IM-T-9A and IM-T-11A Interface Module
Datasheet
Interface Modules For Use With a Primary Safety Device
•
•
•
•
•
•
•
Interface Modules provide isolated safety output contacts for a primary safety
device (for example, a safety light screen or safety module) which has solid-state or
hard contact outputs and external device monitoring (EDM) capability.
Model IM-T-9A features three normally open 6 amp redundant-output channels.
Model IM-T-11A features two normally open redundant-output channels and one
normally closed non-safety auxiliary output channel, all rated at 6 amps.
Normally closed outputs for connection to the primary safety device’s monitoring
input.
24 V DC operation
22.5 mm (0.9 inch) DIN-rail-mountable housing
Convenient plug-in terminal blocks
WARNING:
• Not a stand-alone point-of-operation guarding device
• This Banner Engineering Corp. device is not a stand-alone point-of-operation guarding device, as
defined by OSHA regulations. Failure to install point-of-operation guards on hazardous machinery can
result in a dangerous condition that could lead to serious injury or death.
• Install point-of-operation guarding devices, such as safety light curtains and/or hard guards, to protect
personnel from hazardous machinery.
Overview
The IM-T-9A and -11A Interface Module operates on 24 V dc inputs and provides isolated redundant output channels for interfacing
dc safety controls (such as safety light screens or other safety modules) to safety circuits. The Interface Module can also be used to
switch low power capacity of safety controls with low current output rating (see wiring diagrams and the output configuration
specifications).
The outputs of the Interface Module will follow the action of the safety outputs from the primary safety device which control it, within
a 20 millisecond switching delay time. The Interface Module’s normally open outputs each are rated for up to 250 V ac/dc at up to 6
amps. (See Specifications for derate curves.)
The Interface Module offers a series connection of normally closed contacts (labeled Y1-Y2 and Y3-Y4) for monitoring by the
external device monitoring (EDM) function of the primary safety device. These forced-guided (mechanically-linked) contacts allow
the safety device to detect failures of the Interface Module, and at a minimum, must be monitored in applications requiring Control
Reliability per OSHA/ANSI or Category 3 or 4 per ISO13849-1.
Important... read this before proceeding
The user is responsible for satisfying all local, state, and national laws, rules, codes, and regulations relating to the use of this
product and its application. Banner Engineering Corp. has made every effort to provide complete application, installation, operation,
and maintenance instructions. Please contact a Banner Applications Engineer with any questions regarding this product.
The user is responsible for making sure that all machine operators, maintenance personnel, electricians, and supervisors are
thoroughly familiar with and understand all instructions regarding the installation, maintenance, and use of this product, and with the
machinery it controls. The user and any personnel involved with the installation and use of this product must be thoroughly familiar
with all applicable standards, some of which are listed within the specifications. Banner Engineering Corp. makes no claim regarding
a specific recommendation of any organization, the accuracy or effectiveness of any information provided, or the appropriateness of
the provided information for a specific application.
Applicable U.S. Standards
ANSI B11 Standards for Machine Tools Safety
Contact: Safety Director, AMT – The Association for Manufacturing Technology, 7901 Jones Branch Drive, Suite 900, McLean, VA
22102-4206 USA, www.amtonline.org
NFPA 79 Electrical Standard for Industrial Machinery
Contact: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471 USA, www.nfpa.org/
ANSI/RIA R15.06 Safety Requirements for Industrial Robots and Robot Systems
Original Document
62822 Rev. H
9 August 2021
62822
IM-T-9A and IM-T-11A Interface Module
Contact: Robotic Industries Association, 900 Victors Way, Suite 140, Ann Arbor, MI 48108 USA, www.robotics.org
Applicable International Standards
EN ISO 12100 Safety of Machinery – Basic Concepts, General Principles for Design
EN 60204-1 Electrical Equipment of Machines Part 1: General Requirements
EN ISO 13849-1 Safety-Related Parts of Control Systems
Contact: IHS Markit (Global Engineering Documents), 15 Inverness Way East, Englewood, CO 80112 USA, https://global.ihs.com/
Status Indicators
Two green indicator LEDs on the front of each Interface Module indicate the output status of internal relays K1 and K2.
