MMD-TA-11B/MMD-TA-12B Muting Module
Instruction Manual
Original Instructions
116390 Rev. D
26 June 2019
© Banner Engineering Corp. All rights reserved
116390
MMD-TA-11B/MMD-TA-12B Muting Module
Contents
1 About This Document
.....................................................................................................................................................4
1.1 Important . . . Read This Before Proceeding!
.................................................................................................................................. 4
1.2 Use of Warnings and Cautions
........................................................................................................................................................ 4
2 Introduction
.................................................................................................................................................................... 5
2.1 Features
.......................................................................................................................................................................................... 5
2.2 Functional Overview
........................................................................................................................................................................ 5
2.2.1 Operating Status LEDs and Diagnostic Display
.......................................................................................................................6
2.2.2 Automatic or Monitored Manual Reset Select
......................................................................................................................... 7
2.2.3 Lockout Conditions
................................................................................................................................................................. 8
2.2.4 Control Reliability: Redundancy and Self-Checking
................................................................................................................ 8
2.2.5 Muteable Safety Stop Interface (MSSI)
.................................................................................................................................... 8
2.2.6 Safety (Protective) Stop Interface (SSI)
.................................................................................................................................... 8
2.2.7 Output Signal Switching Device (OSSD) Outputs
.................................................................................................................... 8
2.2.8 Auxiliary Output (Aux)
...............................................................................................................................................................9
2.2.9 External Device Monitoring (EDM)
...........................................................................................................................................9
2.2.10 Mute Inputs (M1–M4) and Mute Devices
.............................................................................................................................. 9
2.2.11 Mute Enable (ME)
................................................................................................................................................................ 10
2.2.12 Mute Lamp Output (ML)
....................................................................................................................................................... 10
2.2.13 Backdoor Timer
...................................................................................................................................................................10
2.2.14 Mute on Power-Up
............................................................................................................................................................... 11
2.2.15 Override
................................................................................................................................................................................11
2.2.16 One-Way/Two-Way Muting
................................................................................................................................................ 12
2.3 Designated and Qualified Persons
................................................................................................................................................ 12
3 Specifications
............................................................................................................................................................... 13
3.1 Dimensions
................................................................................................................................................................................... 15
4 System Installation
........................................................................................................................................................ 16
4.1 Appropriate Application
................................................................................................................................................................. 16
4.2 Muting Application Design
............................................................................................................................................................17
4.3 Use of Corner Mirrors with Optical Safety Systems
..................................................................................................................... 17
4.4 Multiple Presence-Sensing Safety Devices (PSSDs)
....................................................................................................................17
4.5 Pass-Through Hazards
.................................................................................................................................................................. 17
4.5.1 Reducing or Eliminating Pass-Through Hazards
................................................................................................................... 18
4.6 Installing the Module
......................................................................................................................................................................18
4.7 Muting Module Configuration
....................................................................................................................................................... 18
........................................................................................................................................... 19
4.8 Connection Terminals and Functions
4.8.1 Remove a Terminal Block
..................................................................................................................................................... 21
4.9 Installing Input Devices
................................................................................................................................................................. 22
4.9.1 Manual Reset Switch
..............................................................................................................................................................22
4.9.2 Muting Devices
.......................................................................................................................................................................22
4.10 Mute Lamp Output (ML)
...............................................................................................................................................................25
4.11 Auxiliary Output (AUX)
................................................................................................................................................................ 25
4.12 Override Switch Wiring
................................................................................................................................................................ 26
4.13 SSI and MSSI Interfacing
.............................................................................................................................................................26
4.14 Safety Circuit Integrity and ISO 13849-1
..................................................................................................................................... 27
4.14.1 Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles
..................................................................................... 27
4.14.2 Safety Circuit Integrity Levels
...............................................................................................................................................27
4.14.3 Fault Exclusion
..................................................................................................................................................................... 27
4.15 Generic SSI and MSSI Wiring
...................................................................................................................................................... 27
4.15.1 Category 2
............................................................................................................................................................................28
4.15.2 Category 3
............................................................................................................................................................................28
4.15.3 Category 4
...........................................................................................................................................................................30
4.16 SSI Emergency Stop Switch Device Wiring
................................................................................................................................31
4.16.1 Emergency Stop Push Button Switches
............................................................................................................................. 31
4.16.2 Safety Circuit Integrity Levels and Emergency Stop Functions
.......................................................................................... 31
4.16.3 Category 2
...........................................................................................................................................................................31
4.16.4 Category 3
...........................................................................................................................................................................32
4.16.5 Category 4
...........................................................................................................................................................................32
4.17 SSI/MSSI Interlocked Guard or Gate Wiring
.............................................................................................................................. 33
4.17.1 Safety Circuit Integrity Levels
..............................................................................................................................................33
4.17.2 Safety Interlock Switch Requirements
................................................................................................................................. 33
4.17.3 Positive-Opening Safety Interlocking Switches
................................................................................................................... 34
4.17.4 Monitoring Series-Connected Safety Interlock Switches
.................................................................................................... 34
4.17.5 Category 2
...........................................................................................................................................................................35
4.17.6 Category 3
...........................................................................................................................................................................35
MMD-TA-11B/MMD-TA-12B Muting Module
4.17.7 Category 4
...........................................................................................................................................................................36
....................................................................................................................................36
4.18 SSI Supplemental Safety System Wiring
5 Machine Interface - Initial Wiring and Checkout
.......................................................................................................... 38
5.1 Verifying System Operation
.......................................................................................................................................................... 38
5.2 Temporary Power and Initial Checkout
........................................................................................................................................ 38
6 Permanent Wiring to the Guarded Machine
.................................................................................................................. 40
6.1 Mute Enable Wiring
.......................................................................................................................................................................45
6.2 External Device Monitoring (EDM) Wiring
..................................................................................................................................... 45
6.3 Output Signal Switching Device (OSSD) Output Connections
..................................................................................................... 46
6.4 FSD Interfacing Connections
........................................................................................................................................................46
6.4.1 Safety (Protective) Stop Circuits
........................................................................................................................................... 46
6.5 Commissioning Checkout
.............................................................................................................................................................47
7 Operating Instructions
.................................................................................................................................................. 48
7.1 Security Protocol
.......................................................................................................................................................................... 48
7.2 Periodic Checkout Requirements
.................................................................................................................................................. 48
7.3 Normal Operation
.......................................................................................................................................................................... 48
8 Troubleshooting
............................................................................................................................................................50
8.1 Troubleshooting Lockout Conditions
............................................................................................................................................ 50
8.2 Diagnostic Display
......................................................................................................................................................................... 50
8.3 Effects of Electrical Noise
............................................................................................................................................................. 50
8.4 Troubleshooting Conditions, using the Module’s Diagnostic Display
........................................................................................... 50
9 Periodic Checkout Procedure
...................................................................................................................................... 52
9.1 Schedule of Checkouts
.................................................................................................................................................................52
9.2 Commissioning Checkout
.............................................................................................................................................................52
9.2.1 Safeguarding Checkout
.........................................................................................................................................................53
9.2.2 Muting Checkout
................................................................................................................................................................... 54
9.3 Daily Checkout
..............................................................................................................................................................................54
9.4 Semi-Annual Checkout
................................................................................................................................................................. 55
10 Mute Timing Sequences
.............................................................................................................................................56
10.1 Muting Sequence with Two Muting Devices
10.2 Muting Sequence with Four Muting Devices
11 Typical Muting Applications
............................................................................................................................... 56
.............................................................................................................................. 56
....................................................................................................................................... 58
11.1 Entry/Exit Applications
................................................................................................................................................................58
11.2 Home or Station Applications
..................................................................................................................................................... 60
11.3 Robot Load/Unload Station Application
..................................................................................................................................... 60
11.4 Turret Table Application
..............................................................................................................................................................61
11.5 Power Press Applications
........................................................................................................................................................... 62
12 Accessories
................................................................................................................................................................. 64
12.1 Solid-State LED-Based Mute Lamp
............................................................................................................................................ 64
12.2 Interface Modules
....................................................................................................................................................................... 64
12.2.1 Mechanically Linked Contactors
......................................................................................................................................... 64
13 Product Support and Maintenance
............................................................................................................................ 65
13.1 Repairs
.........................................................................................................................................................................................65
13.2 Banner Engineering Corp Limited Warranty
............................................................................................................................... 65
13.3 Contact Us
...................................................................................................................................................................................65
14 Standards and Regulations
......................................................................................................................................... 66
14.1 U.S. Application Standards
......................................................................................................................................................... 66
14.2 OSHA Regulations
...................................................................................................................................................................... 66
14.3 International/European Standards
.............................................................................................................................................. 67
15 Glossary
......................................................................................................................................................................68
MMD-TA-11B/MMD-TA-12B Muting Module
1 About This Document
1.1 Important . . . Read This Before Proceeding!
It is the responsibility of the machine designer, controls engineer, machine builder, machine operator, and/or maintenance
personnel or electrician to apply and maintain this device in full compliance with all applicable regulations and standards.
The device can provide the required safeguarding function only if it is properly installed, properly operated, and properly
maintained. This manual attempts to provide complete installation, operation, and maintenance instruction. Reading the
manual in its entirety is highly recommended. Please direct any questions regarding the application or use of the device to
Banner Engineering.
For more information regarding U.S. and international institutions that provide safeguarding application and safeguarding
device performance standards, see Standards and Regulations (p. 66).
WARNING:
• The user is responsible for following these instructions.
• Failure to follow any of these responsibilities may potentially create a dangerous condition that
could result in serious injury or death.
• Carefully read, understand, and comply with all instructions for this device.
• Perform a risk assessment that includes the specific machine guarding application. Guidance on
a compliant methodology can be found in ISO 12100 or ANSI B11.0.
• Determine what safeguarding devices and methods are appropriate per the results of the risk
assessment and implement per all applicable local, state, and national codes and regulations.
See ISO 13849-1, ANSI B11.19, and/or other appropriate standards.
• Verify that the entire safeguarding system (including input devices, control systems, and output
devices) is properly configured and installed, operational, and working as intended for the
application.
• Periodically re-verify, as needed, that the entire safeguarding system is working as intended for
the application.
1.2 Use of Warnings and Cautions
The precautions and statements used throughout this document are indicated by alert symbols and must be followed for
the safe use of the MMD-TA-11B/MMD-TA-12B Muting Module. Failure to follow all precautions and alerts may result in
unsafe use or operation. The following signal words and alert symbols are defined as follows:
Signal Word
Definition
WARNING
Warnings refer to potentially hazardous situations which, if not
avoided, could result in serious injury or death.
CAUTION
Cautions refer to potentially hazardous situations which, if not
avoided, could result in minor or moderate injury.
Symbol
These statements are intended to inform the machine designer and manufacturer, the end user, and maintenance
personnel, how to avoid misapplication and effectively apply the MMD-TA-11B/MMD-TA-12B Muting Module to meet the
various safeguarding application requirements. These individuals are responsible to read and abide by these statements.
4
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
2 Introduction
2.1 Features
•
•
•
•
•
•
•
•
•
•
•
Compact, 67.5 mm (2.7 in) DIN-mounted housing with plug-in terminal
blocks
For use with Output Signal Switching Device (OSSD) outputs, such as
the outputs of the various families of EZ-SCREEN® light curtain and
safety laser scanner, or other safety devices with hard relay contact
safety outputs, or +24 V dc (PNP) outputs.
Monitors two or four inputs to automatically suspend the safety
function of a safeguarding device
Can be used as a dual controller when muting function is not used
Safety (protective) Stop Interface (SSI) for connection of supplemental
safeguarding devices, E-stops, or other devices
Category 2, 3, or 4 wiring per ISO 13849-1/-2
Selectable external device monitoring (EDM)
Selectable Automatic or Monitored Manual Reset provides flexibility for
point-of-operation, area, or perimeter guarding
Two normally open (N.O.) safety contacts (model MMD-TA-11B) or
diverse-redundant solid-state safety outputs (model MMD-TA-12B)
Status LEDs and two-digit Diagnostic Display indicate module status
Easy configuration for:
◦ Auto/manual reset
◦ One-/two-channel EDM
◦ One-/two-direction muting
◦ Selectable mute enable
◦ Monitored/non-monitored mute lamp
◦ Selectable backdoor timer
◦ Selectable mute on power-up
2.2 Functional Overview
The Banner MMD-TA-11B / MMD-TA-12B Muting Module (the Module) is an accessory component of a safeguarding
system, which may incorporate such primary safeguards as safety light screens, safety interlocked gates/guards, or other
presence-sensing safeguarding devices (PSSDs). The Muting Module monitor the redundant mute device inputs and
automatically suspend the safeguarding function of a device during the non-hazardous portion of the machine cycle.
In this manual, the term muting refers to the automatic suspension of the safeguarding function of the primary safety device
during a non-hazardous portion of the machine cycle where personnel are not exposed to harm.
The muting function allows material to be manually or automatically fed into or removed from a machine process, without
tripping the primary safety device. The Muting Module accomplishes this by using redundant microprocessors that monitor
the status of inputs and outputs, so that a single fault will cause the receiver to issue a stop command to the machine. The
Muting Module, like all Banner safety products, is extensively Failure Mode and Effects Analysis (FMEA) tested to establish
an extremely high degree of confidence that no internal component will, even if it does fail, cause a failure to danger. This
design philosophy aids machine designers to comply with U.S. control reliability and worldwide standards for the highest
level of safety.
www.bannerengineering.com - Tel: + 1 888 373 6767
5
MMD-TA-11B/MMD-TA-12B Muting Module
Safety Light Screen
Defined Area
Safety Light
Screen Control
MMD-TA-..
Muting Module
FSD2/OSSD2
CH B
FSD1/OSSD1
CH A
+24V dc
0V dc
MSSI
Machine
Interface
+24V dc
OSSD1*
OSSD2*
EDM1
EDM2
Mute
Enable
0V dc
GND
Mute Devices
M1, M2, M3, M4
Override
Reset
SSI
AUX* Mute
Lamp
* Model MMD-TA-11B: These are relay contact outputs
Model MMD-TA-12B: This is a solid-state output
Figure 1. Block diagram of a safeguarding system employing the Muting Module and a safety light screen (user-supplied) as a primary safety device
Individual features discussed in the following sections are:
• Operating status LEDs and diagnostic display
• Auto/manual reset
• Lockout conditions
• Control reliability
• Mutable Safety Stop Interface (MSSI)
• Safety Stop Interface (SSI)
• Output Signal Switching Device (OSSD) outputs
• Auxiliary (AUX) output
• External device monitoring (EDM)
• Mute devices and mute inputs (M1−M4)
• Mute enable input (ME)
• Mute lamp output (ML)
• Backdoor timer
• Mute on power-up
• Override
• One-way/two-way muting
2.2.1 Operating Status LEDs and Diagnostic Display
The Module has three Operating Status LEDs (one each red, amber, and green), plus a 2-digit Diagnostic Display, visible
through a window in the front cover. The individual LEDs provide constant, ongoing system status information at a glance.
The Diagnostic Display provides error codes that correspond to the cause of a fault or configuration error which results in a
lockout, and other more detailed conditions. See Operating Instructions (p. 48) and Troubleshooting (p. 50) for further
information.
6
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
A
Key
B
G
C
F
D
Description
A
Safety Stop Inputs (SSI) Active LEDs (green)
B
Muteable Safety Stop Input(s) (MSSI) Active LEDs (green)
C
2-Digit Diagnostic Display
D
Red, Green, Amber Status LEDs
E
Reset Input (green)
F
Muting Devices Status LEDs (amber)
G
Override Active LEDs (amber)
E
Figure 2. Muting Module features
Note: A green or amber indicator is provided for each input to verify an active state. A green indicator is
provided for the Reset Input and for MSSI and SSI inputs. An amber indicator is provided for each of the
mute device (M1–M4) and override inputs.
2.2.2 Automatic or Monitored Manual Reset Select
The selectable Automatic or Monitored Manual Reset (X1−X2) provides flexibility for the user who has applications in which
the operator is continually sensed, or in applications where the operator can pass through and become clear of the sensing
field (see Pass-Through Hazards (p. 17)) or other applications requiring a manual reset.
The configuration is selected via two banks of DIP switches located under the Module’s front cover.
Monitored Manual Reset
Manual Reset is typically used in situations where the individual can pass through a sensing field and become clear of a
safeguarding device, such that the device can no longer prevent hazardous motion (for example, perimeter guarding). The
Module monitors the input for two transitions: from open-to-closed, and from closed-to-open within a certain time period.
This prevents the reset button from being tied down or failing in a closed condition, and causing an unintended or automatic
reset.
Upon power-up, when the Module has been configured for manual reset, for the Output Signal Switching Device (OSSD)
outputs to turn ON, both the Muteable Safety Stop Interface (MSSI) and the Safety (Protective) Stop Interface (SSI) must be
active (closed) and a monitored manual reset must be accomplished. The reset is accomplished by closing the Reset input
for a minimum of 1/4 second, but not longer than 2 seconds and then re-opening the input. The OSSD outputs will turn ON
once the open-closed-open action occurs.
In this configuration, the Module must be manually reset after power-up, lockouts, and after the cycling of either the MSSI
(not muted) or the SSI. The location for the manual reset device (for example, a normally open key switch) must comply with
the warning in Manual Reset Switch (p. 22) and refer to that section for further information on key resets.
Automatic Reset
Upon power-up, when the Module is configured for automatic reset, the Output Signal Switching Device (OSSD) outputs will
automatically turn ON once power is applied, the self-test is accomplished, and the Muteable Safety Stop Interface (MSSI)
and the Safety (Protective) Stop Interface (SSI) are active (closed). The OSSD outputs will also turn ON after either interface
is de-activated and then re-activated. In either case, no external input or reset is required.
Automatic reset is typically used in situations where the individual is continually sensed by the defined area or in situations
where supplemental safeguards prevent the initiation of hazardous motion while an individual is within the safeguarded
space (for example, point-of-operation guarding).
In either case, a manual reset must be performed to recover from a lockout condition.
www.bannerengineering.com - Tel: + 1 888 373 6767
7
MMD-TA-11B/MMD-TA-12B Muting Module
In Automatic Reset mode, input X1−X2 stays open.
2.2.3 Lockout Conditions
A lockout condition of the Module will cause both Output Signal Switching Device (OSSD) outputs to go OFF. A lockout
condition is indicated by a flashing Red status indicator and an error number displayed on the Diagnostic Display.
A description of possible lockouts, their causes, troubleshooting hints, and a Manual Reset routine are listed in
Troubleshooting (p. 50).
2.2.4 Control Reliability: Redundancy and Self-Checking
Redundancy requires that Module circuit components be backed up to the extent that, if the failure of a single component
will prevent effective machine stopping action when needed, that component must have a redundant counterpart which will
perform the same function. The microprocessor-controlled Muting Module is designed with diverse redundancy. Diverseredundant components are of different designs, and microprocessor programs used by them run from different instruction
sets.
Redundancy must be maintained for as long as the Muting Module is in operation. Since a redundant system is no longer
redundant once a component has failed, the Module is designed to be continuously self-checking. A component failure
detected by or within the self-checking system causes a stop signal to be sent to the guarded machine and puts the
Module into a lockout condition.
Recovery from this type of lockout condition requires replacement of the failed component (to restore redundancy) and the
appropriate reset procedure (see Manual Reset Switch (p. 22)). Possible causes are listed in Troubleshooting (p. 50). The
Diagnostic Display is used to diagnose causes of a lockout condition.
2.2.5 Muteable Safety Stop Interface (MSSI)
The Muteable Safety Stop Interface (MSSI) input (S11−S12, S21−S22) is a specialized Safety (Protective) Stop Interface
(SSI) that can be muted during the non-hazardous portion of the machine cycle.
The Module requires redundant input signals from the external primary safeguard which is to be muted. These inputs
typically are either two solid-state safety outputs or two monitored forced-guided relay outputs from an appropriate safety
device. For complete information, see Specifications (p. 13) and SSI and MSSI Interfacing (p. 26).
WARNING:
• Emergency Stop Functions
• Muting or bypassing the safety outputs will render the Emergency Stop function ineffective.
• Do not connect any Emergency Stop devices to the MSSI Input; do not mute or bypass any
Emergency Stop device. ANSI NFPA79 and IEC/EN 60204-1 require that the Emergency Stop
function remain active at all times.
