39 SERIES
MasterINTERFACE - Relay interface modules
Common features
• Space saving 6.2 mm wide
• Connections for 16-way jumper link
• Integral coil indication and protection circuit
• Secure retention and easy ejection by plastic
clip
• Dual screw head (blade+cross) terminals and
Push-in terminals versions
• 35 mm rail mounting (EN 60715)
MasterBASIC
39
SERIES
EMR
Electromechanical Relays
SSR
Solid State Relays
• 1 CO 6 A/250 V AC
• High switching capability
• 1 solid state output (options 0.1 A/48 V DC,
2 A/24 V DC, 2 A/240 V AC)
• Silent, high speed switching, long electrical life
39.11/39.01
B
39.10/39.00
• For general use in any type of system
• EMR: 6 to 24 and 125 V AC/DC,
230 V AC upply
• SSR: 6 to 24 V DC, 125 V AC/DC,
230 V AC supply
• Screw terminal and Push-in terminal
MasterBASIC - EMR ATEX
• Available on request - See page 14
MasterPLUS
• Accepts the output fuse module, for the easy
Page 4
39.31 - 39.31.3/39.61 - 39.61.3
Page 5
39.30 - 39.30.3/39.60 - 39.60.3
and space efficient protection of output circuits
• EMR: 6 to 125 V AC/DC, 125 and 220 V DC,
230 V AC and 24…240 V AC/DC supply
• SSR: 24 - 125 V AC/DC, 6 to 220 V DC,
230 V AC and 24…240 V AC/DC supply
• Special 125 V AC/DC and 230 V AC leakage
current suppression types (39.31.3, 39.61.3
EMR and 39.30.3, 39.60.3 SSR)
• Screw terminal and Push-in terminal
MasterINPUT
• Jumper link option for the quick and easy
Page 6
39.41/39.71
Page 7
39.40/39.70
distribution of supply voltage to proximity
switches and similar input devices
• EMR: 6 to 24 V and 125 V AC/DC,
230 V AC supply
• SSR: 6 - 24 V DC, 24 - 125 V AC/DC,
230 V AC supply
• Screw terminal and Push-in terminal
Page 9
Page 8
MasterOUTPUT
• Jumper link option for the quick and easy
39.21/39.51
39.20/39.50
distribution of supply voltage to output side
and its connection to electromagnetic valves
and similar output devices
• EMR: 6 to 24 V and 125 V AC/DC,
230 V AC supply
• SSR: 6 to 24 V DC, 125 V AC/DC,
230 V AC supply
• Screw terminal and Push-in terminal
MasterTIMER
• Timer adjustment via top mounted rotary knob
Page 11
Page 10
39.81/ 39.91
39.80/39.90
accessible after assembly
VII-2016, www.findernet.com
• Control signal terminal
• DIP-switch for selection of 4 time scales and
8 functions
• Output with fuse module option
• EMR and SSR: 12 to 24 V AC/DC supply
• Screw terminal and Push-in terminal
Page 12
Page 13
39
SERIES
39 SERIES
Typical applications
MasterBASIC
39.11 - 39.10 - 39.01 - 39.00
MasterPLUS
39.31 - 39.30 - 39.31.3 - 39.30.3 - 39.61 - 39.60 - 39.61.3 - 39.60.3
• For general interface use in any type of system • This special version provides extra protection for the output circuit thanks to the replaceable fuse
and application.
• Can be used for input interface applications
between auxiliary contacts, sensors etc. and
controllers, PLC's or motors. Or for output
interface between PLC's controllers and relays,
solenoids etc.
B
Output devices
module.
• For general interface use in any type of system and application.
• Can be used for input interface applications between auxiliary contacts, sensors etc. and
controllers, PLC's or motors. Or for output interface between PLC’s controllers and relays, solenoids
etc.
8012823356709
8012823356709
Output devices
Fuse module
093.63
093.63.0.024
093.63.8.230
PLC - Output
PLC - Output
PLC - Input
PLC - Input
Input devices
2
Input devices
VII-2016, www.findernet.com
Fuse module
093.63
093.63.0.024
093.63.8.230
39 SERIES
Typical applications
39
SERIES
MasterINPUT
39.41 - 39.40 - 39.71 - 39.70
MasterOUTPUT
39.21 - 39.20 - 39.51 - 39.50
input device to the interface without the need
for additional terminals - saving component
cost, time and panel space.
• Quick and easy distribution of supply voltage
through the jumper link on the Bus-Bar (BB)
connection.
• Ideal for interface applications between the
auxiliary contacts, sensors, limit switches and
Controllers or PLC’s.
of output device to the interface without
the need for additional terminals - saving
component cost, time and panel space.
• Quick and easy distribution of supply voltage
through the jumper link on the Bus-Bar (BB)
connection.
• Ideal for interface applications between the
PLC’s or Controllers and output devices such as
electomagnetic valves or motors etc..
• These models allow the full termination of
• These models allow the full termination
Output devices
MasterTIMER
39.81 - 39.80 - 39.91 - 39.90
• Slim and Multifunction Timed Interface
modules.