Figure 1. Interface Module Status Indicators
IM-T-9A
S1
13
IM-T-11A
S2
23
33
Y1
Y2
S1
13
K1 Energized
(S1/S2)
K1
Machine
Safety
IM-T-9A
23
K1
K2
Ch.1
Ch.2
Ch.2
K2
14
24
S3
Y1
Y2
Machine
Safety
IM-T-11A
Ch.1
Y4
Y3
S2
31
34
S4
Y4
Y3
14
32
S3
24
S4
K2 Energized
(S3/S4)
Primary Safety Device Requirements
IM-T-9A and -11A Interface Module are driven by one or two safety output channels of a primary safety device. For higher risk
applications, the design of the primary safety device must meet OSHA/ANSI control reliability requirements (U.S. applications) or
ISO/IEC/EN Category 3 or 4, Performance Level d or e, and SIL 2 or 3 requirements for European applications. The Interface
Module must be used only with primary safety devices that have External Device Monitoring capability (see wiring figures and the
Warning Interfacing MPCEs).
At a minimum, each output channel of the primary safety device must:
• Include one normally open forced-guided (mechanically linked) contact, or
• Include one solid-state 24V dc sourcing safety output (OSSD), and
• Be self-monitored to result in a safe (OFF) condition in the event of a failure, and
• Be capable of switching 50 mA at 24 V dc ± 15%.
NOTE: As OSSD solid-state outputs on primary safety devices very often are pulsed, it is possible that the relay coils will produce an
audible buzzing. This relay buzzing does not affect the function of the Interface Module, as long as the pulse width is below 500 μs
(microseconds) and the duty cycle (t1/ t2) is greater than 500.
Final Switching Device (FSD): The component of the machine’s safety-related control system that interrupts the circuit to the
machine primary control element (MPCE) when the output signal switching device (OSSD) goes to the OFF-state.
Output Signal Switching Device (OSSD): The component of the electro-sensitive protective equipment (ESPE) connected to the
control system of the machine which, when the sensing device is actuated during normal operation, responds by going to the OFFstate.
Figure 2. Requirements for pulsed output signals from a primary safety device
t 1 > 500
t2
t1
+24V dc
0V dc
2
t2
(500 µs max.)
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 62822 Rev. H
IM-T-9A and IM-T-11A Interface Module
WARNING: Not for use as a safety monitoring module
1. DO NOT connect E-stop switches, 2-hand control actuators/switches, safety interlock switches, or
similar devices directly to this Interface Module.
2. ALWAYS connect terminals Y1-Y2 and Y3-Y4 of this Interface Module to the monitoring input of the
primary safety device that controls it.
This Interface Module does not have the circuitry required to perform a self-check. A single fault inside the unit
or in external devices (like switches or emergency stop buttons) can go undetected and create an unsafe
condition. Failure to properly connect this Interface Module to a primary safety device with a monitoring function
could result in serious injury or death.
Mechanical Installation
The Interface Module must be installed inside an enclosure.
It is not designed for exposed wiring. It is the user’s responsibility to house the Interface Module in an enclosure with NEMA 3 (IEC
IP54) rating, or better. The Interface Module mounts directly to standard 35 mm DIN rail.
Heat Dissipation Considerations: For reliable operation, ensure that the operating specifications are not exceeded. The enclosure
must provide adequate heat dissipation, so that the air closely surrounding the Interface Module does not exceed the maximum
operating temperature stated in the Specifications. Methods to reduce heat build-up include venting, forced airflow (for example,
exhaust fans), adequate enclosure exterior surface area, and spacing between modules and other sources of heat.
Electrical Installation
WARNING:
• Risk of electric shock
• Use extreme caution to avoid electrical shock. Serious injury or death could result.
• Always disconnect power from the safety system (for example, device, module, interfacing, etc.),
guarded machine, and/or the machine being controlled before making any connections or replacing any
component. Lockout/tagout procedures might be required. Refer to OSHA 29CFR1910.147, ANSI
Z244-1, or the applicable standard for controlling hazardous energy.