2.2.6 Safety (Protective) Stop Interface (SSI)
The Module has a provision for an additional Safety (Protective) Stop Interface (X5−X6, X7−X8) to connect an optional
device, such as a supplemental safeguard, E-stop button, or safety switch(es), to issue a stop command. This dual-channel
interface is similar to the Muteable Safety Stop Interface (MSSI), but is always functional, even when the primary safety
device is being muted. For complete information, see Specifications (p. 13) and SSI and MSSI Interfacing (p. 26).
2.2.7 Output Signal Switching Device (OSSD) Outputs
Model MMD-TA-12B has two solid-state safety outputs (Y5−Y6, Y7−Y8); and model MMD-TA-11B has two normally open
hard-contact safety outputs (13−14, 23−24), labeled “OSSD1” and “OSSD2” (see Figure 1 (p. 6)). The solid-state safety
outputs are actively monitored to detect short circuits to the supply voltage, to each other, and to other sources of electrical
energy. If a failure is detected, the outputs will switch to an OFF-state. For circuits requiring the highest level of safety and
reliability, either OSSD must be capable of stopping the motion of the guarded machine in an emergency.
During the muted portion of the machine cycle, the Muteable Safety Stop Interface (MSSI) inputs will be ignored and
OSSD1 and OSSD2 will remain ON. During other portions (not muted) of the cycle, if the MSSI either open or go OFF,
OSSD1 and OSSD2 will go OFF.
In any case, if the Safety (Protective) Stop Interface (SSI) interface opens, OSSD1 and OSSD2 will go OFF. See Mute Timing
Sequences (p. 56) for timing diagrams.
8
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
2.2.8 Auxiliary Output (Aux)
The Auxiliary (Aux) monitoring PNP (Z3−Z4) output on the MMD-TA-12B and the parallel N.C. contact output on the -11B
are intended for non-safety related purposes. The status of this auxiliary output is indicated by the green Status LED. See
Auxiliary Output (AUX) (p. 25) for more information.
2.2.9 External Device Monitoring (EDM)
Two inputs are provided for monitoring the state of external devices, such as MPCEs. These terminals are labeled “EDM1”
(Y1−Y2) and “EDM2” (Y3−Y4). The Module’s EDM inputs can be configured in three ways: one-channel, two-channel, or no
monitoring. One- and two-channel EDM are used when the Output Signal Switching Device (OSSD) outputs directly control
the de-energizing of the MPCEs or external devices.
•
•
•
One-Channel Monitoring: a series connection of closed monitor contacts that are forced-guided (mechanically
linked) from each device controlled by the Muting Module. The monitor contacts must be closed before the Module
can be reset (either Manual or Automatic). After a reset is executed and the safety outputs (OSSDs) are closed, the
status of the monitor contacts is no longer monitored. However, the monitor contacts must be closed within 200
milliseconds of the OSSD outputs going from ON to OFF.
Two-Channel Monitoring: an independent connection of closed monitor contacts that are forced-guided
(mechanically linked) from each device controlled by the Muting Module. Both EDM inputs must be closed before
the Module can be reset and the OSSDs can turn ON. While the OSSDs are ON, the inputs may change state (either
both open, or both closed). If the inputs remain in opposite states for more than 200 milliseconds, a lockout will
occur. Additionally, both inputs must be closed 200 milliseconds after the OSSD outputs go OFF, or a lockout will
occur.
No Monitoring: If no monitoring is desired, the 1-ch/2-ch selection switches must be configured for two-channel
EDM, and Y1 must be jumpered to Y3. If the Module is set for No Monitoring, the user must ensure that any single
failure of the external devices does not result in a hazardous condition and a successive machine cycle will be
prevented (see Control Reliability: Redundancy and Self-Checking (p. 8)).
2.2.10 Mute Inputs (M1–M4) and Mute Devices
Muting Function
To mute the primary safeguard appropriately, the design of a muting system must:
1. Identify the non-hazardous portion of the machine cycle.
2. Select the proper muting devices.
3. Include proper mounting and installation of those devices.
The Module can monitor and respond to redundant signals that initiate the mute (M1: Z11–Z21; M2: Z12–Z22; M3: Z13–Z23;
M4: Z14–Z24). The mute then suspends the safeguarding function by ignoring the state of the Muteable Safety Stop
Interface (MSSI). This allows a person to interrupt the defined area to load and/or unload parts or an object to pass through
the defined area of a safety light screen, without generating a stop command. (This should not be confused with blanking,
which disables one or more beams in a safety light screen, resulting in larger resolution.) See Mute Timing Sequences (p.
56) for example mute timing sequences.
The mute may be triggered by a variety of external devices. This feature provides a variety of options to tailor the System to
the requirements of a specific application.
A pair of muting devices must be triggered simultaneously (within 3 seconds of one another). This reduces the chance of
common mode failures or defeat.
WARNING:
• Muting is allowed only during the non-hazardous portion of the machine cycle
• Failure to follow these instructions could result in serious injury or death.
• Design the muting application so that no single component failure can prevent the stop
command or allow subsequent machine cycles until the failure is corrected (per ISO 13849-1 and
ANSI B11.19).
WARNING:
• Muting inputs must be redundant
• A single device, with multiple outputs, can fail so that the system is muted at an inappropriate
time, causing a hazardous situation.
• Do not use a single switch, device, or relay with two normally open contacts for the mute inputs.
www.bannerengineering.com - Tel: + 1 888 373 6767
9
MMD-TA-11B/MMD-TA-12B Muting Module
Mute Devices
The beginning and end of a mute cycle must be triggered by outputs from either pair of muting devices, depending on the
application. The mute device pairs both must have normally open contacts, or have one device with a PNP output and one
device with an NPN output, both of which fulfill the muting device requirements in Specifications (p. 13) and Muting
Devices (p. 22). These contacts must close (conduct) when the switch is actuated to initiate the mute, and must open
(non-conducting) when the switch is not actuated and in a power-OFF condition.
The Module monitors the mute devices to verify that their outputs turn ON within 3 seconds of each other. If the inputs do
not meet this simultaneity requirement, a mute condition can not occur.
Several types and combinations of mute devices can be used, including, but not limited to: limit switches, photoelectric
sensors, positive-driven safety switches, inductive proximity sensors, and whisker switches.
2.2.11 Mute Enable (ME)
The Mute Enable input (X13−X14) is a non-safety-rated input. When the input is closed (terminals X13−X14 jumpered), the
Module will allow a mute condition to occur; opening this input while the System is muted will have no effect. The Module is
factory-supplied with a jumper installed between terminals X13−X14. To use the Mute Enable function, remove the jumper.
Typical uses for Mute Enable include:
• Allow the machine control logic to create a window for muting to begin
• Inhibit muting from occurring
• Reduce the chance of unauthorized or unintended bypassing or defeat of the safety system
Simultaneity Timer Reset Function
The Mute Enable (ME) input can also be used to reset the simultaneity timer of the mute inputs. If one input is active for
longer than three seconds before the second input becomes active, the simultaneity timer will prevent a mute cycle from
occurring. This could be due to a normal stoppage of an assembly line that may result in blocking one mute device and the
simultaneity time running out.
If the ME input is cycled (closed-open-closed) while one mute input is active, the simultaneity timer is reset, and if the
second mute input becomes active within three seconds, a normal mute cycle begins. The timing requirement for the
closed-open-closed is similar to the manual reset function. Initially, the input needs to be active (closed) for longer than 1/4
second, then open for longer than 1/4 second, but not longer than 2 seconds, and then must re-close to reset the
simultaneity timer. The function can reset the timer only once per mute cycle (that is, all mute inputs M1−M4 must open
before another reset can occur).
2.2.12 Mute Lamp Output (ML)
Some applications require that a lamp (or other means) be used to indicate when the safety device (for example, light
screen) is muted; the module provides for this (X3−X4; see Caution below). This indication is selectable between a
monitored or a non-monitored output signal (NPN sinking). The monitored output will prevent the initiation of a mute after an
indicator failure is detected (current draw falls below 10 mA or goes above 360 mA). If the application requires compliance
with UL 61496, Lamp Monitoring must be selected and the lamp used must meet applicable requirements (see Mute Lamp
Output (ML) (p. 25)).
CAUTION:
• Mute status must be readily observed
• Failure of the mute indicator should be detectable from the location of the muted device and
prevent the next mute.
• Verify the indicator's operation at suitable intervals. Provide easily observed indication that the
safety device is muted. Select lamp monitoring if the application requires compliance with UL
61496.
2.2.13 Backdoor Timer
The Backdoor Timer allows the user to select a maximum period of time that muting is allowed to occur. This feature
hinders the intentional defeat of the muting devices to initiate an inappropriate mute. It is also useful for detecting a
common mode failure that would affect all mute devices in the application.
The timer begins when the second muting device makes the simultaneity requirement (within 3 seconds of the first device),
and will allow a mute to continue for the predetermined time. After the timer expires, the mute ends – no matter what the
signals from the mute devices indicate. If the Muteable Safety Stop Interface (MSSI) is open, the Output Signal Switching
10
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
Device (OSSD) outputs will turn OFF and must be manually reset (if Module is configured for Manual Reset). The Override
function can be activated to force the OSSDs ON in order to clear the obstruction.
If the Backdoor Timer expires, a #50 error code will be displayed until all mute device inputs are open and the MSSI is
active (closed).
The Backdoor Timer can be disabled (that is, set for infinite time). See Figure 4 (p. 19) and configure DIP switches #5 and
#6 for Backdoor Time-Out OFF.
WARNING:
• Mute Time Limit
• Select an infinite time for the mute time limit (disabling) only if the possibility of an inappropriate
or unintended mute cycle is minimized, as determined and allowed by the machine’s risk
assessment. It is the user’s responsibility to ensure that this does not create a hazardous
situation.
2.2.14 Mute on Power-Up
Mute Enable must be closed to allow Mute on Power-Up. If selected, the Mute on Power-Up function will initiate a mute
when power is applied, the Mute Enable input is closed, the Muteable Safety Stop Interface (MSSI) inputs are active
(closed), and either M1−M2 or M3−M4 (but not all four) are closed.
If Auto Reset is configured, the Module allows 10 seconds for the MSSI and Safety (Protective) Stop Interface (SSI) to
become active (closed) to accommodate systems that may not be immediately active at power-up.
If Manual Reset is configured, the first valid reset after the MSSI and SSI are active (closed) will result in a mute cycle if all
other conditions are satisfied.
WARNING: Mute on Power-Up Function—Only use the Mute on Power-Up function in applications
where:
• Muting the System (M1 and M2 closed) when power is applied is required, and
• Using it does not, in any situation, expose personnel to any hazard.
2.2.15 Override
The Override function (X9−X10, X11−X12) allows the user to manually force the Output Signal Switching Device (OSSD)
outputs ON for up to 30 seconds in a situation such as an object becoming stuck in the defined area of a safety light screen
after the mute ends (for example, a car body on a transfer line entering a work cell). The feature is intended to allow the user
to jog the part out of the defined area. The need to perform an Override is indicated by a flashing mute lamp.
This input requires two normally open switches, both of which must be closed within 3 seconds of each other. The Override
cycle will last a maximum of 30 seconds, after which the Override input must be released for at least 0.5 seconds prior to
the next Override cycle. An Override can be initiated only after tripping of the Muteable Safety Stop Interface (MSSI) inputs
causes the Module to latch its OSSDs OFF. This override is a mute dependent override, so at least one mute sensor must
also be blocked (on).
Note: A stop command issued by the Safety (Protective) Stop Interface (SSI) cannot be overridden.
When Override is used, the following precautions must be taken:
Prevent exposure to any hazard during an Override
•
•
Provide a readily observable indication of an Override
•
Provide supplemental safeguarding, per ANSI NFPA79 and IEC/EN60204-1
The Override switches must be supervised and must prevent automatic operation. Also, one or more of the following must
be true:
•
Motion is initiated by a hold-to-run or similar device
•
If a portable control station (for example, an enabling device) with an emergency stop device is used, motion may
be initiated only from that station
•
Motion, speed, or power of the machine is limited
•
The machine’s range of motion is limited
www.bannerengineering.com - Tel: + 1 888 373 6767
11
MMD-TA-11B/MMD-TA-12B Muting Module
WARNING:
• Limit the use of the bypass and/or override function
• Failure to follow these instructions could result in serious injury or death.
• The bypass and/or override function is not intended for production purposes; use it only for
temporary or intermittent actions, such as to clear the defined area of a safety light screen if
material becomes stuck. When bypass and/or override is used, the user must install and use it
according to applicable standards (such as ANSI NFPA79 or IEC/EN60204-1).
2.2.16 One-Way/Two-Way Muting
One-way (directional) muting allows the safeguard to be muted only if mute devices are actuated in the order M1, M2, (mute
initiated), M3, and M4. This method allows for a single-direction material flow and reduces the possibility of intentional
defeat of the muting devices.
Two-way (non-directional) muting allows the safeguard to be muted any time the actuation of M1−M2 or M3−M4 meets the
3-second simultaneity requirement. This allows the flow of material from either direction (two-way material flow).
Note: The object must activate all four four mute devices (M1, M2, M3 and M4) at one time during the
mute cycle when using four mute devices to extend the mute until the light screen is clear.
2.3 Designated and Qualified Persons
For the purposes of this manual, the following definitions apply:
Designated Person: A person or persons identified and designated in writing, by the employer, as being appropriately
trained and qualified to perform a specified checkout procedure.
Qualified Person: A person or persons who, by possession of a recognized degree or certificate of professional training, or
who, by extensive knowledge, training, and experience, has successfully demonstrated the ability to solve problems relating
to the implementation of this safety system.
12
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
3 Specifications
Overvoltage Category
III (IEC 60664-1)
Pollution Degree
2
Supply Protection Circuitry
All inputs and outputs are protected from short circuit to +24V dc or dc
common.
Status Indicator LEDs
3 Status Indicator LEDs (Red, Green and Amber): indicate waiting for
Reset, Lockout, Override, and OSSD status
Amber and Green LEDs adjacent to individual inputs/interfaces indicate
status (ON = active/ closed)
Diagnostic Code Display
Diagnostic Display is a two-digit numeric display that indicates the
cause of lockout conditions and the amount of time remaining for the
backdoor timer.
Muting Lamp Output
A monitored or non-monitored (selectable) sinking output. If monitoring
has been selected, the current draw must be 10 mA to 360 mA.
Interconnect wire resistance < 30 ohms.
Maximum Switching Voltage: 30 V dc
Maximum Switching Current: 360 mA
Minimum Switching Current: 10 mA
Saturation Voltage: ≤ 1.5V dc at 10 mA; ≤ 5V dc at 360 mA
Controls and Adjustments
All configured on 2 redundant banks of DIP switches:
Manual/auto reset
One-way/two-way muting
Monitored/non-monitored mute lamp output
One-channel/two-channel/no EDM
Backdoor timer
Mute on power-up enable
Inputs
The MSSI and the SSI can be interfaced with external devices that have
either hard contact outputs or solid-state sourcing outputs.
When connecting the MSSI (S11-S12, S21-S22) or SSI (X5-X6, X7-X8)
inputs to relay outputs or hard contacts, these contacts must be
capable of switching 15-30V dc at 10-50 mA.
Operating Range for MSSI and SSI Inputs:
OFF State: -3 V to +5V, 0 to 2 mA
ON State: 15-30 V, 10-50 mA
Muteable Safety Stop Interface (MSSI): This input consists of two
channels (MSSI-A and MSSI-B), and can be muted when the
requirements for a mute cycle have been met. When muted, the OSSDs
remain ON, independent of the MSSI status. If not muted, anytime
either or both channels open, the OSSD outputs will go OFF. Maximum
external resistance per channel must not exceed 400 Ω. (See SSI and
MSSI Interfacing (p. 26) for further information.)
Safety Stop Interface (SSI): This input consists of two channels (SSI-A
and SSI-B), and is always active. Any time either or both channels open,
the OSSD Outputs will go OFF. Maximum external resistance per
channel must not exceed 400 Ω. (See SSI and MSSI Interfacing (p. 26)
for further information.)
External Device Monitoring (EDM)
Two pairs of terminals are provided to monitor the state of external
devices controlled by the OSSD outputs. Each device must be capable
of switching 15-30V dc at 10-50 mA.
Muting Device Inputs
The muting devices work in pairs (M1 and M2, M3 and M4) and are
required to be closed within 3 seconds of each other (simultaneity
requirement/synchronous actuation) to initiate a mute (assuming all
other conditions are met). Each muting device must be capable of
switching 15-30 V dc at 10-50 mA.
Mute Enable Input
The Mute Enable input must have +24V dc applied in order to start a
mute; opening this input after mute has begun has no effect. The
switching device must be capable of switching 15-30 V dc at 10-50 mA.
Override Inputs
The two-channel inputs must be closed within 3 seconds of each other
(simultaneity/synchronous action requirement) and held closed during
the 30-second Override. To initiate a subsequent Override, open both
channels, wait 3 seconds, and then re-close both channels (within 3
seconds). The switching devices must be capable of switching 15-30 V
dc at 10-50 mA.
Reset Input
Terminals must be closed for a minimum of 0.25 seconds and not more
than 2.0 seconds in order to guarantee a reset. The switching device
must be capable of switching 15-30 V dc at 10-50 mA.
Mounting
Mounts to standard 35 mm DIN-rail track
Vibration Resistance
10 Hz to 55 Hz at 0.35 mm displacement per IEC 68-2-6
Construction
Polycarbonate housing.
Environmental Rating
Rated NEMA 1; IEC IP20. Safety Module must be installed inside an
enclosure rated NEMA 3 (IEC IP54) or better.
Connections
Removable terminal blocks; see Figure 5 (p. 20) for terminal locations.
Operating Conditions
Temperature: 0 °C to +50 °C (+32 °F to +122 °F)
95% maximum relative humidity (non-condensing)
Heat Dissipation Considerations: See Installing the Module (p. 18).
Safety Ratings
SIL 3 (IEC 61508); SIL CL 3 (IEC 62061); Category 4, Performance Level
(PL) e (ISO 13849-1)
Model MMD-TA-11B: PFHd of 2 x 10-9
Model MMD-TA-12B: PFHd of 1.2 x 10-9
Application Notes
Mute Timing Sequences: Mute Timing Sequences (p. 56)
Typical Muting Applications: Typical Muting Applications (p. 58)
Application Standards: U.S. Application Standards (p. 66)
Certifications 1
SIL 3 (IEC 61508 & 62061)
ESPE
NIPF
Category 4, PL e
10GH
UL 1998
(ISO 13849-1)
UL 61496
In the E.U., for use as a replacement device only.
1 Contact Banner for IEC 61508/62061 and ISO 13849-1 data.
www.bannerengineering.com - Tel: + 1 888 373 6767
13
MMD-TA-11B/MMD-TA-12B Muting Module
Model MMD-TA-11B
System Power Requirements
Model MMD-TA-11B: +24 V dc ±15% at 300 mA maximum (SELV/
PELV)
(not including draw of the MSSI power, AUX, ML, M1-M4 and OSSD
connections)
The external voltage supply must be capable of buffering brief mains
interruptions of 20 ms, as specified in IEC/EN 60204-1
Response Time (MSSI and SSI)
(relay output) 20 ms maximum
Safety Outputs
Two normally open contact output channels and one normally closed
auxiliary contact output channel: Each normally open output channel is
a series connection of contacts from two forcedguided (positive-guided)
relays, K1-K2. The normally closed AUX contact (non-safety) 31-32 is a
parallel connection of contacts from K1-K2.
Contacts: AgNi, 5 μm gold-plated
Low Current Rating:
CAUTION: The 5 μm gold-plated contacts
allow the switching of low current/low
voltage. In these low-power applications,
multiple contacts can also be switched in
series (for example, dry switching). To
preserve the gold plating on the contacts
and also guarantee reliable switching, the
following values should be kept within the
minimum and maximum ranges.
Minimum voltage: 1V ac/dc
Maximum voltage: 60V
Minimum current: 5 mA ac/dc
Maximum current: 300 mA
Minimum power: 5 mW (5 mVA)
Maximum power: 7 W (7 VA)
High Current Rating: If higher loads must be switched through one or
more of the contacts, the minimum and maximum values of the
contact(s) changes to:
Minimum voltage: 15V ac/dc
Maximum voltage: 120V ac/dc
Minimum current: 30 mA ac/dc
Maximum current: 6 A
Minimum power: 0.45 W (0.45
VA)
Maximum power: 160 W (720
VA)
Non-Safety Outputs
Aux. output 31-32 is a parallel connection of two N.C. contacts from
internal relays K1 and K2.