B
Output devices
Fuse module
093.63
093.63.0.024
093.63.8.230
VII-2016, www.findernet.com
PLC - Output
PLC - Output
PLC - Input
PLC - Input
Input devices
Input devices
3
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterBASIC - EMR
39.11/39.01
1 Pole interface module, 6.2 mm wide, ideal
for PLC and electronic systems
• Common connection possible with optional
jumper links (terminals A1, A2 and 11)
• UL Listing (certain relay/socket combinations)
B
• 6 A electromechanical relay
• 6 to 24 and 125 V AC/DC and 230 V AC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.11
Screw terminal
39.01
Push-in terminal
For outline drawing see page 22, 23
Contact specification
Contact configuration
1 CO (SPDT)
Rated current/
Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
6/10
250/400
Rated load AC1
VA
Rated load AC15 (230 V AC)
VA
300
Single phase motor rating (230 V AC)
kW
0.185
Breaking capacity DC1: 30/110/220 V
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Minimum switching load
Standard contact material
1500
AgNi
Supply specification
Nominal voltage (UN)V AC/DC
V AC (50/60 Hz)
Rated power
VA (50 Hz)/W
6 - 12 - 24 - 110…125
220…240
See page 18
Operating range
(0.8…1.1)UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
4
ms
5/6
kV
6 (8 mm)
V AC
°C
1000
–40…+70
IP 20
VII-2016, www.findernet.com
Technical data
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
MasterBASIC - SSR
39.10/39.00
1 Pole interface module, 6.2 mm wide, ideal
for PLC and electronic systems
• Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
• UL Listing (certain relay/socket combinations)
B
• 0.1 or 2 A solid state relay
• 6 to 24 and 125 V AC/DC and 230 V AC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.10
Screw terminal
39.00
Push-in terminal
For outline drawing see page 22, 23
Output specification (SSR)
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms)
Rated voltage/
Maximum blocking voltage
A
Switching voltage range
2/20 DC
0.1/0.5 DC
2/40 AC
V
24/33 DC
48/60 DC
240/— AC
V
(1.5…24) DC
(1.5…48) DC
(12…275) AC
600
Repetitive peak off-state voltage
Vpk
—
—
Minimum switching current
mA
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
V
0.12
1
1.6
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)V AC/DC
110…125
V AC (50/60 Hz)
220…240
V DC
Rated power
6 - 12 - 24
VA (50 Hz)/W
See page 19
Operating range
(0.8…1.1)UN
Must drop-out voltage
0.1 UN
Technical data
Operate/release time
Dielectric strength
between input/output
Ambient temperature range
VII-2016, www.findernet.com
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.6
12/12
2500
–20…+55
IP 20
Approvals relay (according to type)
5
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterPLUS - EMR
39.31/39.61
39.31.3/39.61.3
1 Pole interface modules, 6.2 mm wide, ideal
for PLC and electronic systems
• Accepts output fuse module 093.63,
• 6 A electromechanical relay
• 6 to 125 V AC/DC, 125 and 220 V DC, 230 V AC,
24…240 V AC/DC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.31/39.31.3
Screw terminal
• 6 A electromechanical relay
• Leakage current suppression version,
125 V AC/DC and 230 V AC supply
• Screw terminal and push-in terminal
39.61/39.61.3
Push-in terminal
Fuse module
093.63
093.63.0.024
093.63.8.230
For outline drawing see page 22, 23
Contact specification
Contact configuration
Rated current/
Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
Rated load AC1
VA
1 CO (SPDT)
1 CO (SPDT)
6/10
6/10
250/400
250/400
1500
1500
Rated load AC15 (230 V AC)
VA
300
300
Single phase motor rating (230 V AC)
kW
0.185
0.185
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
6/0.2/0.12
6/0.2/0.12
mW (V/mA)
500 (12/10)
500 (12/10)
AgNi
AgNi
6 - 12 - 24 - 60 - 110…125 - 24…240
110…125
220…240
220…240
Standard contact material
Supply specification
Nominal voltage (UN)V AC/DC
V AC (50/60 Hz)
V DC
110…125 - 220
—
See page 18
See page 18
Operating range
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
0.6 UN
0.6 UN
Must drop-out voltage
0.1 UN
0.3 UN
Rated power
VA (50 Hz)/W
Technical data
Mechanical life AC/DC
cycles
10 · 106
10 · 106
Electrical life at rated load AC1
cycles
60 · 10
60 · 103
ms
5/6
5/6
kV
6 (8 mm)
6 (8 mm)
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
6
V AC
°C
3
1000
1000
–40…+70 (+55 for 220 V DC)
–40…+70
IP 20
IP 20
VII-2016, www.findernet.com
B
093.63.0.024, 093.63.8.230 (for 5 x 20 mm
fuses) for quick and easy load protection, see
page 27
• Common connection possible with optional
jumper links (terminals A1, A2 and 11)
• UL Listing (certain relay/socket combinations)
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
MasterPLUS - SSR
39.30/39.60
39.30.3/39.60.3
1 Pole interface modules, 6.2 mm wide, ideal
for PLC and electronic systems
• Accepts output fuse module 093.63,
093.63.0.024, 093.63.8.230 (for 5 x 20 mm
fuses) for quick and easy load protection, see
page 27
• Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
• UL Listing (certain relay/socket combinations)
B
• 0.1 or 2 A solid state relay
• 24 - 125 V AC/DC, 6 to 220 V DC and 230 V AC,
24…240 V AC/DC supply
125 V AC DC and 230 V AC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.30/39.30.3
Screw terminal
• 0.1 or 2 A solid state relay
• Leakage current suppression version,
• Screw terminal and push-in terminal
39.60/39.60.3
Push-in terminal
Fuse module
093.63
093.63.0.024
093.63.8.230
For outline drawing see page 22, 23
Output specification (SSR)
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240 39.x0.3.xxx.9024 39.x0.3.xxx.7048 39.x0.3.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms)
Rated voltage/
Maximum blocking voltage
A
Switching voltage range
2/20 DC
1 NO (SPST-NO)
0.1/0.5 DC
2/40 AC
2/20 DC
0.1/0.5 DC
2/40 AC
V
24/33 DC
48/60 DC
240/— AC
24/33 DC
48/60 DC
240/— AC
V
(1.5…24) DC
(1.5…48)DC
(12…275) AC
(1.5…24) DC
(1.5…48)DC
(12…275) AC
600
Repetitive peak off-state voltage
Vpk
—
—
600
—
—
Minimum switching current
mA
1
0.05
22
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
0.001
0.001
1.5
V
0.12
1
1.6
0.12
1
1.6
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)V AC/DC
V AC (50/60 Hz)
V DC
Rated power
24 - 110…125 - 24…240
110…125
220…240
220…240
6 - 12 - 24 - 60 - 110…125 - 220
—
See page 19
See page 19
(0.8…1.1)UN
(0.8…1.1)UN
0.1 UN
0.3 UN
VA (50 Hz)/W
Operating range
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength
between input/output
Ambient temperature range
VII-2016, www.findernet.com
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.6
12/12
0.2/0.6
0.04/0.6
2500
2500
–20…+55
–20…+55