• Make no more connections to the device or system than are described in this manual. Electrical
installation and wiring must be made by a Qualified Person 1 and must comply with the applicable
electrical standards and wiring codes, such as the NEC (National Electrical Code), NFPA 79, or IEC
60204-1, and all applicable local standards and codes.
WARNING:
• Determine the safety category
• The design and installation of the safety devices and the means of interfacing of those devices could
greatly affect the level of safety circuit integrity.
• Perform a risk assessment to determine the appropriate safety circuit integrity level or safety category,
as described by ISO 13849-1, to ensure that the expected risk reduction is achieved and that all
applicable regulations and standards are met.
CAUTION: When FSD1 switches +24 V DC and FSD2 switches 0 V DC (Figures 4 and 5), a short circuit
between the wires leading to S1, S2, S3 and S4 is detected immediately and K1 and K2 de-energize. However,
a short circuit can result in a high current through the FSD1 and FSD2 contacts, so the current coming from the
24 V DC supply connected to FSD1 and FSD2 must be fused or limited to 6 amps maximum. Otherwise,
damage to the primary safety device may result.
It is not possible to give exact wiring instructions for a Safety Module that interfaces to a multitude of machine control configurations.
The following guidelines are general in nature.
The Safety Module has no delay function. Its output relay contacts open within 20 milliseconds after a safety input opens. This
classifies the Safety Module as functional stop "Category 0" control, as defined by ANSI NFPA 79 and IEC/EN 60204-1.
The inputs can be connected to (that meet the requirements for primary safety device above):
•
•
A +24 V DC solid-state (PNP) outputs in single-channel or dual-channel wiring configuration, or
A +24 V/0 V DC source that is switched by hard/relay contacts in single-channel or dual-channel wiring configuration.
The dual-channel wiring configuration allows the primary safety device to detect certain failures and faults, such as short circuits,
that could result in a loss of the safety function. Two-channel control should be used whenever unsafe failure of the control wires
cannot be eliminated. The first circuit shown below can meet ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety
rating and the installation of the primary safety device.
1
A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has
successfully demonstrated the ability to solve problems relating to the subject matter and work.
P/N 62822 Rev. H
www.bannerengineering.com - Tel: + 1 888 373 6767
3
IM-T-9A and IM-T-11A Interface Module
The outputs of the primary safety device must, at minimum, comply with the requirements described. These outputs must be
monitored for failure by the primary safety device. In addition, a single output failure cannot prevent normal stopping action, and a
successive cycle cannot be initiated until the failure has been corrected.
Figure 3. Generalized wiring to a 2-channel primary safety device with two hardcontact safety outputs (FSD1 and FSD2) and two monitoring inputs.
+24 V dc
0 V dc
Figure 4. Generalized wiring to a 2-channel primary safety device with two hardcontact safety outputs and one monitoring contact feedback input.
+24 V dc
0 V dc
Primary
Safety
Device
Primary
Safety
Device
EDM1
EDM1
EDM2
Safety Output
Safety Output
Safety Output
Safety Output
..IM..9A
..IM..9A
S1
S4
K2
K2
K1
Y1
K1
S3
S2
S3
S1
S4
S2
Y1
MPCE2
Y2
Y2
Y3
Y3
MPCE1
Machine
Control
14
23
24
33
K2
K1
Feedback (optional)
MPCE
1
MPCE
2
MPCE2
Y4
Y4
13
MPCE1
Machine
Control
13
14
23
24
33
34
Arc suppressors
(see WARNING)
K2
K1
Feedback (optional)
MPCE
1
MPCE
2
34
Arc suppressors
(see WARNING)
Although these wiring diagrams show model IM-T-9A, the connections for model IM-T-11A are identical.
4
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 62822 Rev. H
IM-T-9A and IM-T-11A Interface Module
Figure 5. Generalized wiring to a 2-channel primary safety device with two
current-sourcing safety outputs and two monitoring inputs.