Contact: AgNi, 5 µm gold-plated
Low Current Rating:
CAUTION: The 5 µm gold-plated contacts
allow the switching of low current/low
voltage. To preserve the gold plating on the
contacts and also guarantee reliable
switching, the following values should be
kept within the minimum and maximum
ranges.
Minimum Voltage: 1 V ac/dc
Maximum Voltage: 24 V ac/dc
Minimum Current: 5 mA ac/dc
Maximum Current: 250 mA
ac/dc
Minimum Power: 5 mW (5 mVA)
Maximum Power: 6 W (6 VA)
High Current Rating: For higher loads, the min. and max. values of the
contact(s) changes to:
Minimum Voltage: 15V ac/dc
Maximum Voltage: 24V ac/dc
Minimum Current: 30 mA ac/dc
Maximum Current: 250 mA
ac/dc
Minimum Power: 0.45 W
(0.45VA)
Maximum Power: 6 W (6VA)
Mechanical Life: 50,000,000 operations
Electrical Life: >10 x 106 cycles
Mechanical life: 50,000,000 operations
Electrical life: 120,000 operations (typical, at 144 W [1,380 VA] switched
power, resistive load)
Note: Transient suppression is recommended
when switching inductive loads. Install
suppressors across load. Never install
suppressors across output contacts (see
Warning, in Permanent Wiring to the Guarded
Machine (p. 40)).
Model MMD-TA-12B
System Power Requirements
+24 V dc ±15% at 250 mA maximum (SELV/PELV)
(not including draw of the MSSI power, AUX, ML, M1-M4 and OSSD
connections)
The external voltage supply must be capable of buffering brief mains
interruptions of 20 ms, as specified in IEC/EN 60204-1
Response Time (MSSI and SSI)
(solid-state output) 10 ms maximum
Safety Outputs: Model MMD-TA-12B
Two diverse-redundant solid-state safety outputs: 24 V dc, 0.5 A
sourcing OSSD (output signal switching device)
ON-State voltage: ≥ Vin-1.5 V dc
OFF-State voltage: 1.2 V dc maximum (0-1.2 V dc)
Maximum load capacitance: 1.0 µF
Maximum load inductance: 10 H
Leakage current: 0.50 mA maximum
Cable resistance: 10 ohms maximum
OSSD test pulse width: < 100 µs
OSSD test pulse period: > 100 ms
Switching current: 0-0.5 A
Non-Safety Outputs
Z4-Z3 = Aux. 24 V / 250 mA PNP output follows the two OSSD safety
outputs
14
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
3.1 Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.
86.0 mm
(3.38")
67.5 mm (2.65")
118.0 mm (4.65")
www.bannerengineering.com - Tel: + 1 888 373 6767
15
MMD-TA-11B/MMD-TA-12B Muting Module
4 System Installation
4.1 Appropriate Application
The correct application of the MMD-TA-11B and -12B Muting Modules is dependent on the type of machine and the
safeguards that are to be interfaced with the Module. The Module is generally interfaced with safeguards that may be used
only on machinery that is capable of stopping motion immediately upon receiving a stop signal and at any point in its
machine cycle. It is the user’s responsibility to verify whether the safeguarding is appropriate for the application and is
installed as instructed by the appropriate installation manuals.
Safety Light Screens, Single/Multiple Beam Safety Systems, or other Presence-Sensing Safeguarding Devices (PSSDs)
generally may not be used for the following:
• With single stroke (also called full revolution) clutched machinery, as this type of machinery is incapable of stopping
immediately.
• On certain other types of machinery, including any machine with inadequate or inconsistent stopping response time,
or any machine that ejects materials or component parts through the defined area.
• In any environment likely to adversely affect the efficiency of the safeguard(s) or the Muting Module. For example,
corrosive chemicals or fluids or unusually severe levels of smoke or dust, if not controlled, may degrade the
efficiency of a safety light screen.
If there is any doubt about whether or not your machinery is compatible with this Muting Module, contact Banner’s
Application Engineers at the factory.
WARNING:
• Not a stand-alone point-of-operation guarding device
• This Banner device is not a stand-alone point-of-operation guarding device, as defined by OSHA
regulations. Failure to install point-of-operation guards on hazardous machinery can result in a
dangerous condition that could lead to serious injury or death.
• Install point-of-operation guarding devices, such as safety light screens and/or hard guards, to
protect personnel from hazardous machinery.
Important...Read this Before Proceeding!
The Banner MMD-TA-11B or -12B Muting Module is an accessory device that is typically used in conjunction with a
machine safeguarding device. Its ability to perform this function depends upon the appropriateness of the application and
upon the Muting Module’s proper mechanical and electrical installation and interfacing to the machine to be guarded.
If all mounting, installation, interfacing, and checkout procedures are not followed properly, the Muting Module cannot
provide the protection for which it was designed.
WARNING:
• Follow all regulations.
• Failure to follow these instructions could result in serious bodily injury or death.
• The user is responsible to ensure that all local, state, and national laws, rules, codes, or
regulations relating to the installation and use of this control system in any particular application
are satisfied. Extreme care should be taken to ensure that all legal requirements have been met
and that all technical installation and maintenance instructions contained in this manual are
followed. Read this manual carefully before installing the system.
The user has the sole responsibility to ensure that this Muting Module is installed and interfaced to the guarded machine by
Qualified Persons, in accordance with this manual and applicable safety regulations.
Important: The user is responsible for safe application of this product.
The muting application examples described in Typical Muting Applications (p. 58) depict generalized
guarding situations. Every guarding application has a unique set of requirements.
Ensure that all legal requirements are met and that all installation instructions are followed. Direct any
questions regarding safeguarding should Banner Engineering.
16
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
4.2 Muting Application Design
Following are typical applications where muting is used. See Typical Muting Applications (p. 58) for more detailed
information.
• Entry/Exit Applications. The muting devices are placed to allow the entry or exit of a pallet or cart of work materials
to enter or exit a workstation without tripping the safety light screen, and without allowing the entrance of personnel
into the hazardous area.
• Home or Station Applications. The muting devices must be placed to mute the safety light screen only when a
hazard does not exist or is in another area — so that personnel are not exposed to any hazard.
• Robot Load/Unload Station Application. The Station muting application uses independent safety light screen
circuits, each with its own muting circuit and sensors to protect work locations. When a robot is active in Station A,
for example, Station B safety light screen is muted.
• Turret Table Application. A Turret Table application is similar to the Robot Load/Unload Station muting application,
except that any movement of the table ends the mute.
• Power Press Applications. The muting devices are placed so that the mute is initiated only during the nonhazardous, opening portion of the cycle (typically the machine upstroke).
WARNING:
• Muting is allowed only during the non-hazardous portion of the machine cycle
• Failure to follow these instructions could result in serious injury or death.
• Design the muting application so that no single component failure can prevent the stop
command or allow subsequent machine cycles until the failure is corrected (per ISO 13849-1 and
ANSI B11.19).
4.3 Use of Corner Mirrors with Optical Safety Systems
Mirrors are typically used with safety light screens and single-/multiple-beam safety systems to guard multiple sides of a
hazardous area. If the safety light screen is muted, the safeguarding function is suspended on all sides. It must not be
possible for an individual to enter the guarded area without being detected and a stop command issued to the machine
control. This supplemental safeguarding is normally provided by an additional device(s) that remains active while the
Primary Safeguard is muted and could be interfaced with the Safety (Protective) Stop Interface (SSI) input. Therefore,
mirrors are typically not allowed for muting applications.
4.4 Multiple Presence-Sensing Safety Devices (PSSDs)
Muting multiple PSSDs or a PSSD with multiple sensing fields is not recommended unless it is not possible for an individual
to enter the guarded area without being detected and a stop command issued to the machine control. If multiple sensing
fields are muted the possibility exists that personnel could move through a muted area or access point to enter the
safeguarded area without being detected.
For example, in an entry/exit application where a pallet initiates the mute cycle by entering a cell, if both the entry and the
exit PSSDs are muted, it may be possible for an individual to access the guarded area through the exit of the cell. An
appropriate solution would be to mute the entry and the exit with separate safeguarding devices.
WARNING:
• Do not safeguard multiple areas with mirrors or multiple sensing fields if personnel can enter the
hazardous area while the system is muted and not be detected
• Entering the hazardous area without being detected is dangerous and could result in serious
injury or death.
• Verify all areas are guarded and a stop command is issued to the guarded machine when
someone enters the hazardous area.
4.5 Pass-Through Hazards
A pass-through hazard is associated with applications where personnel may pass through a safeguard (at which point the
hazard stops or is removed), and then may continue into the hazardous area. Subsequently, their presence is no longer
detected, and the safeguard can not prevent the start or restart of the machine. The related danger is the unexpected start
or restart of the machine while personnel are within the hazardous area.
www.bannerengineering.com - Tel: + 1 888 373 6767
17
MMD-TA-11B/MMD-TA-12B Muting Module
In the use of safety light screens, a pass-through hazard typically results from large separation/safety distances calculated
from long stopping times, large defined area resolution, reach over, reach through, or other installation considerations. A
pass-through hazard can be generated with as little as 75 mm (3 in) between the defined area and the machine frame or
hard guarding.
4.5.1 Reducing or Eliminating Pass-Through Hazards
Measures must be taken to eliminate or reduce pass-through hazards. One solution is to ensure that personnel are
continually sensed while within the hazardous area. This can be accomplished by using supplemental safeguarding,
including: safety mats, area scanners, and horizontally mounted safety light screens. While it is recommended to eliminate
the pass-through hazard altogether, this may not be possible due to cell or machine layout, machine capabilities, or other
application considerations.
An alternate method is to ensure that once the safeguarding device is tripped it will latch, and require a deliberate manual
action to reset. This type of supplemental safeguarding relies upon the location of the reset switch as well as safe work
practices and procedures to prevent an unexpected start or restart of the guarded machine.
The reset switch or actuating control must be positioned outside the guarded area, and provide the switch operator with a
full unobstructed view of the entire guarded area and any associated hazards as the reset is performed. The reset switch or
actuating control must not be reachable from within the guarded area and must be protected (through the use of rings or
guards) against unauthorized or inadvertent operation. A key-actuated reset switch provides some operator control, as it
can be removed by the operator and taken into the guarded area. However, this does not prevent unauthorized or
inadvertent resets due to spare keys in the possession of others, or additional personnel entering the safeguarded area
unnoticed.
The reset of a safeguard must not initiate hazardous motion. Also, before each reset of the safeguard is performed, safe
work procedures require that a start-up procedure be followed and that the individual performing the reset verify that the
entire hazardous area is clear of all personnel. If any areas can not be observed from the reset switch location, additional
supplemental safeguarding must be used: at a minimum, visual and audible warnings of machine start-up.
WARNING:
• Pass-Through Hazards, Presence-Sensing Safeguarding Devices, and Muting
• If the presence-sensing safeguarding device (PSSD) is guarding an application in which
personnel have access into the sensing area or field (for example, a machine operator at the point
of operation) while the PSSD is muted, all pass-through hazards must be eliminated. The
individual must be sensed continually while in the safeguarded area; this will prevent initiation of
a machine cycle if the mute ends while the individual is within the hazardous area. If the passthrough hazard cannot be eliminated, as in entry/exit applications, the individual must be
detected entering the safeguarded area and the hazardous motion must stop immediately.
4.6 Installing the Module
The Muting Module mounts to a standard 35 mm DIN-rail track. The Module must be installed inside an enclosure rated
NEMA 3 (IEC IP 54) or better. It can be mounted in any orientation. It must be used with a properly installed and applied
safeguard (for example, safety light screen, interlocked barrier guard). The user must comply with all instructions contained
within product manuals and relevant regulations.
For reliable operation, the user must ensure that the operating specifications are not exceeded. The enclosure must provide
adequate heat dissipation, so that the air closely surrounding the Module does not exceed its maximum operating
temperature. Methods to reduce heat build-up include venting, forced air flow (for example, exhaust fans), adequate
enclosure exterior surface area, and spacing between Modules and other sources of heat.
Mount the Module in a convenient location that is free from heavy impulse force and high-amplitude vibration.
Electrostatic Discharge (ESD) can cause damage to electronic equipment. To prevent this, follow proper ESD handling
practices such as:
• Wear an approved wrist strap or other approved grounding products.
• Touch a grounded object before handling the Module.
See ANSI/ESD S20.20 for further information about managing ESD.
4.7 Muting Module Configuration
The Muting Module should be configured before initial checkout and use. Two banks of DIP switches are located under the
front cover. To access the DIP switches, use a screwdriver to gently pry the cover loose from the Module housing.
18
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
Because the Module has redundant microprocessors, two DIP switch banks (Bank A and Bank B) must be set identically.
Failure to set Bank A and Bank B identically will result in a lockout condition. Power must be OFF when changing DIP
switch settings; changing settings while power is ON will cause a lockout condition. The parameters to be manually
configured are shown in Figure 4 (p. 19).
Figure 3. Use a screwdriver to gently pry the cover loose from the Module housing
Switch
Bank A
Switch
Bank B
Switch
1
Auto/Manual MSSI Reset
SSI auto reset
SSI manual reset*
3
Two-way muting
(one sensor pair)
One-way muting*
4
One-Channel or TwoChannel EDM
One-channel
EDM
Two-channel or
no EDM*
5 ON, 6 ON
5 ON, 6 OFF
No backdoor
time-out (infinite)
30-minute
backdoor timeout
5 OFF, 6 ON
5 OFF, 6 OFF
60-second
backdoor timeout
30-second
backdoor timeout*
Backdoor Time-Out
7
Monitored/Non-Monitored
Mute Lamp
Mute lamp not
monitored
Mute lamp
monitored*
8
Mute on Power-Up
Mute on powerup
No mute on
power up*
OFF
5 6 7
MSSI manual
reset*
Auto/Manual SSI Reset
5–6
3 4
MSSI auto reset
One-Way or Two-Way Mute
Initiate Sequence
ON
2
OFF Position
2
Factory Default Settings
1
ON Position
8
*Factory default setting.
Note: Switch numbers, for example SW
1, refer to both switch banks A and B.
Figure 4. Muting Module manual configuration parameters
4.8 Connection Terminals and Functions
All electrical connections are made through removable terminals.
Jumper terminal X5 (SSIb) to terminal X6 (SSIa), and jumper terminal X7 (SSId) to terminal X8 (SSIc) (factory default) to
disable the Safety Stop Interface (SSI). Do not short Channel A to Channel B.
www.bannerengineering.com - Tel: + 1 888 373 6767
19
MMD-TA-11B/MMD-TA-12B Muting Module
WARNING:
• Risk of electric shock
• Use extreme caution to avoid electrical shock. Serious injury or death could result.
• Always disconnect power from the safety system (for example, device, module, interfacing, etc.),
guarded machine, and/or the machine being controlled before making any connections or
replacing any component. Lockout/tagout procedures might be required. Refer to OSHA
29CFR1910.147, ANSI Z244-1, or the applicable standard for controlling hazardous energy.
• Make no more connections to the device or system than are described in this manual. Electrical
installation and wiring must be made by a Qualified Person2 and must comply with the applicable
electrical standards and wiring codes, such as the NEC (National Electrical Code), ANSI NFPA79,
or IEC 60204-1, and all applicable local standards and codes.
Z21 M1 Z11
Z13 M3 Z23
S11 S12 S21 S22
Y1
Y2 Y3
A1
X1 X2
Y4
Z12 M2 Z22
X5
X6
X7
X8
X9 X10 X11 X12
X3
X4
31
32
13
Z14 M4 Z24
14
23
X13 X14 A2
24
Potential
High-Voltage
Terminals
All terminals are low-voltage except for those indicated otherwise.
Terminal
Function
Terminal
Function
Terminal
Function
Z13
M3, 0V
Z21
M1, 24V
Z12
M2, 0V
M3
Muting 3 In (PNP)
M1
Muting 1 In (PNP)
M2
Muting 2 In (NPN)
Z23
M3, 24V
Z11
M1, 0V
Z22
M2, 24V
S11
MSSI b (ch A)
X5
SSI b (ch A)
X9
Override a (ch A)3
S12
MSSI a (ch A)
X6
SSI a (ch A)
X10
Override b (ch A)3
S21
MSSI d (ch B)
X7
SSI d (ch B)
X11
Override c (ch B)3
S22
MSSI c (ch B)
X8
SSI c (ch B)
X12
Override d (ch B)3
Y1
EDM 1 a Out (24V)
X3
Mute Lamp Out (24V)
13
OSSD 1 a (Relay)
Y2
EDM 1 b In
X4
Mute Lamp In
14
OSSD 1 b (Relay)
Y3
EDM 2 b In
31
AUX a (Relay)
23
OSSD 2 a (Relay)
Y4
EDM 2 a Out (24V)
32
AUX b (Relay)
24
OSSD 2 b (Relay)
A1
+24V dc
Z14
M4, 0V
X13
Mute Enable Out (24V)
X1
Reset In
M4
Muting 4 In (NPN)
X14
Mute Enable In
X2
Reset Out (24V)
Z24
M4, 24V
A2
0V dc
Figure 5. MMD-TA-11B terminal connection locations
2
A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and
experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
3 Contacts only.
20
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
Z13 M3 Z23
S11 S12 S21 S22
Y1
A1
Y2
Y3
X1 X2
Y4
Z21 M1 Z11
Z12 M2 Z22
X5
X6
X7
X8
X9 X10 X11 X12
X3
X4
Z3
Z4
Y5
Z14 M4 Z24
Y6
Y7
Y8
X13 X14 A2
All terminals are low-voltage.
Terminal
Function
Terminal
Function
Terminal
Function
Z13
M3, 0V
Z21
M1, 24V
Z12
M2, 0V
M3
Muting 3 In (PNP)
M1
Muting 1 In (PNP)
M2
Muting 2 In (NPN)
Z23
M3, 24V
Z11
M1, 0V
Z22
M2, 24V
S11
MSSI b (ch A)
X5
SSI b (ch A)
X9
Override a (ch A)4
S12
MSSI a (ch A)
X6
SSI a (ch A)
X10
Override b (ch A)4
S21
MSSI d (ch B)
X7
SSI d (ch B)
X11
Override c (ch B)4
S22
MSSI c (ch B)
X8
SSI c (ch B)
X12
Override d (ch B)4
Y1
EDM 1 a Out (24V)
X3
Mute Lamp Out (24V)
Y5
OSSD 1 a Out
Y2
EDM 1 b In
X4
Mute Lamp In
Y6
OSSD 1 b 0V
Y3
EDM 2 b In
Z3
AUX b 0V
Y7
OSSD 2 b 0V
Y4
EDM 2 a Out (24V)
Z4
AUX a Out
Y8
OSSD 2 a Out
A1
+24V dc
Z14
M4, 0V
X13
Mute Enable Out (24V)
X1
Reset In
M4
Muting 4 In (NPN)
X14
Mute Enable In
X2
Reset Out (24V)
Z24
M4, 24V
A2
0V dc
Figure 6. MMD-TA-12B terminal connection locations
4.8.1 Remove a Terminal Block
1. Insert a small screwdriver into the slot shown.
Figure 7. Removal of Terminal Blocks
4 Contacts only.
www.bannerengineering.com - Tel: + 1 888 373 6767
21
MMD-TA-11B/MMD-TA-12B Muting Module
2. Pry to loosen.
3. When reinserting a terminal block, take care to slide the dovetail on the terminal block into the slot on the frame.
4.9 Installing Input Devices
4.9.1 Manual Reset Switch
The manual reset switch connects to Module terminals X1 and X2. See Muting Module Configuration (p. 18) for Auto/Manual
Reset configuration.
X1
X2
Figure 8. Manual Reset switch connections
Note: If a solid state switch is used, connect the PNP output of the switch to X1. The switch must be
powered from the same supply as the MMD.
Any reset switches must be located so that a reset is possible only from outside, and in full view of, the hazardous area. The
switch must also be out of reach from within the safeguarded space. If any hazardous areas are out of view from the switch
location, additional means of safeguarding must be provided.
The switch must be protected from accidental or unintended actuation (for example, through the use of rings or guards).
Using a key switch provides some level of personal control, because the key may be removed. This will hinder a reset while
the key is under the control of an individual, but must not be relied upon solely to guard against accidental or unauthorized
reset. Spare keys in the possession of others, or additional personnel entering the safeguarded area unnoticed may create a
hazardous situation.
WARNING:
• Install reset switches properly
• Failure to properly install reset switches could result in serious injury or death.
• Install reset switches so that they are accessible only from outside, and in full view of, the
safeguarded space. Reset switches cannot be accessible from within the safeguarded space.