IP 20
IP 20
12/12
Approvals relay (according to type)
7
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterINPUT - EMR
39.41/39.71
1 Pole interface module, 6.2 mm wide, ideal
for PLC and electronic systems
• Jumper link option for the quick and easy
• 6 A electromechanical relay
• 6 - 12 - 24 - 125 V AC/DC and 230 V AC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.41
Screw terminal
39.71
Push-in terminal
For outline drawing see page 22, 23
Contact specification
Contact configuration
1 CO (SPDT)
Rated current/
Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
6/10
250/400
Rated load AC1
VA
Rated load AC15 (230 V AC)
VA
300
Single phase motor rating (230 V AC)
kW
0.185
Breaking capacity DC1: 30/110/220 V
A
Minimum switching load
mW (V/mA)
Standard contact material
1500
6/0.2/0.12
50 (5/2)
AgNi + Au
Supply specification
Nominal voltage (UN)V AC/DC
V AC (50/60 Hz)
Rated power
VA (50 Hz)/W
6 - 12 - 24 - 110…125
220…240
See page 18
Operating range
(0.8…1.1)UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
8
ms
5/6
kV
6 (8 mm)
V AC
°C
1000
–40…+70
IP 20
VII-2016, www.findernet.com
B
distribution of supply voltage to proximity
switches and similar input devices (Bus-bar
connection BB)
• Gold plated output contact as standard, for
better compatibility with low energy PLC inputs
• UL Listing (certain relay/socket combinations)
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
MasterINPUT - SSR
39.40/39.70
1 Pole interface modules, 6.2 mm wide, ideal
for PLC and electronic systems
• Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices (Bus-bar
connection BB)
• UL Listing (certain relay/socket combinations)
B
• 0.1 or 2 A solid state relay
• 6 - 12 - 24 V DC, 24 - 125 V AC/DC and 230 V AC
supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.40
Screw terminal
39.70
Push-in terminal
For outline drawing see page 22, 23
Output specification (SSR)
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms)
Rated voltage/
Maximum blocking voltage
A
Switching voltage range
2/20 DC
0.1/0.5 DC
2/40 AC
V
24/33 DC
48/60 DC
240/— AC
V
(1.5…24) DC
(1.5…48) DC
(12…275) AC
600
Repetitive peak off-state voltage
Vpk
—
—
Minimum switching current
mA
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
V
0.12
1
1.6
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)V AC/DC
24 - 110…125
V AC (50/60 Hz)
220…240
V DC
Rated power
6 - 12 - 24
VA (50 Hz)/W
See page 19
Operating range
(0.8…1.1)UN
Must drop-out voltage
0.1 UN
Technical data
Operate/release time
Dielectric strength
between input/output
VII-2016, www.findernet.com
Ambient temperature range
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.6
12/12
2500
–20…+55
IP 20
Approvals relay (according to type)
9
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterOUTPUT - EMR
39.21/39.51
1 Pole interface modules, 6.2 mm wide, ideal
for PLC and electronic systems
• Jumper link option for the quick and easy
• 6 A electromechanical relay
• 6 - 12 - 24 - 125 V AC/DC and 230 V AC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.21
Screw terminal
39.51
Push-in terminal
For outline drawing see page 22, 23
Contact specification
Contact configuration
1 NO (SPST-NO)
Rated current/
Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
6/10
250/400
Rated load AC1
VA
Rated load AC15 (230 V AC)
VA
300
Single phase motor rating (230 V AC)
kW
0.185
Breaking capacity DC1: 30/110/220 V
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Minimum switching load
Standard contact material
1500
AgNi
Supply specification
Nominal voltage (UN)V AC/DC
V AC (50/60 Hz)
Rated power
VA (50 Hz)/W
6 - 12 - 24 - 110…125
220…240
See page 18
Operating range
(0.8…1.1)UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
10
ms
5/6
kV
6 (8 mm)
V AC
°C
1000
–40…+70
IP 20
VII-2016, www.findernet.com
B
distribution of supply voltage to output side
(Bus-bar connection BB) and its connection
to electromagnetic valves and similar output
devices
• UL Listing (certain relay/socket combinations)
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
MasterOUTPUT - SSR
39.20/39.50
1 Pole interface modules, 6.2 mm wide,
ideal for PLC and electronic systems
• Jumper link option for the quick and easy
distribution of supply voltage to output side
(Bus-bar connection BB) and its connection
to electromagnetic valves and similar output
devices
• UL Listing (certain relay/socket combinations)
B
• 0.1 or 2 A solid state relay
• 6 to 24 V DC, 125 V AC/DC and 230 V AC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.20
Screw terminal
39.50
Push-in terminal
For outline drawing see page 22, 23
Output specification (SSR)
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/
Maximum peak current (10 ms)
Rated voltage/
Maximum blocking voltage
A
Switching voltage range
2/20 DC
0.1/0.5 DC
2/40 AC
V
24/33 DC
48/60 DC
240/— AC
V
(1.5…24) DC
(1.5…48) DC
(12…275) AC
Repetitive peak off-state voltage
Vpk
—
—
600
Minimum switching current
mA
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
V
0.12
1
1.6
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)V AC/DC
110…125
V AC (50/60 Hz)
220…240
V DC
Rated power
6 - 12 - 24
VA (50 Hz)/W
See page 19
Operating range
(0.8…1.1)UN
Must drop-out voltage
0.1 UN
Technical data
Operate/release time
Dielectric strength
between input/output
Ambient temperature range
VII-2016, www.findernet.com
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.6
12/12
2500
–20…+55
IP 20
Approvals relay (according to type)
11
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterTIMER - EMR
39.81/39.91
Slim timed interface module, 6.2 mm wide,
ideal for space-saving timing solutions in panels
• Timer adjustment via top mounted rotary knob,
accessible after assembly
• Control signal terminal
• DIP-switch for selection of 4 time scales and
8 functions
• Accepts output fuse module 093.63,
093.63.0.024, 093.63.8.230 (for 5 x 20 mm
fuses) for quick and easy load protection, see
page 27
• Common connection possible with optional
jumper links (terminals A1, A2 and 15)
• UL Listing (certain relay/socket combinations)
39.81
Screw terminal
• 6 A electromechanical relay
• 12 - 24 V AC/DC supply
• Screw terminal and push-in terminal
• 35 mmrail (EN 60715) mounting
39.91
Push-in terminal
Fuse module
093.63
093.63.0.024
093.63.8.230
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
For outline drawing see page 22, 23
Contact specification
Contact configuration
1 CO (SPDT)
Rated current/
Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
Rated load AC1
VA
6/10
250/400
1500
Rated load AC15 (230 V AC)