+24 V dc
0 V dc
Primary
Safety
Device
Figure 6. Generalized wiring to a 2-channel primary safety device with two
current-sourcing safety outputs and one monitoring input.
+24 V dc
0 V dc
Primary
Safety
Device
EDM1
EDM
+
+
+
EDM2
Safety
Output
+
Safety
Output
Safety Output
Safety Output
..IM..9A
..IM..9A
S4
K2
S1
K2
S1
S4
K1
S3
K1
S2
Y1
S2
S3
Y1
Y2
MPCE2
Y3
Y2
Y3
MPCE1
Y4
Machine
Control
13
14
23
24
33
K2
K1
Feedback (optional)
MPCE2
MPCE1
Y4
MPCE
1
MPCE
2
Machine
Control
13
14
23
24
33
K2
K1
MPCE
2
34
Feedback (optional)
34
MPCE
1
Arc suppressors
(see WARNING)
Arc suppressors
(see WARNING)
Although these wiring diagrams show model IM-T-9A, the connections for model IM-T-11A are identical.
WARNING:
• Properly install arc or transient suppressors
• Failure to follow these instructions could result in serious injury or death.
• Install any suppressors as shown across the coils of the machine primary control elements. Do not
install suppressors directly across the output contacts of the safety or interface module. In such a
configuration, it is possible for suppressors to fail as a short circuit.
P/N 62822 Rev. H
www.bannerengineering.com - Tel: + 1 888 373 6767
5
IM-T-9A and IM-T-11A Interface Module
Figure 7. Generalized wiring to a primary safety device with one redundant relay
safety output (one-channel control) and one monitoring input.
+24 V dc
0 V dc
Primary
Safety
Device
WARNING: Single-Channel Wiring. Singlechannel wiring, as shown is only for use
when the PSD and the Interface Module
are within the same enclosure. Refer to
One-Channel Control.
EDM
Safety Output
..IM..9A
S1
S4
K2
K1
S3
S2
Y1
Y2
Y3
MPCE2
MPCE1
Y4
Machine
Control
13
14
23
24
33
K2
K1
Feedback (optional)
MPCE
1
MPCE
2
34
Arc suppressors
(see WARNING)
Although this wiring diagram shows model IM-T-9A, the
connection for model IM-T-11A is identical.
The single-channel input wiring configuration can not detect short circuits to secondary sources of +24 V DC or detect the loss of the
switching function of the primary safety device (i.e., it is not redundant) and thus this circuit typically can meet only ISO 13849-1
Category 2.
It is recommended that in all circumstances the installation of the Interface Module and its associated primary safety device are
installed to eliminate or minimize the possibility of failures and faults that could result in the loss of the safety function(s). Methods to
eliminate or minimize the possibility of these failures include, but are not limited to:
•
•
•
•
•
•
Physically separating interconnecting control wires from each other and from secondary sources of power.
Routing interconnecting control wires in separate conduit, runs, or channels.
Locating all elements (modules, switches, and devices under control) within one control panel, adjacent to each other, and
directly connected with short wires.
Properly installing multi-conductor cabling and multiple wires through strain-relief fittings. (Overtightening of a strain-relief
can cause short circuits at that point.)
Using positive-opening components as described by IEC 60947-5-1 installed and mounted in a positive mode.
Periodically checking the functional integrity / safety function and training operators, maintenance personnel, and others
associated with the operation of the machine to recognize and immediately correct such failures.
If you have any questions about your intended use, please contact a Banner applications engineer at the numbers listed on the last
page.
Connection to the Machine to be Controlled
The wiring diagrams show a generic connection of two safety output channels of the Interface Module to Machine Primary Control
Elements MPCE1 and MPCE2. A Machine Primary Control Element is an electrically powered device, external to the Interface
Module, which stops the machinery being controlled by immediately removing electrical power from the machine and (when
necessary) by applying braking to dangerous motion.