Protect reset switches against unauthorized or inadvertent operation (for example, through the
use of rings or guards). If there are any hazardous areas that are not visible from the reset
switches, provide additional safeguarding.
Reset Routine
The Muting Module requires a manual reset to clear a latch condition and resume operation following a stop command. To
perform a manual reset, close the normally open reset switch and hold it there for at least 1/4 second, but not longer than 2
seconds, and then re-open the switch. Internal lockout conditions also require a manual reset to return the system to RUN
mode after the failure has been corrected and the input correctly cycled.
4.9.2 Muting Devices
The user is required by OSHA and ANSI to arrange, install, and operate the safety system so as to protect personnel and
minimize the possibility of defeating the safeguard. Mute devices must meet a 3-second simultaneity requirement to
activate muting; that is, devices in a pair must be activated within 3 seconds of one another.
General Muting Device Requirements
The muting devices (typically sensors or switches) must, at a minimum, comply with the following requirements:
1. There must be a minimum of two independent hard-wired muting devices.
2. The muting devices must either both have normally open contacts or PNP outputs both of which must fulfill the
input requirements listed in the Specifications. These contacts must close when the switch is actuated, and must
open (or not conduct) when the switch is not actuated or in a power OFF condition.
22
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
3. The activation of the inputs to the muting function must be from separate sources. These sources must be mounted
separately in order to prevent an unsafe muting condition resulting from misadjustment, misalignment, or a single
common mode failure. (For example, physical damage to the mounting surface could cause both muting devices to
be knocked out of alignment, resulting in false muting input signals.) Only one of these sources may pass through,
or be affected by, a programmable logic controller or similar device.
4. The muting devices must be installed so that they can not be easily defeated or bypassed.
5. The muting devices must be mounted so that their physical position and alignment can not be easily changed.
6. It must not be possible for environmental conditions to initiate a mute condition (for example, extreme airborne
contamination).
7. The muting devices must not be set to use any delay or other timing functions (unless such functions are
accomplished so that no single component failure prevents the removal of the hazard, subsequent machine cycles
are prevented until the failure is corrected, and no hazard is created by extending the muted period).
Examples of Muting Sensors and Switches
Photoelectric Sensors (Opposed Mode)
Opposed-mode sensors, which initiate the muted condition when the beam path is blocked, should be configured
for dark operate (DO) and have open (non-conducting) output contacts in a power OFF condition. Both the emitter
and receiver from each pair should be powered from the same source, to eliminate common mode failures.
Photoelectric Sensors (Polarized Retroreflective Mode)
The user must ensure that false proxing (activation due to shiny or reflective surfaces) is not possible. Banner LP
sensors with linear polarization can greatly reduce or eliminate this effect.
Use a sensor configured for Light Operate (LO or N.O.) if initiating a mute when the retroreflective target or tape is
detected (for example, home position). Use a sensor configured for Dark Operate (DO or N.C.) when a blocked
beam path initiates the muted condition (for example, entry/exit). Both situations must have open (non-conducting)
output contacts in a power OFF condition.
Positive-Opening Safety Switches
Two (or four) independent switches, each with a minimum of one closed safety contact to initiate the mute cycle,
are typically used. An application using a single switch with a single actuator and two closed contacts could result
in an unsafe situation.
Inductive Proximity Sensors
Typically, inductive proximity sensors are used to initiate a muted cycle when a metal surface is detected. Due to
excessive leakage current causing false ON conditions, two-wire sensors are not to be used. Only three- or fourwire sensors that have discrete PNP, NPN, or hard-contact outputs that are separate from the input power can be
used.
WARNING:
• Avoid hazardous installations
• Improper adjustment or positioning could result in serious injury or death.
• Properly adjust or position the two or four independent position switches so that they close only
after the hazard no longer exists and open again when the cycle is complete or the hazard is
again present.
• The user is responsible for satisfying all local, state, and national laws, rules, codes, and
regulations relating to the use of safety equipment in any particular application. Ensure that all
appropriate agency requirements have been met and that all installation and maintenance
instructions contained in the appropriate manuals are followed.
Muting Device Wiring
The Module provides supply voltage, if required, and input connections for the muting devices. One or two pairs of muting
devices (typically sensors or switches) must be used; these pairs are designated M1-M2 and M3-M4. The M1 and M3
inputs are PNP (sourcing). The M2 and M4 inputs are NPN (sinking). Also available are terminals to supply power (+24 V dc)
to the muting devices.
The current draw of all devices must not exceed 500 mA.
www.bannerengineering.com - Tel: + 1 888 373 6767
23
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
MMD-TA-..B
A1
Z21 +
M1 PNP
Z11
M1
-
Z23 +
M3 PNP
M1
R
M3
Z13 -
M3
Carrier
Basket
E
Light
Screen
M2
Z24 +
M4
M4 NPN
M4
Z14 -
Z22 +
M2 NPN
M2
Z12 -
Figure 9. Four Limit Switches as M1, M2, M3, and M4
+24V dc
MMD-TA-..B
A1
Z21 +
+
+
-
-
+
+
-
-
M1 PNP
Z23 +
M1
or
M3 PNP
Z11 -
Z13 -
Z22 +
Z24
M2 NPN
M4 NPN
Z12 -
M2
or
Z14
M3
+
M4
-
Figure 10. Relay (hard contact) output sensors
24
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
Polarized
Retro
MMD-TA-..B
A1
+
PNP
Z21 +
M1 PNP
Z23 +
M1
or
M3 PNP
-
Z11
-
Z13 -
+
Z22 +
Z24 +
NPN
-
M2 NPN
M2
Z12 -
or
M4 NPN
Z14
M3
M4
-
Figure 11. Two (or four) sensors using semiconductor outputs
4.10 Mute Lamp Output (ML)
The Mute Lamp output provides for the visible indication that the safety device’s safeguarding function is muted. This
indication must be readily observable. Failure of this indication should be detectable and prevent the safeguard from being
muted, or the operation of the indicator should be verified at suitable intervals. The Mute Lamp output also flashes to
indicate an Override condition.
The Module can be configured for a monitored or non-monitored mute lamp. It is the user’s responsibility to make sure that
each application meets local regulations. If the installation is governed by UL regulations, the mute lamp must be monitored
(SW7 = OFF, banks A and B). This output may also be used as an input to control logic (for example, a PLC) if nonmonitored is selected (SW7 = ON, banks A and B). The current draw of the mute lamp must not exceed 360 mA. See the
following figure.
+
Mute
Lamp
X3
X4
Figure 12. Mute Lamp output wiring
4.11 Auxiliary Output (AUX)
Model MMD-TA-11B
Model MMD-TA-12B
The non-safety-related output on this model is a 24V ac/dc,
250 mA normally-closed relay contact. See output
specifications.
A non-safety-related PNP output is available at terminals
Z3–Z4. This monitoring output is for light-duty, non-safetyrelated control functions, such as an input to a
programmable logic controller (PLC). This output follows the
OSSD outputs. Maximum current draw of the AUX output is
250 mA.
31
K1
Load
V+
K2
32
0V
+V
Z4
0V
Figure 13. AUX output wiring — MMD-TA-11B
+
Load -
Z3
Figure 14. AUX output wiring — MMD-TA-12B
www.bannerengineering.com - Tel: + 1 888 373 6767
25
MMD-TA-11B/MMD-TA-12B Muting Module
4.12 Override Switch Wiring
The Module provides connection terminals for the Override switches. See the following figure and Override (p. 11).
X9
Override A
X10
X11
Override B
X12
Figure 15. Override switch wiring
WARNING:
• Limit the use of the bypass and/or override function
• Failure to follow these instructions could result in serious injury or death.
• The bypass and/or override function is not intended for production purposes; use it only for
temporary or intermittent actions, such as to clear the defined area of a safety light screen if
material becomes stuck. When bypass and/or override is used, the user must install and use it
according to applicable standards (such as ANSI NFPA79 or IEC/EN60204-1).
4.13 SSI and MSSI Interfacing
The Safety Stop Interface (SSI) provides easy integration of safeguards. This interface consists of two input channels (A and
B), which are compatible with Banner Engineering safety devices that have solid-state Output Signal Switching Device
(OSSD) outputs or other devices with sourcing +24 V dc outputs. SSI is also compatible with devices that have normally
open hard contacts or relay outputs (voltage-free).
The Muteable Safety Stop Interface (MSSI) input is a specialized SSI that can be muted during the non-hazardous portion of
the machine cycle.
The input channels (A and B) must meet a simultaneity requirement of 3.0 seconds upon closing and opening. A mismatch
of more than 3.0 seconds will result in a lockout. A lockout that is due to a failure to meet simultaneity requirements can
only be cleared by:
1. Cycling the MSSI (or the SSI, depending on which failed) with simultaneity being met.
2. If the Module is configured for Manual Reset, performing a reset routine.
The MSSI and the SSI can be interfaced with devices with solid-state OSSD outputs, safety interlocking switches, E-stop
buttons, rope/cable pull devices, and other machine control devices that switch +24Vdc. To be interfaced with a safety mat,
a safety mat controller must be connected between the mat and the interface (see Figure 29 (p. 37)).
Note: If the SSI is not to be used, the input channels must be jumpered. See Connection Terminals and
Functions (p. 19).
WARNING:
• Emergency Stop Functions
• Muting or bypassing the safety outputs will render the Emergency Stop function ineffective.
• Do not connect any Emergency Stop devices to the MSSI Input; do not mute or bypass any
Emergency Stop device. ANSI NFPA79 and IEC/EN 60204-1 require that the Emergency Stop
function remain active at all times.
26
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
4.14 Safety Circuit Integrity and ISO 13849-1
4.14.1 Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles
Safety circuits involve the safety-related functions of a machine that minimize the level of risk of harm. These safety-related
functions can prevent initiation, or they can stop or remove a hazard. The failure of a safety-related function or its
associated safety circuit usually results in an increased risk of harm.
The integrity of a safety circuit depends on several factors, including fault tolerance, risk reduction, reliable and well-tried
components, well-tried safety principles, and other design considerations.
Depending on the level of risk associated with the machine or its operation, an appropriate level of safety circuit integrity
(performance) must be incorporated into its design. Standards that detail safety performance levels include ANSI B11.19
Performance Criteria for Safeguarding and ISO 13849-1 Safety-Related Parts of a Control System.
4.14.2 Safety Circuit Integrity Levels
Safety circuits in International and European standards have been segmented into categories, depending on their ability to
maintain their integrity in the event of a failure. The most recognized standard that details safety circuit integrity levels is EN
ISO 13849-1, which establishes five levels: Categories B, 1, 2, 3, and the most stringent, Category 4.
In the United States, the typical level of safety circuit integrity has been called control reliability. Control reliability typically
incorporates redundant control and self-checking circuitry and has been loosely equated to EN ISO 13849-1 Categories 3
and 4 (see CSA Z432 and ANSI B11.TR4).
If the requirements described by EN ISO 13849-1 are to be implemented, a risk assessment must first be performed to
determine the appropriate category, in order to ensure that the expected risk reduction is achieved. This risk assessment
must also take into account national regulations, such as U.S. control reliability or European “C” level standards, to ensure
that the minimum level of performance that has been mandated is complied with.
4.14.3 Fault Exclusion
An important concept within the category requirements of ISO 13849-1 is the “probability of the occurrence of the failure,”
which can be decreased using a technique termed fault exclusion. The rationale assumes that the possibility of certain welldefined failure(s) can be reduced to a point where the resulting fault(s) can be, for the most part, disregarded—that is,
excluded.
Fault exclusion is a tool a designer can use during the development of the safety-related part of the control system and the
risk assessment process. Fault exclusion allows the designer to design out the possibility of various failures and justify it
through the risk assessment process to meet the intent requirements of Category 2, 3 or 4. See ISO 13849-1/-2 for further
information.
Important: Safety (Protective) Stop Interface (SSI) and Muteable Safety Stop Interface (MSSI) Safety
Categories—The level of safety circuit integrity is affected by the design and installation of the safety
devices and the means of interfacing of those devices. Perform a risk assessment to determine the
appropriate safety circuit integrity level or safety category as described by ISO 13849-1, to ensure that
the expected risk reduction is achieved, and that all relevant regulations are complied with.
4.15 Generic SSI and MSSI Wiring
To fully understand category requirements, refer to standard ISO 13849-1. The following is general in nature and is intended
to provide only basic guidance. Each guarding application has its unique set of requirements; it is the user’s responsibility
to ensure that all local, state, and national laws, rules, codes, and regulations are satisfied.
In addition to the use of well-tried, tested, and robust components, and generally accepted principles (including fault
exclusion), the safety function depends on the use of safety-rated devices. These devices are specially designed to reduce
the probability of failing to an unsafe condition, and typically are third-party certified to a recognized safety standard.
www.bannerengineering.com - Tel: + 1 888 373 6767
27
MMD-TA-11B/MMD-TA-12B Muting Module
4.15.1 Category 2
To meet the requirements of a category 2 application, any device connected to the Safety (Protective) Stop Interface (SSI)
and Muteable Safety Stop Interface (MSSI) inputs must meet certain criteria. For example, a type 2 light screen (curtain) that
meets IEC 61496-1/-2 is a device that meets category 2 requirements.
A category 2 safety function must be tested/checked at suitable intervals, the frequency determined by the application’s
risk assessment. It should be noted that a single fault may cause the loss of the safety function.
The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an
acceptable (minimal) level of risk, the possibility of undetected faults or failures that can result in the loss of the safety
function.
+24V dc
0V
MMD-TA-..B
A1
A2
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 16. MSSI and SSI Category 2 interfacing: positive opening switch
0V
+24V dc
MMD-TA-..B
A1
+V
+
0V*
+
EZ-SCREEN
Type 2
A2
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 17. MSSI and SSI Category 2 interfacing: Category 2 safeguarding device (for example, EZ-SCREEN Type 2 or AOPD type 2 per IEC 61496-1/-2)
4.15.2 Category 3
To meet the requirements of a category 3 application, any device connected to the Safety (Protective) Stop Interface (SSI)
and Muteable Safety Stop Interface (MSSI) inputs must meet certain criteria. For example, a type 3 laser area scanner that
meets IEC 61496-1/-3 is a device that meets category 3 requirements.
In a category 3 safety application, a single fault must not cause the loss of the safety function. This is usually accomplished
by using redundant safety inputs or outputs from the safety-rated device. Faults should be detected whenever reasonably
practicable, although a short circuit between input channels or safety outputs may not be detected. It should be noted that
an accumulation of faults may cause the loss of the safety function.
The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an
acceptable (minimal) level of risk, the possibility of undetected faults or catastrophic failures that could result in the loss
ofthe safety function.
28
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
0V
MMD-TA-..B
A2
A1
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 18. MSSI and SSI Category 3 interfacing: two positive-opening switches per single guard
+24V dc
0V
MMD-TA-..B
A1
MSSI or SSI
+
+
Safeguard with
Output Fault
Monitoring
A2
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 19. MSSI and SSI Category 3 interfacing: Category 3 safeguarding device with output fault monitoring (for example, type 3 area scanner AOPDDR
per IEC 61496-1/-3)
www.bannerengineering.com - Tel: + 1 888 373 6767
29
MMD-TA-11B/MMD-TA-12B Muting Module
4.15.3 Category 4
To ensure a category 4 application, any device connected to
the Safety (Protective) Stop Interface (SSI) and Muteable
Safety Stop Interface (MSSI) inputs must meet certain
criteria. For example, a type 4 safety light screen (curtain)
that meets IEC 61496-1/-2 is a device that meets category 4
requirements.
+24V dc
0V
MMD-TA-..B
A2
A1
MSSI or SSI
In a category 4 application, a single fault must not cause the
loss of the safety function. The fault must be detected at or
before the next demand of the safety function, and an
accumulation of faults also must not cause the loss of the
safety function.
This is usually accomplished by the use of redundant safety
inputs or outputs from the safety-rated device that are
monitored to detect certain faults. These faults include:
• Increased response time
• Prevention of one or more safety outputs (OSSDs)
going to the OFF-state
• A short circuit between channels
Note: Solid-state safety outputs, such
as those from EZ-SCREEN Type 4
safety light screens, typically achieve
this level of fault tolerance by selfmonitoring a pulsing of the outputs.
Safety devices with hard-contact or
relay outputs must be connected in a 4wire method as shown in Figure 22 (p.
30).
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 20. MSSI and SSI Category 4 interfacing: two positive-opening
switches per single guard
0V
+24V dc
MMD-TA-..B
A1
MSSI or SSI
+
+
The principle of fault exclusion must be incorporated into
the design and installation to either eliminate, or reduce to
an acceptable (minimal) level of risk, the possibility of
catastrophic failures/faults that could result in the loss of the
safety function.
A2
EZ-SCREEN
Type 4
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 21. MSSI and SSI Category 4 interfacing: category 4 safeguarding
device with output fault monitoring (for example, EZ-SCREEN or AOPD
Type 4 per IEC 61496- 1/-2)
+24V dc
0V
MMD-TA-..B
A2
A1
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
AOPD
Type 4
Figure 22. MSSI and SSI Category 4 interfacing: category 4 safeguarding
device with relay outputs (for example, MINI-SCREEN or AOPD Type 4 per
IEC 61496-1/-2)
30
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
4.16 SSI Emergency Stop Switch Device Wiring
4.16.1 Emergency Stop Push Button Switches
As shown in Figure 23 (p. 32), Figure 24 (p. 32), Figure 25 (p. 33), the E-stop switch must provide one or two contacts
for safety which are closed when the switch is armed. Once activated, the E-stop switch must open all its safety-rated
contacts, and must require a deliberate action (such as twisting, pulling, or unlocking) to return to the closed-contact,
armed position. The switch should be a positive opening (or direct-opening) type, as described by IEC 60947-5-1. A
mechanical force applied to such a button (or switch) is transmitted directly to the contacts, forcing them open. This
ensures that the switch contacts will open whenever the switch is activated.
Standards ANSI NFPA 79, IEC/EN 60204-1, and ISO 13850 specify additional emergency stop switch device requirements,
including the following:
• Emergency Stop push buttons shall be located at each operator control station and at other operating stations
where emergency shutdown is required
• Stop and Emergency Stop push buttons shall be continuously operable and readily accessible from all control and
operating stations where located. Do not connect E-stop buttons to the Muteable Safety Stop Interface (MSSI)
• Actuators of Emergency Stop devices shall be colored red. The background immediately around the device actuator
shall be colored yellow. The actuator of a push-button-operated device shall be of the palm or mushroom-head type
• The Emergency Stop actuator shall be a self-latching type
Note: Some applications may have additional requirements. The user must comply with all relevant
regulations.
WARNING: Emergency Stop Functions
Do not connect any Emergency Stop devices to the MSSI Input; do not mute or bypass any Emergency
Stop device. ANSI NFPA79 and IEC/EN 60204-1 require that the Emergency Stop function remain active
at all times. Muting or bypassing the safety outputs will render the Emergency Stop function ineffective.
WARNING:
• Reset routine required
• Failure to prevent the machine from restarting without actuating the normal start command/
device can create an unsafe condition that could result in serious injury or death.
• Do not allow the machine to restart without actuating the normal start command/device. Perform
the reset routine after clearing the cause of a stop condition, as required by U.S. and international
standards.
4.16.2 Safety Circuit Integrity Levels and Emergency Stop Functions
As part of the required risk assessment for the machine, ANSI NFPA 79 and IEC/EN 60204-1 state that the safety
performance (integrity) must reduce the risk from identified hazards as determined by the risk assessment. See Safety
Circuit Integrity and ISO 13849-1 (p. 27) and Generic SSI and MSSI Wiring (p. 27) for guidance if the requirements as
described by ISO 13849-1 (EN954-1) are to be implemented.
In addition to the requirements stated above, the design and the installation of the emergency stop device (for example,
switch, button, or rope-pull) must be such that the possibility of a catastrophic failure of the device resulting in the loss of
the safety function must be excluded (designed out). Per ISO 13849-2, electromechanical devices that have contacts
designed in accordance to IEC 60947-5-1 Annex K and that are installed per manufacturer’s instructions are expected to
open when the emergency stop device is actuated.