VA
300
Single phase motor rating (230 V AC)
kW
0.185
Breaking capacity DC1: 30/110/220 V
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Minimum switching load
Standard contact material
AgNi
Supply specification
Nominal voltage (UN)V AC/DC
Rated power AC/DC
VA (50 Hz)/W
12 - 24
See page 18
Operating range
(0.8…1.1)UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Specified time range
(0.1…3)s, (3…60)s, (1…20)min, (0.3…6)h
Repeatability%
± 1
Recovery time
ms
≤ 50
Minimum control impulse
ms
50
Setting accuracy - full range
Electrical life at rated load AC1
Ambient temperature range
Protection category
Approvals relay (according to type)
12
%
cycles
°C
5
60 · 103
–20…+50
IP 20
VII-2016, www.findernet.com
B
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
MasterTIMER - SSR
39.80/39.90
Slim timed interface module, 6.2 mm wide, ideal
for space-saving timing solutions in panels
• Timer adjustment via top mounted rotary
knob; accessible after assembly
• Start terminal
• DIP-switch for selection of 4 time scales and
8 functions
B
• Accepts output fuse module 093.63,
093.63.0.024, 093.63.8.230 (for 5 x 20 mm
fuses) for quick and easy load protection, see
page 27
• Common connection possible with optional
jumper links (terminals A1, A2 and 15+)
• UL Listing (certain relay/socket combinations)
39.80
Screw terminal
• 0.1 or 2 A solid state relay
• 12 - 24 V AC/DC supply
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
39.90
Push-in terminal
Fuse module
093.63
093.63.0.024
093.63.8.230
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
For outline drawing see page 22, 23
Output specification (SSR)
39.x0.x.xxx.9024 39.x0.x.xxx.7048 39.x0.x.xxx.8240
Contact configuration
Rated current/
Maximum peak current (10 ms)
Rated voltage/
Maximum blocking voltage
Switching voltage range
1 NO (SPST-NO)
A
2/20 DC
0.1/0.5 DC
2/40 AC
V
24/33 DC
48/60 DC
240/— AC
V
(1.5…24) DC
(1.5…48) DC
(12…275) AC
600
Repetitive peak off-state voltage
Vpk
—
—
Minimum switching current
mA
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
V
0.12
1
1.6
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (UN)V AC/DC
Rated power
VA (50 Hz)/W
12 - 24
See page 19
Operating range
(0.8…1.1)UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
VII-2016, www.findernet.com
Specified time range
(0.1…3)s, (3…60)s, (1…20)min, (0.3…6)h
Repeatability%
± 1
Recovery time
ms
≤ 50
Minimum control impulse
ms
50
Setting accuracy – full range
%
5
Ambient temperature range
°C
–20…+50
Protection category
IP 20
Approvals relay (according to type)
13
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterBASIC - EMR ATEX
39.11/39.01 - x073
1 Pole interface module, 6.2 mm wide, ideal
for PLC and electronic systems
ATEX compliant (EX nA nC)
• 1 CO 6 A
• Screw terminal and push-in terminal
• 35 mm rail (EN 60715) mounting
• ATEX compliant
jumper links (terminals A1, A2 and 11) and
multipole connector MasterADAPTER
• 35 mm rail (EN 60715) mounting
39.11
Screw terminal
39.01
Push-in terminal
For outline drawing see page 22, 23
Contact specification
Contact configuration
1 CO (SPDT)
Rated current/
Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
6/10
250/400
Rated load AC1
VA
Rated load AC15 (230 V AC)
VA
300
Single phase motor rating (230 V AC)
kW
0.185
Breaking capacity DC1: 30/110/220 V
Minimum switching load
1500
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Standard contact material
AgNi
Coil specification
Nominal voltage (UN)V AC/DC
6 - 12 - 24 - 110…125 - 24…240
V AC (50/60 Hz)
230…240
V DC
6 - 12 - 24
Rated power AC/DC
VA (50 Hz)/W
See page 18
Operating range
(0.8…1.1)UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
14
ms
5/6
kV
6 (8 mm)
V AC
°C
1000
–40…+70
IP 20
VII-2016, www.findernet.com
B
• Electromechanical relay
• AC, DC and AC/DC Version
• Screw terminal and Push-in terminal
• UL Listed
• Cadmium free contacts
• Complies with:
--EN 60079-0: 2012 and EN 60079-15:2010
--94/9/CE and 2014/34/UE
• Common connection possible with optional
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
Ordering information ATEX versions
Example: 39 series, screw terminals interface module, electromechanical relay output, 1 CO 6 A, 24 V DC, ATEX Version.
3 9 . 1
Series
Type
0 = Push-in terminals
35 mm rail (EN 60715) mount
1 = Screw terminals
35 mm rail (EN 60715) mount
A
B
C
D
1 . 7 . 0 2 4 . 0
0
7
3
A: Contact material
0 = AgNi Standard
5 = AgNi + Au
C - D: Option
73 = ATEX
Complaiant (Ex nA nC)
B
B: Contact circuit
0 = CO (nPDT)
No. of poles
1 = 1 CO, 6 A
Coil version
0 = AC/DC
7 = DC sensitive
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
Other data ATEX versions
Max current @ 70 °C
Single piece mount
> 8 piece mount
Type 39.11/01
A 6
5
Type 39.11/01 (110…125)V AC/DC only
A 6
4
Terminals
Wire strip length
Screw torque
Screw terminals
Push-in Terminals
mm 10
8
Nm 0.5
—
Wire size
solid and stranded cable
solid and stranded cable
1 x 2.5
1 x 2.5
AWG 1 x 14
1 x 14
mm
2
Markings - ATEX versions - ATEX, II 3G Ex nA nC IIC Gc
MARKING
VII-2016, www.findernet.com
GAS
Specific marking of explosion protection
II
Component for surface plant (different from mines)
3
Category 3: normal level of protection
G
Explosive atmosphere due to presence of combustible gas vapour or mist
Ex nA
Non-sparking equipment
Ex nC
Sealed device (type of protection for category 3G)
IIC
Gas group
Gc
Equipment Protection Level
–40 °C ≤ Ta ≤ +70 °C
Ambient temperature
EPT 15 ATEX 0194 U
EPT: laboratory which issues the CE type certificate
15: year of issue of certificate
0194: number of CE type certificate
U: ATEX component
15
39
SERIES
39 SERIES
Relay interface modules - Ordering information
Ordering information
Example: MasterPLUS 39 series screw terminal interface module, electromechanical relay output, 1 CO (SPDT), 24 V AC/DC coil.
3 9 . 3
B
C
D
1 . 0 . 0 2 4 . 0
0
6
0
Series
Type
1 = MasterBASIC, screw terminal
0 = MasterBASIC, push-in terminal
3 = MasterPLUS, screw terminal,
fuse-protectable output
6 = MasterPLUS, push-in terminal,
fuse-protectable output
4 = MasterINPUT, screw terminal
7 = MasterINPUT, push-in terminal
2 = MasterOUTPUT, screw terminal
5 = MasterOUTPUT, push-in terminal
8 = MasterTIMER multifunction,
screw terminal,
fuse-protectable output
9 = MasterTIMER multifunction,
push-in terminal,
fuse-protectable output
No. of poles
1 = 1 CO (only EMR, except 39.21/51, 1 NO)
0 = 1 NO (only SSR)
Coil version, EMR / Input version, SSR
0 = AC (50/60 Hz)/DC
3 = Leakage current suppression AC (50/60 Hz)
7 = DC sensitive
8 = AC (50/60 Hz)
Coil voltage, EMR/Input voltage, SSR