6
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 62822 Rev. H
IM-T-9A and IM-T-11A Interface Module
Figure 8. Interface Module Pinouts
..IM..9A
S3
K2
S4
..IM..11A
S1
S3
K1
S1
K2
S2
K1
S4
S2
Y1
Y1
Y2
Y2
Y3
Y3
Y4
Y4
13
14
13
14
23
24
23
24
33
34
31
32
External Device Monitoring
To satisfy the requirements of Control Reliability (OSHA and ANSI), Category 3 and 4 of ISO 13849-1 (EN 954-1), the Machine
Primary Control Elements (MPCEs) must each offer a normally closed, forced-guided (mechanically linked) monitor contact. Connect
one normally closed monitor contact from each Machine Primary Control Element as shown in the appropriate hookup drawing (on
previous pages).
In operation, if one of the switching contacts of either MPCE fails in the energized condition, the associated monitor contact will
remain open. Therefore, it will not be possible to reset the Primary Safety Device. If no MPCE-monitor contacts are monitored, it is
the user's responsibility to ensure that any single failure will not result in a hazardous condition and will prevent a successive
machine cycle.
Overvoltage Category II and III Installations (EN 50178 and IEC 60664-1)
The Interface Module is rated for Overvoltage Category III when voltages of 1 V to 150 V AC/DC are applied to the output relay
contacts. It is rated for Overvoltage Category II when voltages of 151 V to 250 V AC/DC are applied to the output relay contacts and
no additional precautions are taken to attenuate possible overvoltage situations in the supply voltage. The Interface Module can be
used in an Overvoltage Category III environment (with voltages of 151 V to 250 V AC/DC) if care is taken either to reduce the level
of electrical disturbances seen by the Interface Module to Overvoltage Category II levels by installing surge suppressor devices (for
example, arc suppressors), or to install extra external insulation in order to isolate both the Interface Module and the user from the
higher voltage levels of a Category III environment.
For Overvoltage Category III installations with applied voltages from 151 V to 250 V AC/DC applied to the output contact(s):
the Interface Module may be used under the conditions of a higher overvoltage category where appropriate overvoltage reduction is
provided. Appropriate methods include:
• An overvoltage protective device
• A transformer with isolated windings
• A distribution system with multiple branch circuits (capable of diverting energy of surges)
• A capacitance capable of absorbing energy of surges
• A resistance or similar damping device capable of dissipating the energy of surges
When switching inductive AC loads, it is good practice to protect the Interface Module outputs by installing appropriately-sized arc
suppressors. However, if arc suppressors are used, they must be installed across the load being switched (for example, across the
coils of external safety relays), and never across the Interface Module’s output contacts (see WARNING, Arc Suppressors).
Auxiliary Monitor Contact (Model ..11A Only)
The action of the auxiliary monitor contact, terminals 31-32, inversely "follows" the action of the safety outputs. The 31-32 auxiliary
monitor contact is to be used only for control functions that are NOT safety-related. A typical use is to communicate the status of the
Interface Module output to a programmable logic controller (PLC).
Many types of mechanisms are used to arrest dangerous machine motion. Examples include mechanical braking systems, clutch
mechanisms, and combinations of brakes and clutches. Additionally, control of the arresting scheme may be hydraulic or pneumatic.
As a result, an MPCE may be one of several control types, including a wide variety of contactors and electromechanical valves. If
your machine documentation leaves any doubt about the proper connection points for the Interface Module output contacts, do not
make any connections. Contact the machine builder for clarification regarding connection to the MPCEs.
Two-Channel Control: Two-channel control allows the Primary Safety Device to detect an unsafe failure of the control wires. Twochannel control should be used whenever unsafe failure of the control wires cannot be eliminated.
P/N 62822 Rev. H
www.bannerengineering.com - Tel: + 1 888 373 6767
7
IM-T-9A and IM-T-11A Interface Module
The outputs of the primary safety device must at minimum, comply with the requirements described on page 5. These outputs must
be monitored for failure by the primary safety device. In addition, a single output failure cannot prevent normal stopping action, and a
successive cycle cannot be initiated until the failure has been corrected.
