ES-UA-5A and ES-VA-5A E-Stop Safety Module
Datasheet
Model ES-UA-5A for 12 to 24 V DC/115 AC operation; model ES-VA-5A for 12 to 24 V DC/230 AC operation
•
•
•
•
•
•
•
•
Monitors emergency stop devices, such as palm buttons and rope/cable pulls, and positiveopening safety switches used for guard/gate interlocking
The safety inputs can monitor:
◦ Hard/relay contacts in a dual-channel hookup using terminals S11-S12 and S21S22, or
◦ A +24 V DC source switched by hard/relay contacts in single-channel hookup
Four normally open output switching channels for connection to control-reliable power
interrupt circuits and three auxiliary output channels
Automatic reset or monitored manual reset
Design complies with standards ANSI B11.19, UL991, ISO 13850 (EN418), and ISO
13849-1 (EN954-1) (Safety Category 4)
For use in functional stop category 0 applications per ANSI NFPA 79 and IEC/EN60204-1
6 amp safety output contacts; 5 amp aux. output contacts
Plug-in terminal blocks
Models
Supply Voltage
Outputs
Output Rating
ES-UA-5A
12 to 24 V DC or 115 V AC
4 Normally open safety
N.O. Safety Outputs: 6 A
1 Normally closed aux.
N.C. Aux. Outputs: 5 A
2 Solid-state aux.
SS Aux. Outputs: 100 mA
ES-VA-5A
12 to 24 V DC or 230 V AC
WARNING:
• Not a stand-alone safeguarding device
• Failure to properly safeguard hazards according to a risk assessment, local regulations, and applicable
standards might lead to serious injury or death.
• This Banner Engineering Corp device is considered complementary equipment that is used to augment
safeguarding that limits or eliminates an individual's exposure to a hazard without action by the
individual or others.
Important: Read This First
The user is responsible for satisfying all local, state, and national laws, rules, codes, and regulations relating to the use of this
product and its application. Banner Engineering Corp. has made every effort to provide complete application, installation, operation,
and maintenance instructions. Please contact a Banner Applications Engineer with any questions regarding this product.
The user is responsible for making sure that all machine operators, maintenance personnel, electricians, and supervisors are
thoroughly familiar with and understand all instructions regarding the installation, maintenance, and use of this product, and with the
machinery it controls. The user and any personnel involved with the installation and use of this product must be thoroughly familiar
with all applicable standards, some of which are listed within the specifications. Banner Engineering Corp. makes no claim regarding
a specific recommendation of any organization, the accuracy or effectiveness of any information provided, or the appropriateness of
the provided information for a specific application.
Applicable U.S. Standards
ANSI B11 Standards for Machine Tools Safety
ANSI B11.19 Performance Criteria for Safeguarding
Contact: Safety Director, AMT – The Association for Manufacturing Technology, 7901 Jones Branch Drive, Suite 900, McLean, VA
22102-4206 USA, www.amtonline.org
NFPA 79 Electrical Standard for Industrial Machinery
Contact: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471 USA, www.nfpa.org/
ANSI/RIA R15.06 Safety Requirements for Industrial Robots and Robot Systems
Contact: Robotic Industries Association, 900 Victors Way, Suite 140, Ann Arbor, MI 48108 USA, www.robotics.org
Applicable International Standards
EN ISO 12100 Safety of Machinery – Basic Concepts, General Principles for Design
EN 60204-1 Electrical Equipment of Machines Part 1: General Requirements
IEC 61508 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems
Original Document
122365 Rev. G
10 August 2021
122365
ES-UA-5A and ES-VA-5A E-Stop Safety Module
IEC 62061 Functional Safety of Safety-Related Electrical, Electronic and Programmable Control Systems
EN ISO 13849-1 Safety-Related Parts of Control Systems
ISO 13850 (EN 418) Emergency Stop Devices, Functional Aspects – Principles for Design
Contact: IHS Markit (Global Engineering Documents), 15 Inverness Way East, Englewood, CO 80112 USA, https://global.ihs.com/
Overview
An Emergency Stop Safety Module is used to increase the control
reliability of an emergency stop circuit. As shown in the wiring
drawings, the models ES-UA-5A and ES-VA-5A E-Stop Safety
Modules (the Safety Modules) are designed to monitor a 1-channel
or 2-channel E-stop switch. A 2-channel E-stop switch has two
electrically isolated contacts.