See page 18
D: Special Version, EMR
0 = Standard
C: Options, EMR
6 = Standard
B: Contact circuit, EMR
0 = CO (except 39.21/51, 1 NO)
A: Contact material, EMR
0 = AgNi Standard
4 = AgSnO2
5 = AgNi + Au
ABCD: Output version, SSR
7048 = 0.1 A - 48 V DC
8240 = 2 A - 230 V AC
9024 = 2 A - 24 V DC
EMR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
39.11/01
39.31/61
39.41/71
39.21/51
39.81/91
Coil version
0.006 - 0.012
0.024 - 0.125 - 8.230
0.006 - 0.012
0.024 - 0.060
0.125 - 0.240 - 8.230
7.125 - 7.220
3.125 - 3.230
0.006 - 0.012
0.024 - 0.125
8.230
0.006 - 0.012
0.024 - 0.125
8.230
0.012 - 0.024
A
B
C
D
0-4-5
0
6
0
0-4-5
0
6
0
0-4-5
0
6
0
0-4-5
0
6
0
0
0
6
0
SSR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
39.10/00
39.30/60
39.40/70
39.20/50
39.80/90
16
Input version
7.006 - 7.012
7.024 - 0.125 - 8.230
7.006 - 7.012
7.024 - 7.060
7.125 - 7.220
0.024 - 0.125 - 0.240
8.230
3.125 - 3.230
7.006 - 7.012
7.024 - 0.024 - 0.125
8.230
7.006 - 7.012
7.024 - 0.125
8.230
0.012 - 0.024
Output version, ABCD
7048 - 8240 - 9024
7048 - 8240 - 9024
7048 - 8240 - 9024
7048 - 8240 - 9024
7048 - 8240 - 9024
VII-2016, www.findernet.com
B
A
39 SERIES
Relay interface modules - Technical data
39
SERIES
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system
V AC 230/400
Rated insulation voltage
V AC 250
Pollution degree
400
3
2
Insulation between coil and contact set
Type of Insulation
Reinforced
Overvoltage category
III
Rated impulse voltage
B
kV (1.2/50)μs 6
Dielectric strength
V AC 4000
Insulation between open contacts (EMR)
Type of disconnection
Micro-disconnection
Dielectric strength
V AC/kV (1.2/50)μs 1000/1.5
Conducted disturbance immunity
UN ≤ 60 V
Fast transients (burst 5/50 ns, 5 kHz) according to EN 61000-4-4
at supply terminals
Voltage pulses (surge 1.2/50 μs) according to EN 61000-4-5
at supply terminals (differential mode)
UN = 125 V
UN = 230 V
kV 4
4
4
kV 0.8
2
4
Other data
Bounce time (EMR): NO/NC
ms 1/6
Vibration resistance (EMR,10…55 Hz): NO/NC
Power lost to the environment
g 10/15
without contact current
W 0.2 (24 V) - 0.4 (230 V)
with rated current
W 0.6 (24 V) - 0.9 (230 V)
Terminals
Screw terminal
Wire strip length
Screw torque
Push-in terminal
mm 10
8
Nm 0.5
—
Solid and stranded cable
Max. wire size
Min. wire size
Solid and stranded cable
mm2 1 x 2.5 / 2 x 1.5
1 x 2.5
AWG 1 x 14 / 2 x 16
1 x 14
mm2 1 x 0.2
1 x 0.2
AWG 1 x 24
1 x 24
Contact specification (EMR)
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
H 39 - Maximum DC1 breaking capacity
DC breaking current (A)
Cycles
F 39 - Electrical life (AC) v contact current
VII-2016, www.findernet.com
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 60 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
17
39 SERIES
Relay interface modules - Technical data
39
SERIES
Coil specifications - Electromechnical Relay
Coil data DC, type 39.31/61
Nominal
voltage
Must drop‑out
voltage
Rated
power
at UN
UN
Umin
Umax
Ur
Rated input
current at UN
IN
V
V
V
V
mA
W
Operating range
125
(110…125)
7.125
88
138
12.5
4.6
0.6
220
7.220
176
242
22
3.0
0.6
Coil data AC/DC, type 39.11/21/31/41/01/51/61/71
Nominal
voltage
Coil
code
Operating range
Must drop‑out
voltage
UN
Umin
Umax
V
V
V
4.8
6.6
0.6
35
Ur
Rated
power
at UN
Rated input
current at UN
IN
V
mA
VA/W
6
0.006
12
0.012
9.6
13.2
1.5
15
0.2/0.2
24
0.024
19.2
26.4
2.4
11
0.25/0.25
60(1)
0.060
48
66
6.0
5.7
0.35/0.35
0.125
88
138
12.5
5.6
0.7/0.7
0.240
20.4
264
2.4
125
(110…125)
240
(24…240)(2)
0.2/0.2
19
(1)
(2)
60 V AC/DC for type 39.31/61 only
24…240 V AC/DC for type 39.31/61 only
1.5/0.3
Coil data AC, type 39.11/21/31/41/01/51/61/71
Nominal
voltage
Coil
code
UN
Umin
Umax
Ur
V
V
V
V
mA
VA/W
184
264
23
4.3
1/0.4
Rated
power
at UN
230
(230…240)
8.230
Must drop‑out
voltage
Rated
power
at UN
Rated input
current at UN
IN
Operating range
Coil data leakage current suppression versions, type 39.31.3/61.3
Nominal
voltage
Coil
code
UN
Umin
Umax
Ur
Rated input
current at UN
IN
V
V
V
V
mA
VA/W
3.125
88
138
44
8.4
1.1/1
3.230
184
264
72
5.9
1.4/0.5
125
(110…125)
230
(230…240)
Operating range
Must drop‑out
voltage
The 39 Series interface modules (supply version 3) have
built-in leakage current suppression to address industry
concerns of the contacts not dropping-out when there is
residual current in the circuit; at (110…125)V AC/DC and
(230…240)V AC.
This problem can occur, for example, when connecting
the interface modules to PLC's with triac outputs or when
connecting via relatively long cables.
Coil data AC/DC timer, type 39.81/91
Nominal
voltage
Coil code
Operating range
(AC/DC)
Must drop‑out
voltage
Rated input current
at UN
DC
AC
Rated power at UN
UN
Umin
Umax
Ur
DC
AC
V
V
V
V
mA
mA
W
VA/W
12
0.012
9.6
13.2
1.2
15
23
0.2
0.3/0.2
24
0.024
19.2
26.4
2.4
11
19
0.25
0.4/0.3
VII-2016, www.findernet.com
B
Coil
code
18
39 SERIES
Relay interface modules - Technical data
39
SERIES
Input specifications - Solid State Relay
Input data DC, type 39.10/20/30/40/00/50/60/70
Nominal
voltage
Input
code
Must drop‑out
voltage
Rated
power
at UN
UN
Umin
Umax
Ur
Rated input
current at UN
IN
V
V
V
V
mA
W
Operating range
6
7.006
4.8
6.6
0.6
7.5
0.2
12
7.012
9.6
13.2
1.2
20.7
0.25
B
24
7.024
19.2
26.4
2.4
10.5
0.25
60 (1)
7.060
38
66
6.0
6.4
0.4
125 (1)
(110…125)
7.125
88
138
12.5
4.6
0.6
220 (1)
7.220
176
242
22
3.0
0.6
Rated input
current at UN
IN
Rated
power
at UN
(1)
60 V DC, 125 V DC and 220 V DC for type 39.30/60 only
(2)
24 V AC/DC for type 39.30/40/60/70 only
24…240 V AC/DC for type 39.30/60 only
Input data AC/DC, type 39.10/20/30/40/00/50/60/70
Nominal
voltage
Input
code
Operating range
UN
Umin
Umax
V
V
V
24 (2)
125
(110…125)
240
(24…240)(3)
0.024
19.2
0.125
88
0.240
20.4
Must drop‑out
voltage
Ur
V
mA
VA/W
2.4
17.5
0.4/0.3
138
12.5
5.5
0.7/0.7
264
2.4
17.5
1.5/0.3
26.4
(3)
Input data AC, type 39.10/20/30/40/00/50/60/70
Nominal
voltage
Input
code
UN
Umin
Umax
Ur
V
V
V
V
mA
VA/W
184
264
23
4.2
1/0.4
230
(230…240)
8.230
Must drop‑out
voltage
Rated
power
at UN
Rated input
current at UN
IN
Operating range
Input data leakage current suppression versions, type 39.30.3/60.3
Nominal
voltage
Input
code
UN
Umin
Umax
Ur
V
V
V
V
mA
VA/W
3.125
88
138
44
8.4
1.1/1
3.230
184
264
72
5.9
1.4/0.5
125
(110…125)
230
(230…240)
Must drop‑out
voltage
Rated
power
at UN
Rated input
current at UN
IN
Operating range
The 39 Series interface modules (supply version 3) have
built-in leakage current suppression to address industry
concerns of the contacts not dropping-out when there is
residual current in the circuit; at (110…125)V AC/DC and
(230…240)V AC.