Note: NOTICE regarding MPCEs To achieve control reliability, two Machine Primary Control Elements (MPCEs)
are required to control each machine hazard. Each MPCE must be capable of immediately stopping the
dangerous machine motion, irrespective of the state of the other. Some machines offer only one primary control
element. For such machines, it is necessary to duplicate the circuit of the single MPCE to add a second MPCE.
MPCEs must offer at least one forced-guided auxiliary contact which is wired to the monitoring contact feedback
input of the primary safety device (see hookup diagrams).
WARNING: Interfacing MPCEs.
NEVER wire any intermediate device(s) (e.g., PLC, PES, PC), between the Interface Module outputs and the
Machine Primary Control Elements (MPCE1 to MPCE3) it switches, in such a manner that in the event of a
failure there is the loss of the safety stop command, OR in such a manner that the safety function can be
suspended, overridden, or defeated, unless accomplished with the same or greater degree of safety. Whenever
forced-guided, mechanically linked relays are added as intermediate switching devices, a normally closed
forced-guided monitor contact from each relay must be added to the series feedback loop between Interface
Module terminals Y1, Y2, Y3, and Y4.
Initial and Periodic Checkout Procedure
The Interface Module can be used safely only when its operation is controlled via an appropriate primary safety device, connected to
the Interface according to the wiring diagrams shown in the wiring diagrams.
CAUTION:
• Disconnect power prior to checkout
• Dangerous voltages might be present along the module wiring barriers whenever power to the machine
control elements is on.
• Before performing the initial checkout procedure, disconnect all power from the machine to be
controlled. Exercise extreme caution whenever machine control power is or might be present. Always
disconnect power to the machine control elements before opening the enclosure housing of the module.
The functioning of the Interface Module and the device(s) connected to it must be verified at initial installation and on a regular
periodic basis to ensure proper operation (see also the machine manufacturer's recommendations).
1. Remove the power controlling (and switched by) the machine control elements.
2. Verify the primary safety device that will be controlling the Interface Module is operating correctly, according to its product
documentation and manufacturer’s recommendations.
3. Confirm proper connection of the Interface Module to the controlling primary safety device according to the wiring diagram.
4. Verify all Interface Module output contacts follow exactly the operation of the safety output contacts of the controlling primary
safety device, when the primary safety device is operated according to its product documentation and manufacturer’s
recommendations.
Repairs
Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it contains no
field-replaceable parts or components. If the device, device part, or device component is determined to be defective by a Banner
Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization) procedure.
Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping is not
covered by warranty.
WARNING:
• Do not abuse the module after failure—If an internal fault has occurred and the module will not reset,
do not tap, strike, or otherwise attempt to correct the fault with a physical impact to the housing.
• Failure to follow these instructions could result in serious injury or death.
• An internal relay might have failed in such a manner that its replacement is required. If the module is not
immediately replaced or repaired, multiple simultaneous failures might accumulate such that the safety
function cannot be guaranteed.
8
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 62822 Rev. H
IM-T-9A and IM-T-11A Interface Module
Specifications
Input Voltage and Current
24 V DC, ±15% no polarity, 10% maximum ripple; 50 mA per input channel
(approximately 2.4 W)
Supply Protection Circuitry
Protected against transient voltages
Overvoltage Category
Output relay contact voltage of 1 V to 150 V AC/DC: Category III
Output relay contact voltage of 151 V to 250 V AC/DC: Category II (Category
III, if appropriate overvoltage reduction is provided)
Vibration Resistance
10 HZ to 55 Hz at 0.35 mm displacement per IEC 60068-2-6
Outputs
IM-T-9A: 3 normally open output channels
IM-T-11A: 2 normally open output channels and 1 normally closed auxiliary
output channel
Each normally open output channel is a series connection of contacts from
two forced-guided (mechanically linked) relays, K1-K2. The normally closed
contact 31-32 is a parallel connection of contacts from K1-K2.
Output Low Current Rating
The 5 μm gold-plated contacts allow the switching of low current/low voltage.
