 500 µs
for a 50-75% and 75-50% load step
%
Full load
Transient Response
4
Over/Undershoot
5
Ripple & Noise
1.5/1
20 MHz bandwidth and 47 µF electrolytic capacitator in
parallel with 0.1 µF ceramic capacitator. 12V/other models.
% pk-pk
Overvoltage Protection
110
130
%
Overload Protection
110
130
% I nom
0.02
%/ ˚C
50
µA
Maximum
Units
Vnom, recycle input to reset
Short Circuit Protection
Trip & Restart
Temperature Coefficient
Overtemperature Protection
Measured internally, Auto Resetting
Output Leakage Current
264 VAC / 60 Hz
Output - 5 V Standby Output
Characteristic
Minimum
Output Voltage
Typical
5.0
Initial Set Accuracy
Minimum Load
±1
%
0
50% load, 115/230 VAC
A
Start Up Delay
Hold Up Time
Notes & Conditions
VDC
0.5
s
500
115/230 VAC full load.
ms
Min at full load, 115 VAC.
After 20 min warm up
Drift
±0.02
%
Line Regulation
±0.5
%
90-264 VAC
Load Regulation
1
%
0-100% load.
Transient Response
4
%
Recovery within 1% in less than 500 µs
for a 50-75% and 75-50% load step
Over/Undershoot
5
%
Full load
Ripple & Noise
2
% pk-pk
2.0
A
0.02
%/˚C
Overload Protection
20 MHz bandwidth and 10 µF electrolytic capacitator in
parallel with 0.1 µF ceramic capacitator
Short Circuit Protection
Trip & Restart
Temperature Coefficient
Remote On/Off
Connect Pin 3 CN202 to Pin 2 CN202 to inhibit
General
Characteristic
Minimum
Efficiency
Isolation: Input to Output
Input to Ground
Output to Ground
Switching Frequency
Typical
Maximum
95
%
230 VAC Full load (see fig. 1 & 2)
VAC
2 x MOPP
1500
VAC
1 x MOPP
1500
VAC
1 x MOPP
PFC, Variable
37
120
kHz
76
106
kHz
Main converter, Variable
kHz
5V standby output
Power Density
Weight
Notes & Conditions
4000
100
Mean Time Between Failure
Units
9.5
W/in3
300
kHrs
2.43 (1.1)
lb (kg)
www.xppower.com
MIL-HDBK-217F, Notice 2 +25 °C GB
2
UCH600 Series
AC-DC Power Supplies
Efficiency Vs Load
Figure 1 - UCH600PS12
100%
Efficiency
90%
80%
110VAC input
70%
230VAC input
60%
50%
10
20
30
40
50
60
70
80
90
100
Load (%)
Figure 2 - UCH600PS24
100%
Efficiency
90%
80%
110VAC input
70%
230VAC input
60%
50%
10
20
30
40
50
60
70
80
90
100
Load (%)
Environmental
Characteristic
Maximum
Units
Notes & Conditions
Operating Temperature
Minimum
-20
Typical
+70
°C
See derating curve
Storage Temperature
-40
+80
°C
5
95
%RH
5000/4000
m
Cooling
Humidity
Convection cooled
Operating Altitude
Shock
±3 x 30g shocks in each plane, total 18 shocks. 30g = 11ms (+/- 0.5msecs), half sine. Conforms to EN60068-2-27
Vibration
Single axis 10-500 Hz at 2g sweep and endurance at resonance in all 3 planes. Conforms to EN60068-2-6
Temperature Derating Curves
Figure 3
Output Load (W)
600
300
0
-20
0
+50
Ambient Temperature (ºC)
3
Non-condensing
ITE/Medical
www.xppower.com
+70
UCH600 Series
AC-DC Power Supplies
EMC: Emissions
Phenomenon
Conducted
Radiated
Standard
Test Level
EN55011/32
Class B
EN55011/32
Class B
Harmonic Current
EN61000-3-2
Class A
Voltage Functions
EN61000-3-3
Criteria
Notes & Conditions
Class C for Load >150W
EMC: Immunity
Standard
Test Level
Criteria
IEC60601-1-2
Ed.4.0 : 2014
as below
as below
Phenomenon
Medical Device EMC
Low Voltage PSU EMC
EN61204-3
High severity level
ESD
EN61000-4-2
4
A
Radiated
EN61000-4-3
3
A
A
EFT
EN61000-4-4
3
Surges
EN61000-4-5
Installation class 3
A
Conducted
EN61000-4-6
3
A
Magnetic Fields
EN61000-4-8
4
A
EN55024 (100 VAC)
EN55024 (240 VAC)
Dips and Interruptions
EN60601-1-2 (100 VAC)
Dip >95% (0 VAC), 8.3 ms
A
Dip 30% (70 VAC), 416 ms
B
Dip >95% (0 VAC), 4160 ms