This problem can occur, for example, when connecting
the interface modules to PLC's with triac outputs or when
connecting via relatively long cables.
Input data AC/DC timer, type 39.80/90
Nominal
voltage
Input
code
Operating range
(AC/DC)
Must drop‑out
voltage
UN
Umin
Umax
Ur
V
V
V
V
Rated input current
at UN
DC
AC
mA
mA
Rated power at UN
DC
AC
W
VA/W
0.012
9.6
13.2
1.2
15
23
0.2
0.3/0.2
0.024
19.2
26.4
2.4
11
19
0.25
0.4/0.3
VII-2016, www.findernet.com
12
24
19
39
SERIES
39 SERIES
Timed interface modules
Timer specifications
EMC specifications
Type of test
Reference standard
Electrostatic discharge
Fast transients (burst) (5-50 ns, 5 and 100 kHz)
Surges (1.2/50 μs) on supply and control
signal terminals
4 kV
air discharge EN 61000-4-2
8 kV
(80 ÷ 1000 MHz) EN 61000-4-3
10 V/m
(1400 ÷ 2700 MHz) EN 61000-4-3
10 V/m
on Supply terminals EN 61000-4-4
4 kV
on control signal terminals EN 61000-4-4
4 kV
common mode EN 61000-4-5
2 kV
differential mode EN 61000-4-5
on Supply terminals EN 61000-4-6
Radio-frequency common mode
(0.15 ÷ 80 MHz)
on control signal terminals EN 61000-4-6
Radiated and conducted emission
EN 55022
0.8 kV
10 V
3 V
class B
Other data
Bounce time (EMR): NO/NC
ms 1/6
Vibration resistance (EMR,10..55 Hz): NO/NC
g 10/15
Power lost to the environment
without contact current
W 0.3
with rated current
W 0.8
Terminals
Screw terminal
Wire strip length
Screw torque
Max. wire size
8
Nm 0.5
—
mm
2
Min. wire size
Push-in terminal
mm 10
Solid and stranded cable
Solid and stranded cable
1 x 2.5 / 2 x 1.5
1 x 2.5
AWG 1 x 14 / 2 x 16
1 x 14
mm2 1 x 0.2
1 x 0.2
AWG 1 x 24
1 x 24
Times scales
1 2 3 4 5
(0.1…3)s
Functions
20
LED
1 2 3 4 5
(3…60)s
1 2 3 4 5
(1…20)min
1 2 3 4 5
(0.3…6)h
Supply voltage
NO contact/output
OFF
Open
ON
Open
ON
Open (timing to close in progress)
ON
Closed
VII-2016, www.findernet.com
B
Radio-frequency electromagnetic field
contact discharge EN 61000-4-2
39 SERIES
Timed interface modules
Wiring diagram
U = Supply voltage
Without control signal
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
With control signal
1 2 3 4 5
*
* With DC supply,
positive polarity has
to be conneted to B1,
terminal (according to
EN 60204-1).
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
39
SERIES
S = Signal switch
= Output contact
(AI) On-delay
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs when power is
removed.
(DI) Interval
Apply power to timer. Output contacts transfer
immediately. After the preset time has elapsed, contacts
reset.
(GI) Pulse (0.5 s) delayed
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs after a fixed time
of 0.5 s.
(SW) Symmetrical flasher (starting pulse on)
Apply power to timer. Output contacts transfer
immediately and cycle between ON and OFF for as long
as power is applied. The ratio is 1:1 (time on = time off ).
(BE) Off-delay with control signal
Power is permenently applied to the timer. The output
contacts transfer immediately on closure of the Signal
Switch (S). Opening the Signal Switch initiates the
preset delay, after which time the output contacts reset.
(CE) On- and off-delay with control signal
Power is permenently applied to the timer. Closing the
Signal Switch (S) initiates the preset delay, after which
time the output contacts transfer. Opening the Signal
switch initiates the same preset delay, after which time
the output contacts reset.
(DE) Interval with control signal on
Power is permenently applied to the timer. On momentary
or maintained closure of Signal Switch (S), the output
contacts transfer, and remain so for the duration of the
preset delay, after which they reset.
(EE) Interval with control signal off
Power is permenently applied to the timer. On opening
of the Signal Switch (S) the output contacts transfer,
and remain so for the duration of the preset delay, after
which they reset.
VII-2016, www.findernet.com
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 24 V AC
B1 - A2 = 12 V DC
21
B
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
Outline drawings - Screw terminal sockets
39.10/39.20
39.11/39.21
Screw terminal
39.30/39.30.3
39.31/39.31.3
Screw terminal
39.40
39.41
Screw terminal
39.80
39.81
Screw terminal
VII-2016, www.findernet.com
B
22
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
Outline drawings - Push-in terminal sockets
39.00/39.01
39.50/39.51
Push-in terminal
39.60/39.60.3
39.61/39.61.3
Push-in terminal
B
39.70
39.71
Push-in terminal
39.90
39.91
Push-in terminal
Main features
Push-in terminals
The push-in terminals permit the quick connection of solid wires or ferrules by their simple insertion into the terminal (A).
It is possible to open the terminal to extract the wire by first pushing down on the push-button using a screwdriver (C).
For stranded cable it is necessary first to open the terminal using the push button, both for the extraction (C) and insertion (B).
It is possible at any time to check the connection via the test aperture, using a 2 mm diameter test probe (D).