Figure 1. Features and Terminals
S31 S32 S33
A1
A2
B1
B2
13
14
23
24
Y30 Y31 Y32
S34 S32 S35
S11 S12 S21 S22
33
34
Y35
43
51
44
52
Safety Circuit Integrity and EN ISO 13849-1 Safety Circuit Principles
Safety circuits involve the safety-related functions of a machine that minimize the level of risk of harm. These safety-related functions
can prevent initiation, or they can stop or remove a hazard. The failure of a safety-related function or its associated safety circuit
usually results in an increased risk of harm.
The integrity of a safety circuit depends on several factors, including fault tolerance, risk reduction, reliable and well-tried
components, well-tried safety principles, and other design considerations.
Depending on the level of risk associated with the machine or its operation, an appropriate level of safety circuit integrity
(performance) must be incorporated into its design. Standards that detail safety performance levels include ANSI B11.19
Performance Criteria for Safeguarding and EN ISO 13849-1 Safety-Related Parts of a Control System.
Safety Circuit Integrity Levels
The safety circuits in International and European standards have been segmented into categories, depending on their ability to
maintain their integrity in the event of a failure. The most recognized standard that details safety circuit integrity levels is ISO
13849-1 (EN954-1), which establishes five levels: Categories B, 1, 2, 3, and 4 (most strict).
In the United States, the typical level of safety circuit integrity is called control reliability. Control reliability typically incorporates
redundant control and self-checking circuitry and is relatively similar to ISO 13849-1 Categories 3 and 4 (see CSA Z432 and ANSI
B11.19).
Perform a risk assessment to determine the appropriate category to make sure that the expected risk reduction is achieved to
implement the requirements described by ISO 13849-1. This risk assessment must also take into account the national regulations,
such as U.S. control reliability or European "C" level standards, to comply with the mandated minimum levels of performance.
WARNING:
• Determine the safety category
• The design and installation of the safety devices and the means of interfacing of those devices could
greatly affect the level of safety circuit integrity.
• Perform a risk assessment to determine the appropriate safety circuit integrity level or safety category,
as described by ISO 13849-1, to ensure that the expected risk reduction is achieved and that all
applicable regulations and standards are met.
2
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 122365 Rev. G
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Fault Exclusion
An important concept within the category requirements of EN ISO 13849-1 is the probability of the occurrence of the failure, which
can be decreased using the "fault exclusion" method. This method assumes that the possibility of certain well-defined failure(s) can
be reduced to a point where the resulting fault(s) can be disregarded.
Fault exclusion is a tool a designer can use during the development of the safety-related part of the control system and the risk
assessment process. It allows the designer to eliminate the possibility of various failures and justify it through the risk assessment
process to meet the requirements of Categories 2, 3, or 4. See EN ISO 13849-1/-2 for further information.
Monitoring of Safety Devices
Requirements vary widely for the level of control reliability or safety category per ISO 13849-1 (EN954-1) in safety applications.
While Banner Engineering always recommends the highest level of safety in any application, it is the responsibility of the user to
safely install, operate and maintain each safety system and comply with all relevant laws and regulations.
Although only a few applications are listed, the Module can monitor a variety of devices as long as the input requirements are
complied with (see Electrical Installation and Specifications). The Safety Module does not have 500 ms simultaneity between inputs
and thus cannot be used for monitoring a two-hand control. In all cases, the safety performance (integrity) must reduce the risk from
identified hazards as determined by the machine's risk assessment.
WARNING:
• Do not mute or bypass any emergency stop device
• Muting or bypassing the safety outputs renders the emergency stop function ineffective.
• ANSI B11.19, NFPA 79 and IEC/EN 60204-1 require that the emergency stop function remains active at
all times.