Dip >95% (0 VAC), 10.0 ms
B
±8kV contact, ±15kV air
A
Dip 30% (168 VAC), 500 ms
A
Dip >95% (0 VAC), 5000 ms
B
Dip 100% (0 VAC), 20 ms
B
Dip 100% (0 VAC), 10.0 ms
A
Dip 60% (40 VAC), 100 ms
B
Dip 30% (70 VAC), 500 ms
B
Dip 100% (0 VAC), 5000 ms
B
Dip 100% (0 VAC), 20 ms
B
Dip 100% (0 VAC), 10.0 ms
EN60601-1-2 (240 VAC)
Notes & Conditions
A
Dip 60% (96 VAC), 100 ms
A
Dip 30% ( 168 VAC), 500 ms
A
Dip 100% (0 VAC), 5000 ms
B
Safety Approvals
Safety Agency
Safety Standard
Notes & Conditions
CB Report
IEC60950-1, IEC62368
Information Technology
UL
UL62368-1
Information Technology
TUV
EN62368-1
Information Technology
CE
LVD
Safety Agency
Safety Standard
Notes & Conditions
CB Report
IEC60601-1 Ed 3.1 Including Risk Management
Medical
UL
ANSI/AAMI ES60601-1 & CSA C22.2 No.60601-1:08
Medical
TUV
EN60601-1
Medical
Isolation
Level
Notes & Conditions
Primary to Secondary
2 x MOPP (Means of Patient Protection)
Primary to Earth
1 x MOPP (Means of Patient Protection)
Secondary to Earth
1 x MOPP (Means of Patient Protection)
IEC60601-1 Ed 3.1
www.xppower.com
4
UCH600 Series
AC-DC Power Supplies
Mechanical Details
7.60 (193.2)
1.57
(40.0)
0.19 (5.0)
0.78 (20.0)
M3 x 0.5 screw hole (4x)
8.0 (203.2)
1.57 (40)
CN3
+
+
JP2
+
+
+
RT1
+
VO-
VO-
L4
RF1
C37
T3
VO-
VO-
5.0
(127)
G
D
Q5
w
+
S
+
D
S
+
VO+
VO+
G
x
VO+
VO+
+
N
L
N
L
y
C5
-
CN2
J1
7
CN1, 3 pin
barrier
terminal
block
9.5mm
pitch.
VO+
+
R148
CN1
+
1
1
3 1
J3
3
Remote On/Off
DC Return
5VSB
0.79
(20.0)
CN202
CN2 12V version
6 pin barrier
terminal block,
9.5mm pitch.
7.8 (198.2)
0.197
(5.0)
CN2 other models
4 pin barrier
terminal block,
9.5mm pitch.
M3 x 0.5 screw hole (4x)
7.33 (186.2)
0.6 (15.2)
CN3 - Fan Connector
Pin 1
Pin 2
Fan+
Fan-
Mates with JST housing PHR-2
4.34
(110.3)
3.8
(96.6)
CN202 - Signal Connector
Pin 1
Pin 2
Pin 3
7.33 (186.2)
+5V Standby
DC Return
Remote On/Off
Mates with JST housing XHP-3
0.6 (15.2)
0.197 (5.0)
0.47 (12)
0.32 (8.2)
To turn output off, connect
Remote On/Off, Pin 3 to Return,
Pin 2.
Output is on if Remote On/Off,
Pin 3 is floating or connected to
5V standby, Pin 1.
Notes
1. All dimensions shown in inches (mm).
Tolerance: ±0.02 (0.5)
5
2. Weight: 2.43 lbs (1100 g) approx.
3. Maximum screw penetration 0.1 (2.5)
www.xppower.com
UCH600 Series
AC-DC Power Supplies
Thermal Considerations
In order to ensure safe operation of the PSU in the end-use equipment, the temperature of the components listed in the table below must
not be exceeded. Temperature should be monitored using K type thermocouples placed on the hottest part of the component
(out of direct air flow). See Mechanical Details for component locations.
Temperature Measurements (At Maximum Ambient)
Max Temperature °C
110°C
120°C
Component
T3 Coil
L4 Coil
Q5 Body
C5
C37
120°C
105°C
105°C
Service Life
The estimated service life of the UCH600 is determined by the cooling arrangements and load conditions experienced in the end application.
Due to the uncertain nature of the end application this estimated service life is based on the actual measured temperature of a key capacitor
with in the product when installed by the end application,
The graph below expresses the estimated lifetime of a given component temperature and assumes continuous operation at this temperature.
Estimated Service Life vs Component Temperature
Figure 4
80000
70000
60000
Lifetime (Hrs)
50000
40000
C37
C5
85
75
30000
20000
10000
0
105
95
65
55
45
C5 + C37 Temperature (ºC)
6
www.xppower.com
27 Feb 20