B
C
D
VII-2016, www.findernet.com
A
23
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
Electromechanical Relay (1 Pole 6 A) & Screw Socket Combinations
Interface Module Code
MasterBASIC
39.11.0.006.0060
39.11.0.012.0060
39.11.0.024.0060
39.11.0.125.0060
39.11.8.230.0060
MasterPLUS
39.31.0.006.0060
39.31.0.012.0060
39.31.0.024.0060
39.31.0.060.0060
39.31.0.125.0060
39.31.0.240.0060
39.31.8.230.0060
39.31.7.125.0060
39.31.7.220.0060
39.31.3.125.0060
39.31.3.230.0060
MasterINPUT
39.41.0.006.5060
39.41.0.012.5060
39.41.0.024.5060
39.41.0.125.5060
39.41.8.230.5060
MasterOUTPUT 1 NO, 6 A only
39.21.0.006.0060
39.21.0.012.0060
39.21.0.024.0060
39.21.0.125.0060
39.21.8.230.0060
MasterTIMER
39.81.0.012.0060
39.81.0.024.0060
B
Coil voltage
Relay
Socket
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
93.61.7.024
93.61.7.024
93.61.7.024
93.61.0.125
93.61.8.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
60 V AC/DC
(110…125)V AC/DC
(24…240)V AC/DC
(230…240)V AC
(110…125)V DC
220 V DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
93.63.7.024
93.63.7.024
93.63.7.024
93.63.7.060
93.63.0.125
93.63.0.240
93.63.8.230
93.63.7.125
93.63.7.220
93.63.3.125
93.63.3.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.5010
34.51.7.012.5010
34.51.7.024.5010
34.51.7.060.5010
34.51.7.060.5010
93.64.7.024
93.64.7.024
93.64.7.024
93.64.0.125
93.64.8.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
93.62.7.024
93.62.7.024
93.62.7.024
93.62.0.125
93.62.8.230
12 V AC/DC
24 V AC/DC
34.51.7.012.0010
34.51.7.024.0010
93.68.0.024
93.68.0.024
Example: .xxxx
.9024
.7048
.8240
24
Interface Module Code
MasterBASIC
39.10.7.006.xxxx
39.10.7.012.xxxx
39.10.7.024.xxxx
39.10.0.125.xxxx
39.10.8.230.xxxx
MasterPLUS
39.30.7.006.xxxx
39.30.7.012.xxxx
39.30.7.024.xxxx
39.30.7.060.xxxx
39.30.7.125.xxxx
39.30.7.220.xxxx
39.30.0.024.xxxx
39.30.0.125.xxxx
39.30.0.240.xxxx
39.30.8.230.xxxx
39.30.3.125.xxxx
39.30.3.230.xxxx
MasterINPUT
39.40.7.006.xxxx
39.40.7.012.xxxx
39.40.7.024.xxxx
39.40.0.024.xxxx
39.40.0.125.xxxx
39.40.8.230.xxxx
MasterOUTPUT
39.20.7.006.xxxx
39.20.7.012.xxxx
39.20.7.024.xxxx
39.20.0.125.xxxx
39.20.8.230.xxxx
MasterTIMER
39.80.0.012.xxxx
39.80.0.024.xxxx
Input voltage
Relay
Socket
6 V DC
12 V DC
24 V DC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.61.7.024
93.61.7.024
93.61.7.024
93.61.0.125
93.61.8.230
6 V DC
12 V DC
24 V DC
60 V DC
(110…125)V DC
220 V DC
24 V AC/DC
(110…125)V AC/DC
(24…240)V AC/DC
(230…240)V AC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.63.7.024
93.63.7.024
93.63.7.024
93.63.7.060
93.63.7.125
93.63.7.220
93.63.0.024
93.63.0.125
93.63.0.240
93.63.8.230
93.63.3.125
93.63.3.230
6 V DC
12 V DC
24 V DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.64.7.024
93.64.7.024
93.64.7.024
93.64.0.024
93.64.0.125
93.64.8.230
6 V DC
12 V DC
24 V DC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.62.7.024
93.62.7.024
93.62.7.024
93.62.0.125
93.62.8.230
12 V AC/DC
24 V AC/DC
34.81.7.012.xxxx
34.81.7.024.xxxx
93.68.0.024
93.68.0.024
VII-2016, www.findernet.com
Solid State Relay (1 Pole 0.1 or 2 A) & Screw Socket Combinations
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
Electromechanical Relay (1 Pole 6 A) & Push-in Socket Combinations
Interface Module Code
MasterBASIC
39.01.0.006.0060
39.01.0.012.0060
39.01.0.024.0060
39.01.0.125.0060
39.01.8.230.0060
MasterPLUS
39.61.0.006.0060
39.61.0.012.0060
39.61.0.024.0060
39.61.0.060.0060
39.61.0.125.0060
39.61.0.240.0060
39.61.8.230.0060
39.61.7.125.0060
39.61.7.220.0060
39.61.3.125.0060
39.61.3.230.0060
MasterINPUT
39.71.0.006.5060
39.71.0.012.5060
39.71.0.024.5060
39.71.0.125.5060
39.71.8.230.5060
MasterOUTPUT 1 NO, 6 A only
39.51.0.006.0060
39.51.0.012.0060
39.51.0.024.0060
39.51.0.125.0060
39.51.8.230.0060
MasterTIMER
39.91.0.012.0060
39.91.0.024.0060
Coil voltage
Relay
Socket
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
93.60.7.024
93.60.7.024
93.60.7.024
93.60.0.125
93.60.8.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
60 V AC/DC
(110…125)V AC/DC
(24…240)V AC/DC
(230…240)V AC
(110…125)V DC
220 V DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
93.66.7.024
93.66.7.024
93.66.7.024
93.66.7.060
93.66.0.125
93.66.0.240
93.66.8.230
93.66.7.125
93.66.7.220
93.66.3.125
93.66.3.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.5010
34.51.7.012.5010
34.51.7.024.5010
34.51.7.060.5010
34.51.7.060.5010
93.67.7.024
93.67.7.024
93.67.7.024
93.67.0.125
93.67.8.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
93.65.7.024
93.65.7.024
93.65.7.024
93.65.0.125
93.65.8.230
12 V AC/DC
24 V AC/DC
34.51.7.012.0010
34.51.7.024.0010
93.69.0.024
93.69.0.024
B
VII-2016, www.findernet.com
Solid State Relay (1 Pole 0.1 or 2 A) & Push-in Socket Combinations
Example: .xxxx
.9024
.7048
.8240
Interface Module Code
MasterBASIC
39.00.7.006.xxxx
39.00.7.012.xxxx
39.00.7.024.xxxx
39.00.0.125.xxxx
39.00.8.230.xxxx
MasterPLUS
39.60.7.006.xxxx
39.60.7.012.xxxx
39.60.7.024.xxxx
39.60.7.060.xxxx
39.60.7.125.xxxx
39.60.7.220.xxxx
39.60.0.024.xxxx
39.60.0.125.xxxx
39.60.0.240.xxxx
39.60.8.230.xxxx
39.60.3.125.xxxx
39.60.3.230.xxxx
MasterINPUT
39.70.7.006.xxxx
39.70.7.012.xxxx
39.70.7.024.xxxx
39.70.0.024.xxxx
39.70.0.125.xxxx
39.70.8.230.xxxx
MasterOUTPUT
39.50.7.006.xxxx
39.50.7.012.xxxx
39.50.7.024.xxxx
39.50.0.125.xxxx
39.50.8.230.xxxx
MasterTIMER
39.90.0.012.xxxx
39.90.0.024.xxxx
Input voltage
Relay
Socket
6 V DC
12 V DC
24 V DC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.60.7.024
93.60.7.024
93.60.7.024
93.60.0.125
93.60.8.230
6 V DC
12 V DC
24 V DC
60 V DC
(110…125)V DC
220 V DC
24 V AC/DC
(110…125)V AC/DC
(24…240)V AC/DC
(230…240)V AC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.66.7.024
93.66.7.024
93.66.7.024
93.66.7.060
93.66.7.125
93.66.7.220
93.66.0.024
93.66.0.125
93.66.0.240
93.66.8.230
93.66.3.125
93.66.3.230
6 V DC
12 V DC
24 V DC
24 V AC/DC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.67.7.024
93.67.7.024
93.67.7.024