4.16.3 Category 2
A single-channel emergency stop application typically provides a category 2 level of circuit performance, because a short
circuit could cause the loss of the safety function. The principle of fault exclusion must be incorporated into the design and
installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of undetected faults or
failures that can result in the loss of the safety function.
www.bannerengineering.com - Tel: + 1 888 373 6767
31
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
0V dc
A1
MMD-TA-..B
A2
SSI
X6 (a)
X5 (b)
X8 (c)
X7 (d)
Figure 23. SSI Category 2 interfacing: positive-opening E-stop switch(es)
4.16.4 Category 3
A dual-channel wiring switching +24 V dc is typically a category 3 application, because a single failure does not result in a
loss of safety. Loss of the switching action in one channel is detected by the actuation of the E-stop button, the opening of
the second channel, and the monitoring function of the Safety (Protective) Stop Interface (SSI) inputs. However, a short
circuit between input channels or safety outputs may not be detected. It should be noted that an accumulation of faults may
cause the loss of the safety function.
The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an
acceptable (minimal) level of risk, the possibility of undetected faults or catastrophic failures that could result in the loss of
the safety function.
+24V dc
0V dc
A1
MMD-TA-..B
A2
SSI
X6 (a)
X5 (b)
X8 (c)
X7 (d)
Figure 24. SSI Category 3 interfacing: positive-opening E-stop switch(es)
4.16.5 Category 4
The self-monitoring Safety (Protective) Stop Interface (SSI) inputs can be interfaced to achieve a category 4 application. The
principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an
acceptable (minimal) level of risk, the possibility of catastrophic failures or faults that could result in the loss of the safety
function.
32
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
0V dc
A1
MMD-TA-..B
A2
SSI
X6 (a)
X5 (b)
X8 (c)
X7 (d)
Figure 25. SSI Category 4 interfacing: positive-opening E-stop switch(es)
Note:
• Connect Multiple E-Stop Switches in Series
• Connecting the contacts of multiple e-stop switches in parallel to the e-stop safety module inputs
defeats the switch contact monitoring ability of the safety module and creates an unsafe condition
that could result in serious injury or death.
• When two or more e-stop switches are connected to the same e-stop safety module, connect the
contacts of both switches together in series. Wire this series combination to the respective safety
module input. Never connect the contacts of multiple e-stop switches in parallel to the e-stop
safety module inputs.
4.17 SSI/MSSI Interlocked Guard or Gate Wiring
The SSI (or MSSI) may be used to monitor electrically interlocked safety guards or gates.
4.17.1 Safety Circuit Integrity Levels
The application requirements for Muting Module vary for the level of control reliability or safety category per ISO 13849-1.
While Banner Engineering always recommends the highest level of safety in any application, the user is responsible to safely
install, operate, and maintain each safety system and comply with all relevant laws and regulations.
The safety performance (integrity) must reduce the risk from identified hazards as determined by the machine’s risk
assessment. See Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles (p. 27) for guidance if the requirements
as described by ISO 13849-1 need to be implemented.
In addition to the requirements stated in this section, the design and installation of the interlocking device should comply
with ANSI B11.19 or ISO 14119.
4.17.2 Safety Interlock Switch Requirements
The following general requirements and considerations apply to the installation of interlocked guards and gates for the
purpose of safeguarding. In addition, the user must refer to the relevant regulations to ensure compliance with all necessary
requirements.
Hazards guarded by the interlocked guard must be prevented from operating until the guard is closed; a stop command
must be issued to the guarded machine if the guard opens while the hazard is present. Closing the guard must not, by itself,
initiate hazardous motion; a separate procedure must be required to initiate the motion. The safety interlock switches must
not be used as a mechanical or end-of-travel stop.
The guard must be located an adequate distance from the danger zone (so that the hazard has time to stop before the
guard is opened sufficiently to provide access to the hazard), and it must open either laterally or away from the hazard, not
into the safeguarded area. The guard also should not be able to close by itself and activate the interlocking circuitry. In
addition, the installation must prevent personnel from reaching over, under, around, or through the guard to the hazard. Any
openings in the guard must not allow access to the hazard (see OSHA 29CFR1910.217 Table O-10, ANSI B11.19, ISO
13857, ISO14120/EN953 or the appropriate standard). The guard must be strong enough to contain hazards within the
guarded area, which may be ejected, dropped, or emitted by the machine.
www.bannerengineering.com - Tel: + 1 888 373 6767
33
MMD-TA-11B/MMD-TA-12B Muting Module
The safety interlock switches, actuators, sensors, and magnets must be designed and installed so that they cannot be
easily defeated. They must be mounted securely so that their physical position cannot shift, using reliable fasteners that
require a tool to remove them. Mounting slots in the housings are for initial adjustment only; final mounting holes must be
used for permanent location.
WARNING: Perimeter Guarding Applications
If the application could result in a pass-through hazard (for example, perimeter guarding), either the
safeguarding device or the guarded machine's MSCs/MPCEs must cause a Latched response following
a Stop command (for example, interruption of the sensing field of a light curtain, or opening of an
interlocked gate/guard). The reset of this Latched condition may only be achieved by actuating a reset
switch that is separate from the normal means of machine cycle initiation. The switch must be positioned
as described in this document.
Lockout/Tagout procedures per ANSI Z244.1 may be required, or additional safeguarding, as described
by ANSI B11 safety requirements or other appropriate standards, must be used if a passthrough hazard
cannot be eliminated or reduced to an acceptable level of risk. Failure to follow these instructions could
result in serious injury or death.
4.17.3 Positive-Opening Safety Interlocking Switches
Safety interlock switches must satisfy several requirements. Each switch must provide electrically isolated contacts: at
minimum, one normally closed (N.C.) contact from each individually mounted switch. The contacts must have positiveopening (direct-opening) design, as described by IEC 60947-5-1, with one or more normally closed contacts rated for
safety. Positive-opening operation causes the switch to be forced open, without the use of springs, when the switch
actuator is disengaged or moved from its home position (visit www.bannerengineering.com for examples).
In addition, the switches must be mounted in a positive mode to move/disengage the actuator from its home position and
open the normally closed contact when the guard opens.
4.17.4 Monitoring Series-Connected Safety Interlock Switches
When monitoring two individually mounted safety switches (as shown in the Category 4 circuit figure), a faulty switch will be
detected if it fails to switch as the guard opens. In this case, the Module will deenergize its safety outputs (OSSDs) and
disable its reset function until the input requirements are met, such as the replacement of the faulty switch. However, when
a series of safety interlocking switches is monitored by a single Module, the failure of one switch in the system may be
masked or not be detected at all (see the Category 2 and Category 3 circuit figures).
Series-connected safety interlock switch circuits may not meet OSHA Control Reliability or ISO 13849 Safety Category 4
requirements because of the potential of an inappropriate reset or a potential loss of the safety stop signal. Those
requirements are not met due to the typical inability to fault exclude the failure of the safety interlock switch. A multiple
connection of this type should not be used in applications where loss of the safety stop signal or an inappropriate reset can
lead to serious injury or death. The following scenarios assume two positive-opening safety switches on each guard, both
connected in series to switches of a second guard:
1. Masking of a failure. If a guard is opened but the switch fails to open, the redundant safety switch will open and
cause the Muting Module to de-energize its outputs. If the faulty guard is then closed, both Muting Module input
channels also close, but because one channel did not open, the Muting Module will not reset. However, if the faulty
switch is not replaced and a second functional guard is cycled (opening and then closing both of the Muting Module
input channels), the Muting Module considers the failure to be corrected. With the input requirements apparently
satisfied, the Muting Module allows a reset. This system is no longer redundant and, if the second switch fails, may
result in an unsafe condition, such as the accumulation of faults resulting in loss of the safety function.
2. Non-detection of a failure. If a functional guard is opened, the Muting Module de-energizes its outputs (a normal
response). But if then a faulty guard is opened and closed before the functional guard is re-closed, the faulty guard
is not detected. This system is no longer redundant and may result in a loss of safety if the second safety switch
fails to switch when needed.
The systems in either scenario do not inherently comply with the safety standard requirements of detecting single faults and
preventing the next cycle. It is important to periodically check the functional integrity of each interlocked guard individually
in multiple-guard systems using series-connected safety interlock switches. Operators, maintenance personnel, and others
associated with the operation of the machine must be trained to recognize such failures and be instructed to correct them
immediately.
To verify series-connected safety interlock switch functionality:
Open and close each safeguard separately while verifying that the Muting Module outputs operate correctly throughout
the check procedure. Follow each safeguard closure with a manual reset, if needed. If a contact set fails, the Muting
Module will not enable its reset function. If the Muting Module does not reset, a switch may have failed; that switch must
be immediately replaced.
34
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
This check must be performed and all faults must be cleared, at a minimum, during periodic checkouts. Do not use the
series connection of the safety interlock switches if the application cannot exclude these types of failures and such a
failure could result in serious injury or death.
4.17.5 Category 2
A single-channel interlocked guard application typically provides a category 2 level of circuit performance, because a short
circuit could cause the loss of the safety function. The principle of fault exclusion must be incorporated into the design and
installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of undetected faults or
failures that can result in the loss of the safety function.
+24V dc
0V dc
MMD-TA-..B
A2
A1
Open
Open
Open
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 26. MSSI or SSI Category 2 interfacing: positive opening
4.17.6 Category 3
A dual-channel wiring switching +24V dc is typically a category 3 application, because a single failure does not result in a
loss of safety. Loss of the switching action in one channel is detected by the actuation of opening and closing the guard,
allowing the monitoring function of the Muteable Safety Stop Interface (MSSI) or Safety (Protective) Stop Interface (SSI)
inputs to detect the discrepancy between the channels. However, a short circuit between input channels or safety outputs
may not be detected. It should be noted that an accumulation of faults may cause the loss of the safety function.
The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an
acceptable (minimal) level of risk, the possibility of undetected faults or catastrophic failures that could result in the loss of
the safety function.
+24V dc
0V dc
MMD-TA-..B
A2
A1
Open
Open
Open
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 27. MSSI or SSI Category 3 interfacing: Positive-opening Interlocking switch(es)
www.bannerengineering.com - Tel: + 1 888 373 6767
35
MMD-TA-11B/MMD-TA-12B Muting Module
4.17.7 Category 4
The self-monitoring Muteable Safety Stop Interface (MSSI) or Safety (Protective) Stop Interface (SSI) inputs can be
interfaced to achieve a category 4 application. The principle of fault exclusion must be incorporated into the design and
installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of catastrophic failures/faults
that could result in the loss of the safety function.
+24V dc
0V dc
MMD-TA-..B
A1
A2
Open
MSSI or SSI
(a)
S12
X6
(b)
S11
X5
(c)
S22
X8
(d)
S21
X7
Figure 28. SSI Category 4 interfacing: positive-opening interlocking switch(es)
4.18 SSI Supplemental Safety System Wiring
A variety of safety systems can be interfaced with the Mutable Safety Stop Interface (MSSI) and the Safety Stop Interface
(SSI). Each safety application has a unique set of application requirements. The user is responsible to ensure proper
installation and use, and that all relevant standards and regulations are complied with. Figure 29 (p. 37) shows a generic
example of the flexibility of the SSI.
Entry/Exit Application with a Multiple-Beam Safety System (Muted) and a Safety Mat System: see Typical Muting
Applications (p. 58) for more information. This application is widely used in a variety of situations, including manufacturing
cells, robotic cells, palletizers, and de-stackers. One of the many requirements of this muting application is that it must not
be possible for personnel to walk in front of, behind, or next to the muted object (for example, the carrier basket) without
being detected and stopping the hazardous motion.
Figure 29 (p. 37) shows how supplemental safeguarding (such as a safety mat system or horizontal safety light screen)
can be interfaced to prevent personnel from entering the hazardous area during a mute condition.
36
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
EZ-SCREEN Grid
Receiver
Safe Area
(free movement of personnel)
M1
M2
Hazardous Area
(protected from personnel entry)
Carrier
Basket
Safety Mat (or
Horizontal-Mounted
Safety Light Screen)
EZ-SCREEN Grid
Emitter
3-Beam
EZ-SCREEN Grid
(see note above)
0V dc
+24V dc
MMD-TA-11B
A1
OSSD1
+24V dc
0V dc
Ground
+24V dc
0V dc
Ground
OSSD2
S11 b
S21 d
Z21 +
+
+
-
-
M1 PNP
-
-
b
X5
c
X8
d
X7
Mute
Lamp
(indicator)
M2 NPN
4-wire Safety Mat
(or horizontally-mounted
Safety Light Screen)
X1
X2
M1
Z22 +
+
X6
Reset
Z11 -
+
a
SSI
MSSI
S22 c
Safety Mat
Monitor Module
(or Light Screen
Controller)
A2
S12 a
Hard Guarding
X3
+
X4
M2
Z12 X9
Override A
Z23 +
X10
M3 PNP
M3
X11
Z13 -
Override B
X12
Z24 +
M4 NPN
M4
Y1
EDM1
Z14 X13
X14
Y2
Y3
Mute
Enable
EDM2
Y4
(optional)
L1
Machine Interface
(see Figures listed below)
Machine
Control
Circuits*
13
K1A
K2A
K1B
K2B
14
24
23
31
L2
MPCE1
MPCE2
32
K1C
K2C
Machine interface - see Figure 27 (p. 35), Figure 28 (p. 36), Figure 30 (p. 41), and Figure 35 (p. 45).
Figure 29. Interfacing supplemental safeguarding to prevent personnel from entering the hazardous area during the mute
www.bannerengineering.com - Tel: + 1 888 373 6767
37
MMD-TA-11B/MMD-TA-12B Muting Module
5 Machine Interface - Initial Wiring and Checkout
Model MMD-TA-11B provides two normally open safety relay output contacts (13−14 and 23−24) to hook up external
MPCE1 and MPCE2, see Figure 33 (p. 44) and Figure 34 (p. 44).
Model MMD-TA-12B provides two PNP solid-state safety outputs, OSSD1 and OSSD2 (Y5−Y6 and Y7−Y8), see Figure 30
(p. 41), Figure 31 (p. 42), and Figure 32 (p. 43).
For monitoring external devices (both models), normally closed contacts of these devices must be hooked up to EDM #1
(Y1−Y2) and EDM #2 (Y3–Y4).
Before proceeding, ensure that power has been removed from machine or ensure that power is not available to the machine
controls or actuators, and ensure that the machine control (MPCEs) are not connected to or controlled by the OSSD or relay
safety outputs at this time. Permanent connections will be made after Module initial checkout .
5.1 Verifying System Operation
The initial checkout procedure must be performed by a Qualified Person. It must be performed only after configuring the
Module and after properly installing and configuring the safety systems connected to its Muteable Safety Stop Interface
(MSSI) and the Safety (Protective) Stop Interface (SSI) inputs (per System Installation (p. 16)).
The initial checkout procedure is performed on two occasions:
• To ensure proper installation when the System is first installed
• To ensure proper System function whenever any maintenance or modification is performed on the System or on the
machinery being guarded by the System.
For the initial checkout, the Muting Module and associated safety systems must be checked without power being available
to the guarded machine. Final interface connections to the guarded machine cannot take place until these systems have
been checked out.
Verify that:
• Power has been removed from (or is not available to) the guarded machine, its controls or actuators
• The machine control circuit is not connected to the Output Signal Switching Device (OSSD) outputs at this time
(permanent connections will be made following this initial checkout), and that the OSSD leads are isolated (not
shorted together, not shorted to power or ground)
• External device monitoring (EDM) has been configured for No Monitoring (SW4 = OFF or 2 CH) and EDM #1 (Y1−Y2)
and EDM #2 (Y3−Y4) are jumpered
• Other than EDM and Mute Enable, verify proper Module DIP switch configuration for your application
• All input connections have been made per appropriate sections for the Mute Input Devices (M1−M4), SSI, MSSI,
Manual Reset Switch, Mute Lamp, AUX Output, and Override Input
This will allow the Muting Module and the associated safety systems to be checked out, by themselves, before permanent
connections are made to the guarded machine.
5.2 Temporary Power and Initial Checkout
Connect the system DC power at terminals A1 (+24V dc) and A2 (0V dc), see Connection Terminals and Functions (p. 19).
All wiring must comply with NEC and local wiring codes.
1. Leaving power to the guarded machine OFF, power up the Module and the safety systems connected to the
Muteable Safety Stop Interface (MSSI) and the Safety (Protective) Stop Interface (SSI) inputs.
2. Perform system checkout procedures for the external safety systems connected to the MSSI and SSI inputs as
described by the appropriate manuals.
Do not proceed further until all checkout procedures are completed successfully and all problems have been
corrected.
3. Verify that the external safety systems are providing a Green/Go signal to the MSSI and SSI inputs (that is, Banner
Output Signal Switching Device (OSSD) sourcing signal or a closed contact connected to the Signal pin of each
interface). Verify that the green Channel indicators are ON.
Note: If the SSI is not to be used, terminals X5−X6 and X7−X8 must be jumpered (factory default).
Do not short Channel A to Channel B. See SSI and MSSI Interfacing (p. 26).
4. Auto Reset Configuration: Verify that the Green status LED is ON, indicating that the OSSD outputs are ON, and that
a “—” appears on the Diagnostic Display. If not, or if the Red status indicator begins to flash at any time, see
Troubleshooting (p. 50).
38
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
5. Manual Reset Configuration: Verify that the amber status LED is flashing to indicate that a reset is being requested,
and that a “—” appears on the Diagnostic Display. If not, or if the Red status indicator begins to flash at any time,
see Troubleshooting (p. 50).
6. Manual Reset Configuration: Perform a manual reset by closing the Reset input for at least 1/4 second, but not
longer than 2 seconds, and then reopening the contact. Verify that the Green status indicator turns on. The Module
OSSD outputs should be ON at this time.
7. Cycle the MSSI and the SSI (if used) individually and ensure that the Green status indicator turns OFF, and that a
reset is possible after the interface is closed.
Important: If any of the checks in step 1–7 checks fail, do not attempt to use the system until the
reason for the failure(s) is identified and corrected.
8. If the Muting function is not used, proceed to Permanent Wiring to the Guarded Machine (p. 40). If the Muting
function is use, continue with step 9.
9. During the initial checkout procedure of the Muting feature, if possible, verify that the power has been removed or is
otherwise not available to the machine actuators responsible for hazardous motion. At all times ensure that
personnel are not exposed to any hazard.
10. Mute the System by blocking (or activating) both mute devices (typically M1 and M2) simultaneously (within 3
seconds).
11. If used, verify that the Mute indicator turns ON. If not, check the indicator and its wiring, and check the Diagnostic
Display for error codes.
12. Generate a stop command from the safeguarding device connected to the MSSI (for example, interrupt the defined
area of a safety light screen).
13. Verify that MSSI Channel A and B indicators go OFF, but the Green status indicator remains ON.
Note: If the 30- or 60-second Backdoor Timer feature is selected, the Diagnostic Display will
begin to count down in seconds. If the 30-minute Backdoor Timer feature is selected, the timer
countdown is in minutes. A flashing dash will appear on the display if the Backdoor Timer is OFF
(infinite).
14. Clear the Stop command (before the Backdoor Timer expires) and verify that the MSSI Channel A and B indicators
come ON.
15. Clear (deactivate) the mute devices before the Backdoor Timer expires and verify the Mute indicator turns OFF.
The Green status indicator should remain ON.
16. Verify that it is not possible for a single individual to initiate a mute condition by triggering the mute devices (for
example, by blocking both photoelectric beams or actuating both switches) and being able to pass through the
safeguard without being detected and without issuing a stop command to the machine. Do not expose any
individual to hazard while attempting to mute the system.
17. Verify that it is not possible for personnel to pass in front of, behind, or next to the muted object without being
detected and without issuing a stop command to the machine.
18. If one-way (directional) muting has been selected, verify that the system can not be muted by blocking (or activating)
M3−M4 before M1−M2. Do not expose any individual to hazard while attempting to mute the system.
19. If all checks have been verified, proceed to Permanent Wiring to the Guarded Machine (p. 40).
Important: If any of these checks fail, do not attempt to use the system until the reason for the
failure(s) is identified and corrected.
www.bannerengineering.com - Tel: + 1 888 373 6767
39
MMD-TA-11B/MMD-TA-12B Muting Module
6 Permanent Wiring to the Guarded Machine
Output Signal Switching Device (OSSD) and External device monitoring (EDM) Connections and Electrical Interface Supply
power, the external reset switch, and other inputs (as required by each application) should be previously connected by this
point. The final connections to be made are:
• Mute enable
• EDM wiring
• OSSD outputs
• FSD interfacing
• MPCE connections
WARNING:
• Risk of electric shock
• Use extreme caution to avoid electrical shock. Serious injury or death could result.
• Always disconnect power from the safety system (for example, device, module, interfacing, etc.),
guarded machine, and/or the machine being controlled before making any connections or
replacing any component. Lockout/tagout procedures might be required. Refer to OSHA
29CFR1910.147, ANSI Z244-1, or the applicable standard for controlling hazardous energy.