In these lowpower applications, multiple contacts can also be switched in
series (e.g., “dry switching”). To preserve the gold plating on the contacts, do
not exceed the following max. values at any time:
Min. voltage: 1 V AC/DC
Max. voltage: 60 V
Min. current: 5 mA AC/DC
Max. current: 300 mA
Min. power: 5 mW (5 mVA)
Max. power: 7 W (7 VA)
Output High Current Rating
If higher loads must be switched through one or more of the contacts, the
minimum and maximum values of the contact(s) changes to:
Minimum voltage: 15 V AC/DC
Maximum voltage: 250 V AC / 24 V DC, 6A resistive
Minimum current: 30 mA AC/DC
Minimum power: 0.45 W (0.45 VA)
Maximum power: 150 W (1,500 VA)
IEC 60947-5-1: AC-15: 230 V AC, 3A: DC-13: 24 V DC, 4 A
Pollution Degree
2
Status Indicators
Two green LED indicators: K1 energized, K2 energized
Construction
Polycarbonate housing rated NEMA 1, IEC IP20
Mounting
Mounts to standard 35 mm DIN-rail track. Interface Module must be installed
inside an enclosure rated NEMA 3 (IEC IP54), or better.
Application Notes
There are no adjustments and no user-serviceable parts. See Repairs for
information regarding repair service.
Contacts
AgNi, 5 μm gold-plated
Outputs Response Time
20 milliseconds maximum
Mechanical life
20,000,000 operations
Electrical life
150,000 cycles at 1,500 VA; 1,000,000 cycles at 450 VA; 2,000,000 cycles at
250 VA; 5,000,000 cycles at 125 VA
Feedback contact rating (Y1-Y2, Y3-Y4)
Minimum voltage: 1 V AC/DC
Maximum voltage: 60 V
Minimum current: 5 mA AC/DC
Maximum current: 300 mA
Minimum power: 5 mW (5 mVA)
Maximum power: 7 W (7 VA)
B10d Values
Voltage
Current
B10d
230 V AC
2A
350,000
230 V AC
1A
1,000,000
24 V DC
4A
2,000,000
24 V DC
≤2A
8,000,000
Note: Transient suppression is
recommended when switching inductive
loads. Install suppressors across load.
Never install suppressors across output
contacts (see Warning).
Operating Conditions
0 °C to +50 °C (+32 °F to +122 °F)
90% at +50 °C maximum relative humidity (non-condensing)
Certifications
Design Standards: EN 60947-1, EN 60947-5-1, EN 60068-2-6, EN
60068-2-27
P/N 62822 Rev. H
Required Overcurrent Protection
WARNING: Electrical connections must be
made by qualified personnel in accordance with
local and national electrical codes and
regulations.
Overcurrent protection is required to be provided by end product application
per the supplied table.
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
Supply Wiring (AWG)
Required Overcurrent Protection (Amps)
20
5.0
22
3.0
24
2.0
26
1.0
28
0.8
30
0.5
www.bannerengineering.com - Tel: + 1 888 373 6767
9
IM-T-9A and IM-T-11A Interface Module
Dimensions for IM-T-9A and IM-T-11A
Figure 9. Interface module dimensions
22.5 mm
(0.89")
118.0 mm
(4.65")
S1
13
S2
23
33
Y1
Y2
K1
84.0 mm
(3.31")
Machine
Safety
IM-T -9A
Ch.1
Ch.2
K2
Y4
Y3
14
24
S3
34
S4
Figure 10. Front label for model IM-T-9A
EC Declaration of Conformity (DoC)
Banner Engineering Corp. herewith declares that the IM-T-9A and IM-T-11A Interface Modules are in conformity with the provisions
of the Low Voltage Directive 2014/35/EU and all essential health and safety requirements have been met.
Representative in EU: Peter Mertens, Managing Director Banner Engineering Europe
Address: Park Lane, Culliganlaan 2F, 1831 Diegem, Belgium
Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or
replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not
cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR
TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO
BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL
DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY,
STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously
manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the
product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void
the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to:
www.bannerengineering.com.