93.67.0.024
93.67.0.125
93.67.8.230
6 V DC
12 V DC
24 V DC
(110…125)V AC/DC
(230…240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.65.7.024
93.65.7.024
93.65.7.024
93.65.0.125
93.65.8.230
12 V AC/DC
24 V AC/DC
34.81.7.012.xxxx
34.81.7.024.xxxx
93.69.0.024
93.69.0.024
25
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
MasterBASIC ATEX version, Screw Socket Combinations
Interface Module Code
MasterBASIC ATEX
39.11.0.006.0073
39.11.0.012.0073
39.11.0.024.0073
39.11.0.125.0073
39.11.0.240.0073
39.11.8.230.0073
39.11.7.006.0073
39.11.7.012.0073
39.11.7.024.0073
B
Coil voltage
Relay
Socket
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(24…240)V AC/DC
(230…240)V AC
6 V DC
12 V DC
24 V DC
34.51.7.005.0000
34.51.7.012.0000
34.51.7.024.0000
34.51.7.060.0000
34.51.7.024.0000
34.51.7.060.0000
34.51.7.005.0000
34.51.7.012.0000
34.51.7.024.0000
93.61.0.024.7
93.61.0.024.7
93.61.0.024.7
93.61.0.125.7
93.61.0.240.7
93.61.8.230.7
93.61.7.024.7
93.61.7.024.7
93.61.7.024.7
MasterBASIC ATEX version, Push-in Socket Combinations
Input voltage
Relay
Socket
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125)V AC/DC
(24…240)V AC/DC
(230…240)V AC
6 V DC
12 V DC
24 V DC
34.51.7.005.0000
34.51.7.012.0000
34.51.7.024.0000
34.51.7.060.0000
34.51.7.024.0000
34.51.7.060.0000
34.51.7.005.0000
34.51.7.012.0000
34.51.7.024.0000
93.60.0.024.7
93.60.0.024.7
93.60.0.024.7
93.60.0.125.7
93.60.0.240.7
93.60.8.230.7
93.60.7.024.7
93.60.7.024.7
93.60.7.024.7
VII-2016, www.findernet.com
Interface Module Code
MasterBASIC ATEX
39.01.0.006.0073
39.01.0.012.0073
39.01.0.024.0073
39.01.0.125.0073
39.01.0.240.0073
39.01.8.230.0073
39.01.7.006.0073
39.01.7.012.0073
39.01.7.024.0073
26
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
Accessories
Output fuse module for 39.31/30/81/80/61/60/91/90 types
- For 5 x 20 mm fuses up to 6 A, 250 V
- Easy visibility of the fuse condition through the window
- Type 093.63.0.024 - (6…24)V AC/DC
- Type 093.63.8.230 - (110…240)V AC
- Quick connection to socket
093.63
Approvals
(according to type):
093.63
093.63.0.024
093.63.8.230
Notes
Safety: Because the output circuit can be reinstated (point 3 below), even with the fuse removed, it is important not to
consider the removal of the fuse as a “safety disconnect”. Always isolate elsewhere before working on the circuit.
UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse certified
according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output interface to a PLC
no such restrictions apply, and the fuse module can be usefully employed.
Type 093.63
Type 093.63.0.24 / 093.63.8.230
093.63.0.024
093.63.8.230
Multi-state fuse module
0. A
s delivered, the socket comes without a fuse module. However, the absent fuse is internally replaced with an electrical link
- which allows the interface relay to be used without a fuse module.
In this state, the peg/indicator is visually hidden and the connection is protected by a special cap.
1. With fuse module inserted after removing the cap, the fuse is positioned electrically in series with the common output
terminal of the interface module (11 for EMR versions, 13+ for SSR versions, 15 for EMR timer, 15+ for SSR timer).
This state is indicated by the peg/indicator.
2. If the fuse module is extracted (for example; because the fuse element has blown) the output circuit will be locked open, as
this will generally be the “safe option”.
This state is indicated by the peg/indicator.
VII-2016, www.findernet.com
3. In order to reinstate the output circuit it is necessary to either re-insert the fuse module (complete with functional fuse), or
alternatively, return the peg/indicator to position 0 by gently applying pressure in the direction of the arrow.
27
B
39
SERIES
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
Accessories
16-way jumper link
Rated values
Possibility of multiple connection, side by side
093.16
093.16 (blue)
6 A - 250 V
093.16.0 (black)
093.16.1 (red)
093.16.0
B
093.16.1
Approvals
(according to type):
Dual-purpose plastic separator (1.8 mm or 6.2 mm separation)
093.60
1. By breaking off the protruding ribs (by hand), the separator becomes only 1.8 mm thick; useful for the visual separation of
different groups of interfaces, or necessary for the protective separation of different voltages of neighbouring interfaces, or
for the protection of cut ends of jumper links.
093.60
2. Leaving the ribs in place provides 6.2 mm separation. Simply cutting (with scissors) the relevant segment(s) permits the
interconnection across the separator of 2 different groups of interface relays, using the standard jumper link.
Sheet of marker tags, plastic, 72 tags, 6 x 12 mm
060.72
Sheet of marker tags (CEMBRE'S Thermal transfer printers) ,48 tags, 6 x 12 mm
060.48
060.48
28
VII-2016, www.findernet.com
060.72
39 SERIES
Relay interface modules 0.1 - 2 - 6 A
39
SERIES
Accessories
Terminal doubler (for Push-in sockets only)
093.62
Total load
6 A - 300 V
Solid and stranded cable
Max. wire size
mm
2
2 x 1.5
AWG 2 x 16
B
MasterADAPTER
093.68.14.1
The MasterADAPTER permits the easy connection of A1/A2 terminals of up to MasterINTERFACE modules to PLC outputs via
a 14-Pole ribbon cable, plus simple 2-wire power supply connection ATEX Version.
Technical data
Rated current (per signal path)
A 1
Minimum required supply power
W 3
Nominal voltage (UN)V DC 24
093.68.14.1
Operating range
(0.8…1.1)UN
Approvals
(according to type):
Control logic
Positive switching (to A1)
Power supply status indication
Green LED
Ambient temperature range
°C –40…+70
Terminals for 24 V control logic
Type of connector
14 pole, according to IEC 60603-13
ATEX version
II 3G Ex nA IIC Gc
Terminals for 24 V power supply
Wire strip length
mm 9.5
Screw torque
Nm 0.5
Max. wire size
solid wire
mm2 1 x 4 / 2 x 1.5
AWG 1 x 12 / 2 x 16
Connected MasterADAPTER
stranded wire
mm2 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16
VII-2016, www.findernet.com
Wiring diagram
29