• Make no more connections to the device or system than are described in this manual. Electrical
installation and wiring must be made by a Qualified Person5 and must comply with the applicable
electrical standards and wiring codes, such as the NEC (National Electrical Code), ANSI NFPA79,
or IEC 60204-1, and all applicable local standards and codes.
WARNING:
• Properly install arc or transient suppressors
• Failure to follow these instructions could result in serious injury or death.
• Install any suppressors as shown across the coils of the machine primary control elements. Do
not install suppressors directly across the output contacts of the safety or interface module. In
such a configuration, it is possible for suppressors to fail as a short circuit.
Important: Proper Wiring
The generalized wiring configuration shown in Figure 30 (p. 41), Figure 31 (p. 42), Figure 32 (p. 43),
Figure 33 (p. 44), and Figure 34 (p. 44) are provided only to illustrate the importance of proper
installation. The proper wiring of the Safety system to any particular machine is the sole responsibility of
the installer and end user.
5
40
A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and
experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
0V dc
A1
MMD-TA-12B
A2
EDM1
Y1
Y2
EDM2
Y3
Y4
+
OSSD1
OSSD2
Y5
+
0V
Y6
0V
Y7
Y8
FSD1
FSD2
Single-Channel
Safety Stop Circuit
Dual-Channel
Safety Stop Circuit
Figure 30. Generic machine interface wiring: module model MMD-TA-12B, FSD with Two-Channel EDM
www.bannerengineering.com - Tel: + 1 888 373 6767
41
MMD-TA-11B/MMD-TA-12B Muting Module
0V dc
+24V dc
A1
MMD-TA-12B
A2
Y1
EDM1
Y2
Y3
EDM2
Y4
+
OSSD1
OSSD2
Y5
+
0V
Y6
0V
Y7
Y8
IM-T-9A
S3
S1
K2
+24V dc
Machine
Control
K1
S4
S2
Y3
Y4
Y1
Y2
13
14
23
24
33
34
MPCE
1
*
MPCE
2
*
Feedback (optional)
* Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2 is recommended (see Warning)
Figure 31. Generic machine interface wiring, model MMD-TA-12B: interface module with two-channel EDM
42
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
0V dc
+24V dc
A1
MMD-TA-12B
A2
EDM1
Y1
Y2
EDM2
Y3
Y4
+
OSSD1
OSSD2
Y5
+
0V
Y6
0V
Y7
Y8
IM-T-9A
S3
S1
K2
+24V dc
Machine
Control
K1
S4
S2
Y3
Y4
Y1
Y2
13
14
23
24
33
34
MPCE
1
*
MPCE
2
*
Feedback (optional)
* Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2 is recommended (see Warning)
Figure 32. Generic machine interface wiring, model MMD-TA-12B: interface module with one-channel EDM
www.bannerengineering.com - Tel: + 1 888 373 6767
43
MMD-TA-11B/MMD-TA-12B Muting Module
+24V dc
0V dc
A1
MMD-TA-11B
A2
Y1
EDM1
Y2
Y3
EDM2
Y4
L1
Machine
Control
Circuits
K1A
K2A
K1B
K2B
L2
13
14
24
23
31
MPCE1
MPCE2
32
K1C
K2C
* Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2
is recommended (see Warning)
Figure 33. Generic machine interface wiring, model MMD-TA-11B: MPCE with 2-channel EDM
+24V dc
0V dc
A1
MMD-TA-11B
A2
Y1
EDM1
Y2
Y3
EDM2
Y4
L2
L1
K1A
Machine
Control
Circuits
K2A
13
K1B
K2B
24
23
31
MPCE1
14
MPCE2
32
K1C
K2C
* Installation of transient (arc) suppressors across the coils of MPCE1 and MPCE2
is recommended (see Warning)
Figure 34. Generic machine interface wiring, model MMD-TA-11B: MPCE with 1-channel EDM
44
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
6.1 Mute Enable Wiring
The Module provides a Mute Enable input (ME, X13−X14) for the connection of a potential free contact. Mute Enable gives
the user the ability to frame or create a window of opportunity when a mute can occur. When configured, the Mute Enable
input is a contact that must be closed before the safeguard can be muted. After the safeguard is muted, opening of the
Mute Enable input has no effect, but it must be re-closed before the safeguard can be muted again.
To connect a device (sensor or PLC output) with a solid-state output, see optional wiring in Figure 35 (p. 45).
If Mute Enable is not to be used, leave the factory-installed jumper between X13–X14.
0V dc
+24V dc
A1
Machine Control
MMD-TA-..B
A2
0V dc
X13
or
X14
Optional Wiring
0V dc
+24V dc
+24V dc
A1
Sensor or PLC
MMD-TA-..B
A2
0V dc
X13
Semiconductor
PNP output
X14
Figure 35. Mute Enable Wiring
6.2 External Device Monitoring (EDM) Wiring
The Module provides connection terminals for the External Device Monitoring input (EDM #1—Y1−Y2 and EDM #2—
Y3−Y4). External Device Monitoring must be wired in one of three configurations:
• One-Channel Monitoring — SW4 Banks A and B = ON or 1 CH (see Figure 32 (p. 43) and Figure 34 (p. 44))
•
•
Note: EDM #2 input must be left open.
Two-Channel Monitoring — SW4 Banks A and B = OFF or 2 CH (see Figure 30 (p. 41), Figure 31 (p. 42), Figure 33
(p. 44))
No Monitoring — SW4 Banks A and B = OFF or 2 CH
Note: Terminal Y1 of EDM #1 must be jumpered to Y3 of EDM #2.
After the initial checkout has been successfully completed, the EDM configuration that disabled the monitoring function
must be properly reconfigured. The External Device Monitoring inputs then must be properly connected to the closed
monitoring contacts of the MPCEs (see External Device Monitoring (EDM) (p. 9)). Refer to the important note, below,
regarding MPCE Monitoring Wiring, and Figure 30 (p. 41), Figure 31 (p. 42), Figure 32 (p. 43), Figure 33 (p. 44), and Figure
34 (p. 44).
www.bannerengineering.com - Tel: + 1 888 373 6767
45
MMD-TA-11B/MMD-TA-12B Muting Module
WARNING:
• External Device Monitoring (EDM)
• Creating a hazardous situation could result in serious injury or death.
• If the application does not require this function, the terminal Y1 of EDM #1 must be jumpered to
Y3 of EDM #2. It is the user’s responsibility to ensure that this does not create a hazardous
situation.
Important: Regarding External Device Monitoring Wiring
It is strongly recommended that one normally closed, forced-guided, monitoring contact of each MPCE
or external device be wired in order to monitor the state of the MPCEs (as shown in Figure 30 (p. 41),
Figure 31 (p. 42), Figure 32 (p. 43), Figure 33 (p. 44), and Figure 34 (p. 44)) . If this is done, proper
operation of the MPCEs will be verified. MPCE monitoring contacts must be used in order to maintain
control reliability.
6.3 Output Signal Switching Device (OSSD) Output
Connections
Both of the OSSD outputs must be connected to the machine control such that the machine’s safety related control system
interrupts the circuit or power to the machine primary control element(s) (MPCE), resulting in a nonhazardous condition. This
applies equally to the safety relays of the model MMD-TA-11B and the solid-state output of the model MMD-TA-12B.
Final Switching Devices (FSDs) typically accomplish this when the OSSDs go to an OFF state. See Figure 30 (p. 41).
See the output specifications and Warning below before making OSSD connections and interfacing the Muting Module to
the machine.
WARNING: OSSD Interfacing
To ensure proper operation, the Muting Module output parameters and machine input parameters must
be considered when interfacing the Muting Module solid-state OSSD outputs to the machine inputs.
Machine control circuitry must be designed so that:
• The maximum cable resistance value between the Muting Module solid-state safety outputs and
the machine inputs is not exceeded
• The Muting Module solid-state safety output maximum OFF-state voltage does not result in an
ON condition
• The Muting Module solid-state safety output maximum leakage current, due to the loss of 0V, will
not result in an ON condition
Failure to properly interface the OSSD outputs to the guarded machine could result in serious bodily
injury or death.
6.4 FSD Interfacing Connections
FSDs (Final Switching Devices) take many forms. The most common are forced-guided devices, mechanically linked relays,
or interface modules. The mechanical linkage between the contacts allows the device to be monitored by the External
Device Monitoring circuit for certain failures.
Depending on the application, the use of FSDs can facilitate controlling voltage and current that differs from the OSSD
outputs of the Muting Module. FSDs can also be used to control an additional number of hazards by creating multiple safety
stop circuits.
6.4.1 Safety (Protective) Stop Circuits
Typically, safety stop circuits are either single channel (a series connection of at least two N.O. contacts); or dual channel (a
parallel connection of two N.O. contacts). In either method, the safety function relies on the use of redundant contacts to
control a single hazard, so that if one contact fails ON, the second contact will arrest the hazard and prevent the next cycle
from occurring.
46
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
Interfacing safety stop circuits must be wired so that the safety function cannot be suspended, overridden, or defeated,
unless accomplished in a manner at the same or greater degree of safety as the machine’s safety-related control system
that includes the Muting Module.
The normally open outputs from an interfacing module are a series connection of redundant contacts that form safety stop
circuits and can be used in either single-channel or dual-channel control methods.
Dual-Channel Control—Dual-channel (or two-channel) control has the ability to electrically extend the safe switching point
beyond the FSD contacts. With proper monitoring, such as EDM, this method of interfacing is capable of detecting certain
failures in the control wiring between the safety stop circuit and the MPCEs. These failures include a short-circuit of one
channel to a secondary source of energy or voltage, or the loss of the switching action of one of the FSD outputs, which
may lead to the loss of redundancy or a complete loss of safety if not detected and corrected.
The possibility of a wiring failure increases as the physical distance between the FSD safety stop circuits and the MPCEs
increase, as the length or the routing of the interconnecting wires increases, or if the FSD safety stop circuits and the
MPCEs are located in different enclosures. Thus, dual-channel control with EDM monitoring should be used in any
installation where the FSDs are located remotely from the MPCEs.
Single-Channel Control—Single-channel (or one-channel) control uses a series connection of FSD contacts to form a safe
switching point. After this point in the machine’s safety-related control system, failures that would result in the loss of the
safety function can occur, for example, a short-circuit to a secondary source of energy or voltage.
Thus, this method of interfacing should be used only in installations where FSD safety stop circuits and the MPCEs are
physically located within the same control panel, adjacent to each other, and are directly connected to each other; or where
the possibility of such a failure can be excluded. If this cannot be achieved, then two-channel control should be used.
Methods to exclude the possibility of these failures include, but are not limited to:
• Physically separating interconnecting control wires from each other and from secondary sources of power
• Routing interconnecting control wires in separate conduit, runs, or channels
• Routing interconnecting control wires with low voltage or neutral that cannot result in energizing the hazard
• Locating all elements (modules, switches, devices under control, etc.) within the same control panel, adjacent to
each other, and directly connected with short wires
• Properly installing multi-conductor cabling and multiple wires that pass through strain-relief fittings. Over-tightening
of a strain-relief can cause short circuits at that point
• Using positive-opening or direct-drive components installed and mounted in a positive mode
6.5 Commissioning Checkout
After power is connected to the Muting Module, the External device monitoring (EDM) has been properly configured, and
the Output Signal Switching Device (OSSD) outputs have been connected to the machine to be guarded, the operation of
the Muting Module with the guarded machine must be verified before the combined system may be put into service. To do
this, a Qualified Person must perform the Commissioning Checkout Procedure described in Commissioning Checkout (p.
52).
www.bannerengineering.com - Tel: + 1 888 373 6767
47
MMD-TA-11B/MMD-TA-12B Muting Module
7 Operating Instructions
7.1 Security Protocol
The Module must be mounted inside a lockable enclosure or cabinet rated IP54 or better, both to protect the Module from
environmental conditions and in order to prevent access by unauthorized personnel, if required by applicable standards.
The key (or combination) to the enclosure should be kept in the possession of a Qualified Person and only they should have
access to the configuration switches. A Qualified Person is defined as an individual who, by possession of a recognized
degree or certificate of professional training, or who, by extensive knowledge, training, and experience, has successfully
demonstrated the ability to solve problems relating to the subject matter and work.
7.2 Periodic Checkout Requirements
In addition to the checkouts that are performed by a Qualified Person or persons at the time that the Module is installed and
put into service, the functioning of the safeguarding and the machine must be verified on a regular periodic basis to ensure
proper operation. This is absolutely vital and necessary. Failure to ensure proper operation can lead to serious injury or
death.
See Periodic Checkout Procedure (p. 52) for checkout schedules and procedures.
WARNING:
• Test the safeguarding function and verify proper operation
• Failure to test the safeguarding function at appropriate intervals, verify proper operation, and to
correct problems can lead to the loss of the safety function and an increased risk of harm.
• A machine or automatic test of the Banner device and its interface might be required as
determined by a risk assessment and applicable standard, for example, ISO 14121 and EN ISO
13849-1.
• Verify that the Banner device and the guarded machine perform as outlined in the checkout
procedures and any problem(s) are found and corrected. The user is responsible to perform such
checks on a regular basis and before the system is returned to service.
7.3 Normal Operation
During normal operation, the Module’s three status indicators (red, green and amber) are as shown in Table 1 (p. 48). In
addition, green and amber indicators adjacent to each of the Module’s inputs/interfaces come ON to verify an active state
of that circuit.
During normal operation, the Diagnostic Display will read “—” (solid or, if during the mute cycle, flashing). If the 30-or 60
second Backdoor Timer feature is selected, the Diagnostic Display will begin to count down in seconds. If the 30-minute
Backdoor Timer feature is selected, the timer countdown is in minutes. A flashing dash will appear on the display if the
Backdoor Timer is OFF (infinite). If the Red status indicator begins to flash, the number that appears in the Display signifies
an error; see Diagnostic Display (p. 50) for more information.
See Manual Reset Switch (p. 22) for information on the reset routine.
Table 1: Muting module status indicator conditions
Waiting for Reset6
Output OFF
Output ON
Override
Lockout
Red
ON
ON
OFF
ON
Flashing
Green
OFF
OFF
ON
ON
OFF
Amber
Flashing
ON
OFF
OFF
OFF
6
48
If either Muteable Safety Stop Interface (MSSI) or Safety (Protective) Stop Interface (SSI) set to MANUAL, the red Status LED will be OFF at powerup.
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
WARNING:
• Lockouts and power failures indicate a problem
• Attempts to continue to operate machinery by bypassing the Banner device or other safeguards
is dangerous and could result in serious injury or death.
• A Qualified Person7 must immediately investigate the problem.
7
A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and
experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.
www.bannerengineering.com - Tel: + 1 888 373 6767
49
MMD-TA-11B/MMD-TA-12B Muting Module
8 Troubleshooting
8.1 Troubleshooting Lockout Conditions
A lockout condition causes the Output Signal Switching Device (OSSD) outputs to turn OFF, sending a stop signal to the
guarded machine. A lockout condition is indicated by the Red status indicator flashing and an error code appearing in the
Diagnostic Display. To clear a lockout condition, the failure must be corrected, the associated input must be properly cycled
(if fault was due to an input failure), or a reset routine must be performed.
To perform a reset, close the reset input, hold closed for at least 1/4 second, but no longer than 2 seconds, and then reopen the input.
8.2 Diagnostic Display
The Module’s Diagnostic Display is useful for monitoring the safeguarding system and for quickly diagnosing problems. See
Troubleshooting Conditions, using the Module’s Diagnostic Display (p. 50) for a list of status codes and their meanings,
along with recommended corrective actions.
8.3 Effects of Electrical Noise
The Module is designed and manufactured to be highly resistant to electrical noise and to operate reliably in industrial
settings. However, serious electrical noise may cause a random lockout condition.
Check the following if a noise-related error code is displayed and other remedies have not cleared the problem: sensor
wires or input/output wires routed too close to noisy wiring.
In extreme conditions, it may be necessary to use shielded cabling or relocate the Module, mute devices, and cabling away
from the source of the noise.
8.4 Troubleshooting Conditions, using the Module’s
Diagnostic Display
Status Error Code
8
50
Condition/Error Type/Action
—
(Solid)
System OK
—
(Flashing)
Mute Cycle
31
Output Signal Switching Device (OSSD) Output Error
• One OSSD is shorted to power/ground
• OSSDs are shorted together
32
Reset Input Error
• Reset input shorted/closed
33
Module Error
• Excessive EMI/RFI noise
• Internal failure, replace Module
34
Muteable Safety Stop Interface (MSSI) Error8
• One or both channels shorted to power or ground
• Input channels shorted together
• One channel did not open
• Failed simultaneity (>3 s)
• Excessive EMI/RFI noise
Fault is cleared by cycling the input from open-to-closed.
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
Status Error Code
Condition/Error Type/Action
35
Override Error
• Override input closed at power-up
• Check Override input wiring and connector
• Excessive EMI/RFI noise
36
Mute Lamp Error
• Check/replace lamp (open or short)
• Check wiring and connector
• Check DIP switch settings
37
DIP switch Error
• Check DIP switch settings
• Replace Module
38
External device monitoring (EDM) 1 Error
• Check wiring
• Check operation of device(s) under control
• Check DIP switch settings
• Switching transition > 200 ms
• Excessive EMI/RFI noise
• EDM remains open > 200 ms after OSSDs go OFF (if dropout time verification check on)
• EDM not closed at startup
39
EDM 2 Error
• Verify that input 2 is open (single-channel EDM selected)
• Check wiring
• Check operation of device(s) under control
• Check DIP switch settings
• Excessive EMI/RFI noise
• EDM not closed at startup (Y3–Y4)
40
2-Channel EDM Error
• Check wiring
• Check operation of device(s) under control
• Failed simultaneity between EDM1 and EDM2 (> 200 ms)
• Both EDM open > 200 ms after OSSDs go OFF
• Replace Module
50
Backdoor Timer Expired
• Check muting device operation
• Check muting device wiring
• Check DIP switch settings
• See Backdoor Timer (p. 10)
51
Mute Timing (Simultaneity) Error
• The second mute device of a pair (M1–M2 or M3–M4) did not actuate within 3 seconds of the
first device
• Check muting device operation
• Check wiring
52
Mute Enable (ME) Open Error
• ME input was open when a mute cycle was attempted
• Check Mute Enable wiring
61
Safety (Protective) Stop Interface (SSI) Input Error8
• One or both channels shorted to power or ground
• Input channels shorted together
• One channel did not open
• Failed simultaneity (> 3 s)
• Excessive EMI/RFI noise
Flashing Mute
Lamp
Override Condition
www.bannerengineering.com - Tel: + 1 888 373 6767
51
MMD-TA-11B/MMD-TA-12B Muting Module
9 Periodic Checkout Procedure
Study each procedure from beginning to end before you start to make sure that you understand each step. Refer all
questions to Banner Engineering. Perform checkouts as detailed in Schedule of Checkouts (p. 52). Record results and
keep them in the appropriate place (for example, near the machine, and/or in a technical file).
Banner Engineering highly recommends performing the System checkouts as described. However, a qualified person (or
team) should evaluate these generic recommendations considering their specific application and determine the appropriate
frequency of checkouts. This will generally be determined by a risk assessment, such as the one contained in ANSI B11.0.
The result of the risk assessment will drive the frequency and content of the periodic checkout procedures and must be
followed.
9.1 Schedule of Checkouts
Checkout Procedure
When to Perform
Where to Find the Procedure Who Must Perform the
Procedure
Initial Checkout
At installation
See Machine Interface Initial Wiring and Checkout
(p. 38)
Qualified Person
See Commissioning
Checkout (p. 52)
Qualified Person
See Daily Checkout (p. 54)
Designated Person or
Qualified Person
See Semi-Annual Checkout
(p. 55)
Qualified Person
Any time the System, the guarded
machine, or any part of the
application is installed or altered
Commissioning
Checkout
After installation
Daily Checkout
At each shift change
Whenever changes are made to the
system (either a new configuration of
the safety system that includes the
MMD-TA-1..B module or changes to
the machine)
Machine setup change
Whenever the System is powered up
At least daily
Semi-Annual Checkout
Every six months, following System
installation
WARNING:
• Do not use the system until the checkouts are verified
• Attempts to use the guarded/controlled machine before these checks are verified could result in
serious injury or death.
• If all these checks cannot be verified, do not attempt to use the safety system that includes the
Banner device and the guarded/controlled machine until the defect or problem has been
corrected.