Emergency Stop Push Buttons and Rope/Cable Pull Switches
The safety inputs can be interfaced with positive-opening switches to monitor an emergency-stop (E-stop) push button or rope/cable
pull. The switch must provide one or two contacts for safety which are closed when the switch is armed. Once activated, the E-stop
switch must open all its safety-rated contacts, and must require a deliberate action (such as twisting, pulling, or unlocking) to return
to the closed-contact, armed position. The switch must be a "positive-opening" (or direct-opening) type, as described by IEC
60947-5-1.
Standards ANSI NFPA 79, ANSI B11.19,, IEC/EN60204-1, and ISO 13850 specify additional emergency stop switch device
requirements, including the following:
• Emergency-stop push buttons shall be located at each operator control station and at other operating stations where
emergency shutdown is required.
• Stop and emergency-stop push buttons shall be continuously operable and readily accessible from all control and operating
stations where located. Do not mute or bypass E-stop buttons or rope/cable pulls.
• Actuators of emergency-stop devices shall be colored red. The background immediately around the device actuator shall be
colored yellow (where possible). The actuator of a push-button-operated device shall be of the palm or mushroom-head
type.
• The emergency-stop actuator shall be a self-latching type.
In addition, for Rope/Cable Pull Installations Only:
• The wire rope should be easily visible and readily accessible along its entire length. Red markers or flags may be fixed on
the rope to increase its visibility.
• The rope or cable pull must provide constant tension and must have the capability to react to a force in any direction.
• Mounting points, including support points, must be rigid.
• The rope should be free of friction at all supports. Pulleys are recommended.
• The switch must have a self-latching function that requires a manual reset after actuation
Some applications may have additional requirements; comply with all relevant regulations. See the device manufacturer installation
instructions for complete information (such as SSA-EB1..-.. p/n 162275, or RP-RM83F.. p/n 141245 datasheets).
WARNING:
• Do not mute or bypass any emergency stop device
• Muting or bypassing the safety outputs renders the emergency stop function ineffective.
• ANSI B11.19, NFPA 79 and IEC/EN 60204-1 require that the emergency stop function remains active at
all times.
Interlocked Guards (Gates)
The safety inputs can be interfaced with positive-opening safety switches to monitor the position of an interlock guard or gate. Each
switch must provide electrically isolated contacts: at minimum, one normally closed (N.C.) contact from each individually mounted
switch. The contacts must be of "positive-opening" (direct-opening) design, as described by IEC60947- 5-1, with one or more
normally closed contacts rated for safety. In addition, the switches must be mounted in a "positive mode," to move/disengage the
actuator from its home position and open the normally closed contact when the guard opens.
The design and installation of the interlocked guard and the safety switches should comply with ANSI B11.19, ISO14119, ISO
14120, and/or other applicable standards. See the device manufacturer installation instructions for complete information (such as
GM-FA-10J p/n 60998, SI-LS83/-LS100 p/n 59622, or SI-HG63 p/n 129465 datasheets).
P/N 122365 Rev. G
www.bannerengineering.com - Tel: + 1 888 373 6767
3
ES-UA-5A and ES-VA-5A E-Stop Safety Module
In higher levels of safety performance, the design of a dual-channel coded magnetic switch typically uses complementary switching,
in which one channel is open and one channel is closed at all times. The inputs of the Safety Module do not support
complementary switching, and thus should not be used with coded magnetic safety switches.
Mechanical Installation
The ES-xA-5A E-Stop Safety Module must be installed inside an enclosure.
It is not designed for exposed wiring. It is the user’s responsibility to house the ES-xA-5A E-Stop Safety Module in an enclosure with
NEMA 3 (IEC IP54) rating, or better. The ES-xA-5A E-Stop Safety Module mounts directly to standard 35 mm DIN rail.