WARNING:
• Clear the guarded area before applying power or resetting the system
• Failure to clear the guarded area before applying power could result in serious injury or death.
• Verify that the guarded area is clear of personnel and any unwanted materials before applying
power to the guarded machine or before resetting the system.
9.2 Commissioning Checkout
Perform this checkout procedure as part of Safeguarding System installation (after the System has been interfaced to the
guarded machine as described in Machine Interface - Initial Wiring and Checkout (p. 38) and Permanent Wiring to the
Guarded Machine (p. 40)), or whenever changes are made to the System (either a new configuration of the Module, devices
connected to it, or changes to the machine). A Qualified Person (as defined in the Safety Glossary) must perform the
procedure; checkout results should be recorded and kept on or near the guarded machine, per OSHA 1910.217(e)(1).
To prepare the Module for this checkout, ensure the configuration is as it will be during machine operation.
52
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
9.2.1 Safeguarding Checkout
1. Examine the guarded machine to verify that it is of a type and design compatible with the safeguarding system that
has been installed.
2. Verify the system(s) checkout procedures for the external safety systems connected to the Muteable Safety Stop
Interface (MSSI) and the Safety (Protective) Stop Interface (SSI) inputs as described by the appropriate manuals.
Important: Do not proceed until all checkout procedures are completed successfully and all
problems have been corrected.
3. Verify that:
Access to any dangerous parts of the guarded machine is not possible from any direction not protected by the
safeguarding system, hard guarding, or supplemental safeguarding, and that
• Supplemental safeguarding and hard guarding, as described by the appropriate safety standards, are in place
and functioning properly.
4. Verify that the Reset switch is mounted outside the guarded area, out of reach of anyone inside the guarded area,
and that means of preventing inadvertent use is in place.
5. Examine the electrical wiring connections between the Module’s Output Signal Switching Device (OSSD) outputs
and the guarded machine’s control elements to verify that the wiring meets the requirements stated in Permanent
Wiring to the Guarded Machine (p. 40).
6. Apply power to the Module.
7. Ensure that power to the guarded machine is OFF.
8. Verify that the external safety systems are providing a green/Go signal to the MSSI and SSI inputs, and that the
green MSSI and SSI indicators (two pairs of LEDs located near each terminal) are ON.
When configured for Manual Reset, the amber status indicator will be flashing.
9. Perform a manual reset (close the Reset switch for 1/4 to 2 seconds, then open the switch).
10. Verify that the green status indicator is ON.
•
Note: A red flashing status indicator signifies a lockout condition. See Troubleshooting (p. 50) for
information.
11. In a non-muted condition, generate a stop command from the safeguarding device connected to the MSSI (for
example, interrupt the defined area of a safety light screen).
12. Verify that MSSI Channel A and B and the green status indicators go OFF.
13. In order, reset the safeguard and then the Module (in Manual Reset).
14. Generate a stop command from the safeguarding device connected to the SSI (for example, actuate E-stop button).
15. Verify that SSI Channel A and B and the green status indicators go OFF.
16. In order, reset the safeguard and then the Module (in Manual Reset).
17. Apply power to the guarded machine and verify that the machine does not start up.
18. Generate a stop command from the safeguarding device connected to the SSI and the MSSI in a non-muted
condition.
19. Verify that it is not possible for the guarded machine to be put into motion while either stop commands are present.
20. In order, reset the safeguard and then the Module (in Manual Reset).
21. Initiate machine motion of the guarded machine and, while it is moving, as in step 18 above, generate a stop
command from each safeguarding device.
Do not attempt to insert anything into the dangerous parts of the machine.
Upon issuing the stop command, the dangerous parts of the machine should come to a stop with no apparent
delay.
22. Upon reset of the safeguard and the Module, verify that the machine does not automatically restart, and that the
initiation devices must be engaged to restart the machine.
23. Remove electrical power to the Module.
All OSSD outputs should immediately turn OFF, and should not be capable of turning ON until power is re-applied
and a reset is accomplished.
24. Test the machine stopping response time, using an instrument designed for that purpose, to verify that it is the
same or less than the overall system response time specified by the machine manufacturer.
Banner Engineering may be able to recommend a suitable instrument.
Important: Do not continue operation until the entire checkout procedure is complete and all
problems are corrected.
www.bannerengineering.com - Tel: + 1 888 373 6767
53
MMD-TA-11B/MMD-TA-12B Muting Module
25. Continue with Muting Checkout (p. 54).
9.2.2 Muting Checkout
After Safeguarding Checkout (p. 53), perform the Muting Checkout.
1. Verify that the Module has been reset and the green status indicator is ON.
If the amber status indicator is flashing (indicating the safety system that includes the MMD-TA-1..B module is
waiting for a reset of a latched condition), perform a manual reset. At any time, if the red status indicator begins to
flash, a lockout condition exists. See Troubleshooting Lockout Conditions (p. 50) to determine the cause of the
lockout.
Important: During this procedure, at all times ensure that personnel are not exposed to any
hazard.
2. Mute the system by blocking (or activating) both mute devices (typically M1−M2) simultaneously (within 3 seconds).
3. Verify that the Mute indicator turns ON.
If the Mute indicator does not turn on, check the indicator and its wiring, verify that the mute enable input is closed,
and check the Diagnostic Display for error codes.
4. Generate a stop command from the safeguarding device connected to the Muteable Safety Stop Interface (MSSI);
verify the green MSSI channel indicators are OFF and the green status indicator is ON.
Note: If the Backdoor Timer feature has been selected, the Diagnostic Display will begin to count
down; otherwise a flashing dash will appear on the display.
5. Clear or reset the safeguard (before the Backdoor Timer expires) and verify the green MSSI channel indicators are
ON.
6. Clear (deactivate) the mute devices before the Backdoor Timer expires and verify the Mute indicator goes OFF.
The green status indicator should remain ON.
7. Verify that it is not possible for a single individual to initiate a mute condition by triggering the mute devices (for
example, by blocking both photoelectric beams or actuating both switches) and access the hazard without being
detected and issuing a stop command to the machine (where the green status indicator goes OFF, and a reset of
the latch condition is required).
Do not expose any individual to hazard while attempting to mute the system.
8. Verify that it is not possible for personnel to pass in front of, behind, or next to the muted object without being
detected and without issuing a stop command to the machine.
9. If one-way (directional) muting has been selected, verify that the system can not be muted by blocking (or activating)
M3−M4 before M1−M2.
Do not expose any individual to hazard while attempting to mute the system.
Important: If any of these checks fail, do not attempt to use the safety system that includes the MMDTA-1..B module until the reason for the failure(s) is identified and corrected.
9.3 Daily Checkout
Perform this checkout procedure at every shift change, powerup and machine set-up change.
During continuous machine run periods, this checkout must be performed at intervals not to exceed 24 hours. A Designated
Person or Qualified Person must perform the procedure; checkout results should be recorded and kept on or near the
guarded machine, per OSHA 1910.217(e)(1).
1. Verify that access to the guarded area is not possible from any area not protected by the safeguards interfaced with
the safety system that includes the MMD-TA-1..B module.
Hard guarding, or supplemental presence-sensing devices must be installed, wherever needed, to prevent any
person from reaching around the light grid or entering into the hazard area. Verify that all supplemental guarding
devices and hard guarding are in place and operating properly.
2. Verify that the safeguards interfaced with the safety system that includes the MMD-TA-1..B module have been
properly installed and maintained. See relevant instruction manuals or data sheets.
3. Verify that it is not possible for a person to access the hazard(s), undetected by the safeguards interfaced with the
safety system that includes the MMD-TA-1..B module or by other supplemental guarding (as described in
appropriate standards).
54
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
4. Verify that the Reset switch is mounted outside the guarded area, out of reach of anyone inside the guarded area,
and that the key or other means of preventing inadvertent use is in place.
5. Verify the system(s) checkout procedures for the external safety systems connected to the Muteable Safety Stop
Interface (MSSI) and the Safety (Protective) Stop Interface (SSI) inputs as described by the appropriate manuals.
6. Initiate machine motion of the guarded machine and, during the cycle, generate a stop command from the
safeguarding device. Do not attempt to insert anything into the dangerous parts of the machine. Upon issuing the
stop command, the dangerous parts of the machine should come to a stop with no apparent delay. Upon reset of
the safeguard and the Module, verify that the machine does not automatically restart, and that the initiation devices
must be engaged to restart the machine.
7. With the guarded machine at rest, generate a stop command from the safeguarding device(s) and verify that it is not
possible for the guarded machine to be put into motion.
8. Check carefully for external signs of damage or changes to the safety system that includes the MMD-TA-1..B
module, the interfaced safeguards, the guarded machine, and their electrical wiring. Immediately report any damage
or changes found to management.
Important: If any of these checks fail, do not attempt to use the safety system that includes the MMDTA-1..B module until the reason for the failure(s) is identified and corrected.
9.4 Semi-Annual Checkout
Perform this checkout procedure every six months following the safety system that includes the MMD-TA-1..B module
installation.
A Qualified Person must perform the procedure; checkout results should be recorded and kept on or near the guarded
machine, per OSHA 1910.217(e)(1).
1. Perform the commissioning checkout procedure ( Commissioning Checkout (p. 52)).
If any decrease in machine braking ability has occurred, make the necessary clutch/brake repairs, readjust
safeguard separation distance (Ds) appropriately, record the new Ds calculation, and re-perform the Daily Checkout
procedure.
2. Examine and test the machine primary control elements (MPCEs) and any intermediary controls (such as interface
modules) to verify that they are functioning correctly and are not in need of maintenance or replacement.
3. Inspect the guarded machine to verify that no other mechanical or structural problems could prevent the machine
from stopping or assuming an otherwise safe condition when signalled to do so by the safety system that includes
the MMD-TA-1..B module.
4. Examine and inspect the machine controls and connections to the safety system that includes the MMD-TA-1..B
module to verify that no modifications have been made which adversely affect the System.
Important: If any of these checks fail, do not attempt to use the safety system that includes the MMDTA-1..B module until the reason for the failure(s) is identified and corrected.
www.bannerengineering.com - Tel: + 1 888 373 6767
55
MMD-TA-11B/MMD-TA-12B Muting Module
10 Mute Timing Sequences
10.1 Muting Sequence with Two Muting Devices
For example, X-pattern Entry/Exit System, see Figure 36 (p. 58).
Power
ON
MSSI
Open
Closed
Open
Reset
System Reset
AUX Outputs OFF
MMD-TA-11B (open)
Reset
EDM
OFF (open)
OFF (open)
ON (closed)
OFF (open)
OFF (open)
Closed
Mute Enable Open
Mute
Inputs
Reset
ON (closed)
OFF
OSSD Outputs (open)
Open
Open
Closed
M1
Closed
Closed
{ M2
Closed
Mute Cycle
Mute
Less than
3 seconds
Normal mute cycle
OSSD outputs
remain ON
More than
3 seconds
Mute cycle prevented
due to open
Mute Enable input
Mute cycle prevented
due to simultaneity
not being met
DIP Switch Configuration9
MSSI Auto or Manual Reset . . . SW1 = OFF (Manual)
SSI Auto or Manual Reset . . . . SW2 = OFF (Manual) or ON (Auto)
One-Way Muting . . . . . . . . . . . . SW3 = OFF (1-way)
Two-/One-Channel EDM . . . . . . SW4 = OFF (2 CH)
Backdoor Timer . . . . . . . . . . . . . SW5&6 = OFF (30 sec.)
Monitored Muting Lamp . . . . . . SW7 = OFF (Mon)
Mute on Power-up . . . . . . . . . . . SW8 = OFF (Disable)
10.2 Muting Sequence with Four Muting Devices
For example, an Entry/Exit System using four photoelectric devices. See Figure 40 (p. 59).
9
56
Both DIP switch banks A and B.
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
Power
ON
MSSI
OSSD Outputs
Open
Reset
System Reset
AUX Outputs
MMD-TA-11B
Open
Closed
OFF
(open)
OFF
(open)
EDM Closed
Open
Reset
ON (closed)
OFF (open)
OFF (open)
ON (closed)
OFF (open)
OFF (open)
Open
Mute Enable Open
Mute
Inputs
Mute
Inputs
M1
{ M2
Closed
Closed
M3
Closed
{ M4
Mute Cycle
Closed
Mute
Mute
Less than
3 seconds
Normal mute cycle
OSSD outputs
remain ON
NOTE: A mute cycle begins 100 ms after the second
mute input becomes active, if all other
conditions are met.
One-Way Muting:
Mute cycle prevented
due to mute devices
M3 and M4 closing
before M1 and M2.
Two-Way Muting:
A normal mute cycle
would occur.
Mute cycle drops out
and the OSSD outputs open due
to M3 and M4 not closing before
M1 or M2 open, when the
defined area is blocked.
Since one-way muting has been
selected, M3 and M4 can not
initiate a mute cycle.
DIP Switch Configuration10
MSSI Auto or Manual Reset . . . SW1 = OFF (Manual)
SSI Auto or Manual Reset . . . . SW2 = OFF (Manual) or ON (Auto)
One-Way Muting . . . . . . . . . . . . SW3 = OFF (1-way)
Two-/One-Channel EDM . . . . . . SW4 = OFF (2 CH)
Backdoor Timer . . . . . . . . . . . . . SW5&6 = OFF (30 seconds)
Monitored Muting Lamp . . . . . . SW7 = OFF (Mon)
Mute on Power-up . . . . . . . . . . . SW8 = OFF (Disable)
10
Both DIT switch banks A and B.
www.bannerengineering.com - Tel: + 1 888 373 6767
57
MMD-TA-11B/MMD-TA-12B Muting Module
11 Typical Muting Applications
11.1 Entry/Exit Applications
The muting devices must be placed to ensure that the points that trigger the mute’s start and end are very close to the
safety light screen’s sensing field. This prevents personnel from following, or being pushed by, the object into the
hazardous area without interrupting the safety light screen before the mute window opens or at the time the mute window
closes.
When two pairs of opposed-mode photoelectrics are used as muting devices, as shown below, the crossing point of the
two sensing paths must be on the hazardous side of the safety light screen. The safety light screen will be interrupted
before any personnel would be able to block both beams and mute the system. The devices should detect the material and
not the pallet or the transport in order to hinder an individual from riding into the hazardous area.
Safe Area (free
movement of
personnel)
Light Screen Receiver
M1
Hazardous Area (which
is being protected from
personnel entry)
Carrier Basket
M2
Light Screen Emitter
Hard Guarding
Safety Mat or
Horizontally Mounted
Safety Light Screen
Figure 36. X-Pattern Entry/Exit system using two pairs of opposed-mode photoelectric muting devices
M1
(Emitter)
M1 *
M2 *
Light Screen
Defined Area
M1 *
Light Screen
Defined Area
M2 *
M2
(Receiver)
M2
(Receiver)
M1
(Emitter)
* Sensor not shown
* Sensor not shown
Figure 37. Horizontal photoelectric muting devices placed at different
heights
Figure 38. Photoelectric muting devices placed diagonally
WARNING:
• Verify That Unintentional Muting is Not Possible
• Failure to follow these instructions could result in serious injury or death.
• Position the crossing point of the photoelectric beams in the hazardous area so that it is not
accessible by personnel. An individual must not be able to block both photoelectric beams and
initiate a mute condition.
58
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
A ≥ (line speed in ft/sec) × 0.1 second
B ≈ 3 in or position must hinder personnel following a
muted object
C ≤ Length of carrier basket
Hard Guarding
M1
•
M3
R
•
•
Light Screen
Carrier Basket
E
M2
M4
Trapping hazards must be avoided and
clearance requirements complied with
Switch actuators can not be so long that they
allow a single person to initiate a muted
condition
Polarized-retroreflective (with targets mounted
on carrier) and inductive proximity sensors
could be used in a similar manner, if an
individual can not ride into the hazardous area.
One-way (directional) muting can be used in Exit
applications to reduce the possibility of intentional
defeat.
Transfer Line
A
B
Whisker/Limit Switches
C
Figure 39. Entry/exit system using 4 whisker/limit switches as muting devices
A ≥ (line speed in ft/sec) × 0.1 second
B ≈ 3 in or position must hinder personnel following a
muted object
Light Screen
Hard Guarding
M1
M2
M3
C ≤ Length of carrier basket
M4
D < (line speed in ft/sec) × 3.0 seconds, but beams M1
and M2 must be far enough apart to hinder an individual
from triggering both sensors
E
One-way (directional) muting can be used in Exit
applications to reduce the possibility of intentional
defeat.
Carrier Basket
R
Safety Mat
D
A
B
D
C
Figure 40. An entry/exit system using four photoelectric sensors as M1, M2, M3, and M4
WARNING:
• It must not be possible for personnel to walk in front of, behind, or next to the muted object
without being detected and stopping the hazardous motion.
• Failure to follow these instructions could result in serious injury or death.
• Use supplemental guarding to prevent personnel from entering the hazardous area during a mute
condition.
www.bannerengineering.com - Tel: + 1 888 373 6767
59
MMD-TA-11B/MMD-TA-12B Muting Module
11.2 Home or Station Applications
The muting devices must be placed to ensure that the safety light screen is muted only when the hazard does not exist or is
in another area so that personnel are not exposed. The muting devices must be placed so that if a hazard arises, or the
hazard enters the safeguarded area, the mute will immediately end and the safeguard will be active once again.
In home position muting applications, the light screen is active only while motion is taking place or a hazard is present, such
as the closing of an automated door. In this example, the door is interlocked and the machine can not start until the opening
is completely closed. The hazard being guarded by the light screen is the pinch point caused by the door closing.
M3 and M4 could be two SI-QS75MC safety switches, each with a single safety contact used for the muting input. M1 and
M2 could be SI-QS90MF safety switches, each with two safety contacts (one for muting and one for interlocking) and one
monitoring contact for a logic input.
If the light screen is also guarding hazards within the enclosure when the door is open or preventing cycle initiation, then
switches M3 and M4 would not be used. The door could also be locked by using locking style safety switches, such as the
SI-LS42 as M1 and M2.
Light Screen Emitter
Light Screen Receiver
M3
M1
Automated Door
M4
Hazardous Area
M2
Figure 41. A home position (door) muting application, using 4 safety switches as muting devices
WARNING: User is Responsible for Safe Application of this Device
The muting application examples described in this manual depict generalized guarding situations. Every
guarding application has a unique set of requirements.
Make sure that all legal requirements are met and that all installation instructions are followed. Direct any
questions regarding safeguarding to Banner Engineering.
11.3 Robot Load/Unload Station Application
This station muting application uses two independent safety light screen circuits, each with its own muting circuit and
muting devices (for example, polarized-retroreflective photoelectrics). The application also includes run bars with two-hand
control, auxiliary controls, and E-Stop. The two-hand control is provided at each station to safeguard the operator during
the momentary clamping action of the fixture while the safety light screen is muted.
In this example, the safety light screens are angled outwards (see Figure 42 (p. 61), detail A). This provides proper
separation distance from the hazards created by the robot and the clamping/welding fixtures, while protecting against the
possibility of pass-through hazards. In muting applications involving an operator, the operator must be continually
detectable by the defined area. This ensures that if a hazard arises, causing the mute to end while the operator is present,
the safety light screen will immediately issue a stop.
60
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
While the robot is at station A, the light screen at station B is muted (M1B and M2B are active), allowing the operator to load
or unload without issuing a stop command to the robot. As the robot moves out of the A work envelope (as defined by
Station B mute devices, see detail B) the mute discontinues at station B. If the operator is still within the protected area, a
stop command is immediately issued. As the robot moves to the work envelope of station B, the mute devices M1A and
M2A activate and mute the safety light screen at station A.
Detail A
Station "A" Run-Bar
Station "A"
Angled Light Screen
Hard Guarding
Station A
Work Envelope
Clamping and Welding Fixtures
Angled Light Screen
M1A and M2A
Station "A"
Mute Circuit
Station "B"
Retroreflective Targets
M1B and M2B Station
"B" Mute Circuit
Station "B" Run-Bar with
Two-Hand Control,
E-Stop, and Clamping
Manual Release
Detail B
Figure 42. A robot load/unload application with two-station home-position muting, using polarized retroreflective photoelectrics as muting devices
11.4 Turret Table Application
Turret Table application is similar to the Robot Load/Unload Station muting application, except that any movement of the
table ends the mute. To accomplish this, small retroreflective targets (or tape) are positioned so that they will initiate the
mute (the sensors must be set to Light Operate) only after the table has finished indexing.
Note: The example shows four pairs of targets, one pair for each position.
When the table begins indexing again, the polarized retroreflective photoelectrics immediately lose sight of the targets and
end the mute. Since the rotation of the table is the hazard, the size and positioning of the targets must prevent muting while
motion is taking place.
The top of the emitter and receiver are angled outwards to maintain proper separation distance while preventing a passthrough hazard. Hard guarding, or other safeguarding, must be positioned to prevent personnel from reaching through and
accessing any hazard.
www.bannerengineering.com - Tel: + 1 888 373 6767
61
MMD-TA-11B/MMD-TA-12B Muting Module
Load Conveyor
Unload Conveyor
Retroreflective Targets
at Each Position to
Initiate a Mute
Milling and Drilling
Operations
Load
Unload
M1
M2
Hard Guarding
Defined Area
Muting Sensors and
Retroreflective Targets
at Different Heights
and Positions
Figure 43. A typical application for turret table inspection or operation station muting, using retroreflective photoelectric sensors as muting devices
11.5 Power Press Applications
Muting is allowed on power presses only during the nonhazardous portion of the cycle (for example, the upstroke), per
OSHA1910.217, ANSI B11.1, B11.2, and B11.3. The mute permits the insertion or removal of material into the press that
would otherwise block the sensing field of the safety light screen, causing the press to stop. Muting should not be confused
with Inch or Jog modes, whose manual selection may bypass the safety light screen within the machine control.
For the proper application of muting on a power press, at a minimum, two (or four) independent position switches (such as
cam-operated limit switches, inductive prox sensors, or pressure switches) must be used to initiate the mute during the
nonhazardous portion of the machine cycle. These position switches would be mute devices M1/M2 (and M3/M4 if used).
Typically, these switches have normally open contacts, which are held (or actuated) closed during the mute cycle.
These switches must be mounted separately to prevent misadjustment, misalignment, or a single common mode failure,
which would result in an improper mute cycle or otherwise unsafe condition. They must be installed so that they can not be
easily defeated or bypassed, and their adjustment should be under supervisory control.
The two (or four) muting devices must be properly adjusted (or positioned) so that they close only after the hazard no longer
exists and then open when the cycle is complete (top of stroke) or when the hazard is again present. If improperly adjusted
or positioned, injury or death could result.
62
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
If the machine has reversing capability where a hazard is possible during a muted condition, the control must include an
automatic means through which muting is permitted in the forward (non-hazardous) direction only. A Mute Enable signal
from the machine control, motor drive, or other machine logic, is a means to assist in meeting this requirement.
In muting applications involving an operator, all pass-through hazards must be eliminated so that the operator is continually
detected when in the defined area. This ensures that if a hazard arises, causing the mute cycle to end while the operator is
present, the safety light screen will immediately issue a stop. (See pass-through hazard information below.)
A pass-through hazard is associated with applications that allow personnel to pass through a safeguard, which removes or
stops the hazard(s), and then allows the individual to continue into the hazardous area. Subsequently the individual’s
presence is no longer detected, and the safeguard can not prevent the start or restart of the machine. A pass-through can
be created by as little as 75 mm (3 in) space between the defined area and machine frame. If the safety light screen is
muted while the individual passes through the defined area, a stop command will not be issued and the hazard cannot be
eliminated; the individual must be detected while entering the safeguarded area and the hazardous motion must stop
immediately. This is typically accomplished by supplemental safeguarding such as described in ANSI B11 standards or
other appropriate standards.
WARNING: User Responsibility
The user is responsible for ensuring that all local, state, and national laws, rules, codes, and regulations
relating to the use of this device in any particular application are satisfied. Make sure that all legal
requirements have been met and that all installation, operation, and maintenance instructions contained
in the device documentation are followed.
www.bannerengineering.com - Tel: + 1 888 373 6767
63
MMD-TA-11B/MMD-TA-12B Muting Module
12 Accessories
12.1 Solid-State LED-Based Mute Lamp
Model
Description
SSA-ML-W
+24 V dc, White lens, stack-light style on 12-inch pole (see data sheet p/n 62097)
Note: Any standard NPN white or amber Banner EZ-LIGHT® can be used as a mute lamp.
12.2 Interface Modules
See datasheet p/n 62822 and p/n 208873 for more information.
Model
Input Voltage
Inputs
IM-T-9A
IM-T-11A
24 V dc
SR-IM-9A
2 (dual-channel
hookup)
SR-IM-11A
Safety Outputs
Aux. Outputs
3 N.O.
—
2 N.O.
1 N.C.
3 N.O.
—
2 N.O.
1 N.C.
Output Rating
EDM Contacts
6 amps
2 N.C.
See datasheet for
specifications
12.2.1 Mechanically Linked Contactors
Mechanically Linked Contactors provide an additional 10 or 18 amp carrying capability to any safety system. If used, two
contactors per Safety Output pair are required for Category 4. A single OSSD output with 2 contactors can achieve
Category 3. The N.C. contacts are to be used in an external device monitoring (EDM) circuit.
Model
11-BG00-31-D-024
BF1801L-024
64
Supply Voltage
Inputs
Outputs
24 V dc
2 (dual-channel hookup)
3 N.O. and 1 N.C.
www.bannerengineering.com - Tel: + 1 888 373 6767
Output Rating
10 amps
18 amps
MMD-TA-11B/MMD-TA-12B Muting Module
13 Product Support and Maintenance
13.1 Repairs
Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it contains
no field-replaceable parts or components. If the device, device part, or device component is determined to be defective by
a Banner Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization) procedure.
Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping is
not covered by warranty.
WARNING:
• Shut down the machinery before servicing
• Servicing the Banner device or system while the hazardous machinery is operational could result
in serious injury or death.
• The machinery to which the Banner device or system is connected must not be operating at any
time during major service or maintenance. This might require lockout/tagout procedures (refer to
OSHA1910.147, ANSI Z244-1, ISO 14118 or the applicable standard for controlling hazardous
energy).
13.2 Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following
the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which,
at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not
cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED
(INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO
EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY
EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL
DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT,
WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR
OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any
obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or
improper application or installation of this product or use of the product for personal protection applications when the
product is identified as not intended for such purposes will void the product warranty. Any modifications to this product
without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in
this document are subject to change; Banner reserves the right to modify product specifications or update documentation
at any time. Specifications and product information in English supersede that which is provided in any other language. For
the most recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.
13.3 Contact Us
Banner Engineering Corporate headquarters is located at:
9714 Tenth Avenue North
Minneapolis, MN 55441, USA
Website: www.bannerengineering.com
Phone: + 1 888 373 6767
For worldwide locations and local representatives, visit www.bannerengineering.com.
www.bannerengineering.com - Tel: + 1 888 373 6767
65
MMD-TA-11B/MMD-TA-12B Muting Module
14 Standards and Regulations
The list of standards below is included as a convenience for users of this Banner device. Inclusion of the standards below
does not imply that the device complies specifically with any standard, other than those specified in the Specifications
section of this manual.
14.1 U.S. Application Standards
ANSI B11.1 Mechanical Power Presses
ANSI B11.16 Metal Powder Compacting Presses
ANSI B11.2 Hydraulic Power Presses
ANSI B11.17 Horizontal Extrusion Presses
ANSI B11.3 Power Press Brakes
ANSI B11.18 Machinery and Machine Systems for the
Processing of Coiled Strip, Sheet, and Plate
ANSI B11.4 Shears
ANSI B11.19 Performance Criteria for Safeguarding
ANSI B11.5 Iron Workers
ANSI B11.20 Manufacturing Systems
ANSI B11.6 Lathes
ANSI B11.7 Cold Headers and Cold Formers
ANSI B11.8 Drilling, Milling, and Boring
ANSI B11.21 Machine Tools Using Lasers
ANSI B11.22 Numerically Controlled Turning Machines
ANSI B11.23 Machining Centers
ANSI B11.9 Grinding Machines
ANSI B11.24 Transfer Machines
ANSI B11.10 Metal Sawing Machines
ANSI B11.TR3 Risk Assessment
ANSI B11.11 Gear Cutting Machines
ANSI B11.12 Roll Forming and Roll Bending Machines
ANSI/RIA R15.06 Safety Requirements for Industrial Robots
and Robot Systems
ANSI B11.13 Single- and Multiple-Spindle Automatic Bar
and Chucking Machines
ANSI NFPA 79 Electrical Standard for Industrial Machinery
ANSI B11.14 Coil Slitting Machines
ANSI B11.15 Pipe, Tube, and Shape Bending Machines
14.2 OSHA Regulations
OSHA Documents listed are part of: Code of Federal
Regulations Title 29, Parts 1900 to 1910
OSHA 29 CFR 1910.147 The Control of Hazardous Energy
(lockout/tagout)
OSHA 29 CFR 1910.212 General Requirements for
(Guarding of) All Machines
OSHA 29 CFR 1910.217 (Guarding of) Mechanical Power
Presses
66
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
14.3 International/European Standards
EN ISO 12100 Safety of Machinery – Basic Concepts,
General Principles for Design
EN 60204-1 Electrical Equipment of Machines Part 1:
General Requirements
ISO 13852 (EN 294) Safety of Machinery—Safety Distances
to Prevent Danger Zones Being Reached by the Upper
Limbs
IEC 61496 Electro-sensitive Protection Equipment
EN 574 Two-Hand Control Devices – Functional Aspects –
Principles for Design
ISO 13853 (EN 811) Safety of Machinery—Safety Distances
to Prevent Danger Zones Being Reached by the Lower
Limbs
IEC 60529 Degrees of Protection Provided by Enclosures
IEC 60947-5-1 Low Voltage Switchgear – Electromechanical
Control Circuit Devices
IEC 60947-1 Low Voltage Switchgear – General Rules
IEC 61508 Functional Safety of Electrical/Electronic/
Programmable Electronic Safety-Related Systems
EN ISO 13849-1 Safety-Related Parts of Control Systems
IEC 62061 Functional Safety of Safety-Related Electrical,
Electronic and Programmable Control Systems
EN 13855 (EN 999) The Positioning of Protective Equipment
in Respect to Approach Speeds of Parts of the Human Body IEC 62046 Safety of Machinery – Applications of Protective
Equipment to Detect the Presence of Persons
ISO 14121 (EN 1050) Principles of Risk Assessment
ISO 14119 (EN 1088) Interlocking Devices Associated with
Guards – Principles for Design and Selection
www.bannerengineering.com - Tel: + 1 888 373 6767
67
MMD-TA-11B/MMD-TA-12B Muting Module
15 Glossary
A
ANSI (American National Standards Institute)
Auto Start/Restart (Trip) Condition
Acronym for the American National Standards Institute, an
association of industry representatives that develops technical
standards (including safety standards). These standards comprise
a consensus from a variety of industries on good practice and
design. ANSI standards relevant to application of safety products
include the ANSI B11 Series, and ANSI/RIA R15.06. See
Standards and Regulations (p. 66).
The safety outputs of a safety light screen system turn off when an
object completely blocks a beam. In an Auto Start/Restart
condition, the safety outputs re-energize when the object is
removed from the defined area.
Auto Power-Up
A light screen system feature which, when switched On, enables
the system to be powered up (and recover from a power
interruption) without requiring a manual reset. When Auto PowerUp is On, the light screen controller automatically begins internal
diagnostics upon power-up, and automatically resets the system if
it passes the diagnostic check. When Auto Power-up is Off, a
manual reset is required.
B
Brake
Blocked Condition
A mechanism for stopping, slowing, or preventing motion.
A condition that occurs when an opaque object of sufficient size
blocks/interrupts one or more light screen beams. When a blocked
condition occurs, OSSD1 and OSSD2 outputs simultaneously turn
off within the system response time.
C
CSA
Control Reliability
Abbreviation for Canadian Standards Association, a testing
agency similar to Underwriters Laboratories, Inc. (UL) in the United
States. A CSA-certified product has been type-tested and
approved by the Canadian Standards Association as meeting
electrical and safety codes.
A method of ensuring the performance integrity of a control
system or device. Control circuits are designed and constructed
so that a single failure or fault within the system does not prevent
the normal stopping action from being applied to the machine
when required, or does not create unintended machine action, but
does prevent initiation of successive machine action until the
failure is corrected.
D
Designated Person
Defined Area
A person or persons identified and designated in writing, by the
employer, as being appropriately trained and qualified to perform a
specified checkout procedure.
The "screen of light" generated by a safety light screen system,
defined by the height and the safety distance (minimum distance)
of the system.
E
Emitter
External Device Monitoring (EDM)
The light-emitting component of a safety light screen system,
consisting of a row of synchronized modulated LEDs. The emitter,
together with the receiver (placed opposite), creates a "screen of
light" called the defined area.
68
A means by which a safety device (such as a safety light screen)
actively monitors the state (or status) of external devices that may
be controlled by the safety device. A lockout of the safety device
will result if an unsafe state is detected in the external device.
External device(s) may include, but are not limited to: MPCEs,
captive contact relays/contactors, and safety modules.
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
F
FMEA (Failure Mode and Effects Analysis)
Failure to Danger
A testing procedure by which potential failure modes in a system
are analyzed to determine their results or effects on the system.
Component failure modes that produce either no effect or a
Lockout condition are permitted; failures which cause an unsafe
condition (a failure to danger) are not. Banner safety products are
extensively FMEA tested.
A failure which delays or prevents a machine safety system from
arresting dangerous machine motion, thereby increasing risk to
personnel.
Final Switching Device (FSD)
The component of the machine’s safety-related control system
that interrupts the circuit to the machine primary control element
(MPCE) when the output signal switching device (OSSD) goes to
the OFF-state.
Forced-Guided Contacts
Relay contacts that are mechanically linked, so that when the relay
coil is energized or de-energized, all of the linked contacts move
together. If one set of contacts in the relay becomes immobilized,
no other contact of the same relay will be able to move. The
function of forced-guided contacts is to enable the safety circuit to
check the status of the relay. Forced-guided contacts are also
known as "positive-guided contacts," "captive contacts," "locked
contacts," or "safety relays."
G
Guarded Machine
The machine whose point of operation is guarded by the safety
system.
H
Hazardous Area
Hard (Fixed) Guard
An area that poses an immediate or impending physical hazard.
Screens, bars, or other mechanical barriers affixed to the frame of
the machine intended to prevent entry by personnel into the
hazardous area(s) of a machine, while allowing the point of
operation to be viewed. The maximum size of the openings is
determined by the applicable standard, such as Table O-10 of
OSHA 29CFR1910.217, also called a "fixed barrier guard."
Hazard Point
The closest reachable point of the hazardous area.
I
Internal Lockout
A Lockout condition that is due to an internal safety system
problem. Generally, indicated by the red Status indicator LED
(only) flashing. Requires the attention of a Qualified Person.
K
Key Reset (Manual Reset)
A key-operated switch used to reset a safety light screen system
to Run mode following a Lockout condition, or to enable machine
operation following a Manual Start/Restart (Latch) condition. Also
refers to the act of using the switch.
L
Lockout Condition
A safety light screen condition that is automatically attained in
response to certain failure signals (an internal lockout). When a
Lockout condition occurs, the safety light screen’s safety outputs
turn Off; the failure must be corrected and a manual reset is
required to return the system to Run mode.
www.bannerengineering.com - Tel: + 1 888 373 6767
69
MMD-TA-11B/MMD-TA-12B Muting Module
M
Minimum Object Sensitivity (MOS)
Machine Operator
The minimum-diameter object that a safety light screen system
can reliably detect. Objects of this diameter or greater will be
detected anywhere in the defined area. A smaller object can pass
undetected through the light if it passes exactly midway between
two adjacent light beams. Also known as MODS (Minimum Object
Detection Size). See also Specified Test Piece.
An individual who performs production work and who controls
operation of the machine.
Machine Primary Control Element (MPCE)
An electrically powered element, external to the safety system,
which directly controls the machine’s normal operating motion in
such a way that the element is last (in time) to operate when
machine motion is either initiated or arrested.
Muting
The automatic suspension of the safeguarding function of a safety
device during a non-hazardous portion of the machine cycle.
Manual Start/Restart (Latch) Condition
The safety outputs of a safety light screen system turn off when an
object completely blocks a beam. In a Manual Start/Restart
condition, the safety outputs stay off when the object is removed
from the defined area. To re-energize the outputs, perform a
proper manual reset.
O
OSHA (Occupational Safety and Health Administration)
Off State
A U.S. Federal agency, Division of the U.S. Department of Labor,
that is responsible for the regulation of workplace safety.
The state in which the output circuit is interrupted and does not
permit the flow of current.
OSSD
On State
Output Signal Switching Device. The safety outputs that are used
to initiate a stop signal.
The state in which the output circuit is complete and permits the
flow of current.
P
Point of Operation
Pass-Through Hazard
The location of a machine where material or a workpiece is
positioned and a machine function is performed upon it.
A pass-through hazard is associated with applications where
personnel may pass through a safeguard (which issues a stop
command to remove the hazard), and then continues into the
guarded area, such as in perimeter guarding. Subsequently, their
presence is no longer detected, and the related danger becomes
the unexpected start or restart of the machine while personnel are
within the guarded area.
Point-of-Operation Guarding
Safeguards, such as hard guards or safety light screens, which are
designed to protect personnel from hazardous machine motion
when close to the machine’s point of operation.
Q
Qualified Person
A person who, by possession of a recognized degree or certificate
of professional training, or who, by extensive knowledge, training
and experience, has successfully demonstrated the ability to solve
problems relating to the subject matter and work.
R
Receiver
Reset
The light-receiving component of a safety light screen system,
consisting of a row of synchronized phototransistors. The receiver,
together with the emitter (placed opposite), creates a "screen of
light" called the defined area.
70
The use of a manually operated switch to restore the safety
outputs to the On state from a lockout or a Manual Start/Restart
(Latch) condition.
www.bannerengineering.com - Tel: + 1 888 373 6767
MMD-TA-11B/MMD-TA-12B Muting Module
S
Specified Test Piece
Safety Distance
An opaque object of sufficient size used to block a light beam to
test the operation of a safety light screen system. When inserted
into the defined area and placed in front of a beam, the test piece
causes the outputs to de-energize.
The minimum distance required to allow the machine’s hazardous
motion to stop completely, before a hand (or other object) can
reach the nearest hazard point. Measured from the midpoint of the
defined area to the nearest hazard point. Factors that influence
minimum separation distance include the machine stop time, the
light screen system response time, and the light screen minimum
object detection size.
Supplemental Guarding
Additional safeguarding device(s) or hard guarding, used to
prevent a person from reaching over, under, through or around the
primary safeguard or otherwise accessing the guarded hazard.
Self-Checking (Circuitry)
A circuit with the capability to electronically verify that all of its own
critical circuit components, along with their redundant backups,
are operating properly. Banner safety light screen systems and
safety modules are self-checking.
T
TUV (Technischer Überwachungsverein)
Test Piece
Independent testing and certification organization providing EMC
and product safety testing, certification, and quality management
systems registration.
An opaque object of sufficient size used to block a light beam to
test the operation of a safety light screen system.
U
UL (Underwriters Laboratory)
A third-party organization that tests products for compliance with
appropriate standards, electrical codes, and safety codes.
Compliance is indicated by the UL listing mark on the product.
www.bannerengineering.com - Tel: + 1 888 373 6767
71
Index
A
L
Protective Stop Interface 8
automatic reset 7
AUX 25
auxiliary output 9, 25
lockout condition 50
lockout conditions 8
Q
M
B
backdoor timer 10
C
category 2 28
category 3 28
category 4 30
checkout, periodic 52–55
control reliability 8
corner mirrors 17
D
designated person 12
E
EDM 9
emergency stop wiring 31, 32
external device monitoring 9
F
fault exclusion 27
I
interfacing
MSSI 26
SSI 26
qualified person 12
manual reset 7
manual reset switch 22
ME 10
mirrors 17
ML 10, 25
MSSI 8
MSSI interfacing 26
mute devices 10
mute enable 10
mute lamp output 10, 25
mute sensor 23
mute switch 23
Muteable Safety Stop Interface 8
muting
directional 12
muting
non-directional 12
one-way 12
two-way 12
muting device requirements 22
muting function 9
R
O
timer
backdoor 10
two-way muting 12
one-way muting 12
OSSD Outputs 8
override 11
override switch 26
P
periodic checkout procedure 52–55
redundancy 8
requirements
muting device 22
reset
automatic 7
manual 7
reset routine 22
reset switch
manual 22
S
safety circuit integrity levels 31
Safety Stop Interface 8
self-checking 8
SSI 8
SSI interfacing 26
T
W
wiring
emergency stop 31, 32