Heat Dissipation Considerations: For reliable operation, ensure that the operating specifications are not exceeded. The enclosure
must provide adequate heat dissipation, so that the air closely surrounding the ES-xA-5A E-Stop Safety Module does not exceed the
maximum operating temperature stated in the Specifications. Methods to reduce heat build-up include venting, forced airflow (for
example, exhaust fans), adequate enclosure exterior surface area, and spacing between modules and other sources of heat.
Electrical Installation
WARNING:
• Risk of electric shock
• Use extreme caution to avoid electrical shock. Serious injury or death could result.
• Always disconnect power from the safety system (for example, device, module, interfacing, etc.),
guarded machine, and/or the machine being controlled before making any connections or replacing any
component. Lockout/tagout procedures might be required. Refer to OSHA 29CFR1910.147, ANSI
Z244-1, or the applicable standard for controlling hazardous energy.
• Make no more connections to the device or system than are described in this manual. Electrical
installation and wiring must be made by a Qualified Person 1 and must comply with the applicable
electrical standards and wiring codes, such as the NEC (National Electrical Code), NFPA 79, or IEC
60204-1, and all applicable local standards and codes.
It is not possible to give exact wiring instructions for a Safety Module that interfaces to a multitude of machine control configurations.
The following guidelines are general in nature.
The Safety Module has no delay function. Its output relay contacts open within 25 milliseconds after a safety input opens. This
classifies the Safety Module as a functional stop "Category 0" control, as defined by ANSI NFPA 79 and IEC/EN 60204-1.
The Safety Module is powered by either a 12-24 V DC supply at 4 W or an AC supply (115 V AC, model ES-UA-5A, or 230 V AC,
model ES-VA-5A) at 7 VA. The safety inputs can be connected to:
•
•
A +24 V DC source that is switched by a hard/relay contact in single-channel hookup configuration, or
Hard/relay contacts in a dual-channel wiring configuration using terminals S11-S12 and S21-S22.
Safety Input Device Wiring Options
The operation of all dual-channel wiring options is concurrent, meaning that input channel 1 and input channel 2 must be in the same
state in both the STOP and RUN condition, but with no simultaneity (timing) requirement between the channels.
The dual-channel wiring configuration is able to detect certain failures and faults, such as short circuits, that could result in a loss
of the safety function. Once such a failure or fault is detected, the Safety Module will turn OFF (open) its safety outputs until the
problem is fixed. This circuit can meet ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the
installation of the safety input device. This circuit can detect a short circuit between channels or to another source of power, at a
minimum, when the device is actuated.
A single device with redundant outputs that can fail in such a manner to lose the safety function, such as a single safety interlocking
switch, can typically meet only a Category 2. See below for means to eliminate or minimize the possibility of failures and faults that
could result in the loss of the safety function(s).
The single-channel wiring configuration cannot detect short circuits to secondary sources of +24 V DC or detect the loss of the
switching function of the safety input device (that is, it is not redundant) and thus this circuit typically can meet only ISO 13849-1
Category 2.
It is recommended that in all circumstances the installation of the Safety Module and its associated safety input devices are installed
to eliminate or minimize the possibility of failures and faults that could result in the loss of the safety function(s). Methods to eliminate
or minimize the possibility of these failures include, but are not limited to:
• Physically separating interconnecting control wires from each other and from secondary sources of power.
• Routing interconnecting control wires in separate conduit, runs, or channels.
• Locating all elements (modules, switches, and devices under control) within one control panel, adjacent to each other, and
directly connected with short wires.
• Properly installing multi-conductor cabling and multiple wires through strain-relief fittings. (Over-tightening of a strain-relief
can cause short circuits at that point.)
• Using positive-opening components as described by IEC 60947-5-1 that are installed and mounted in a positive mode.
1
4
A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and experience, has
successfully demonstrated the ability to solve problems relating to the subject matter and work.
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 122365 Rev. G
ES-UA-5A and ES-VA-5A E-Stop Safety Module
•
Periodically checking the functional integrity / safety function and training operators, maintenance personnel, and others
associated with the operation of the machine to recognize and immediately correct such failures.
If you have any questions about your intended use, please contact a Banner applications engineer.
Connection of Multiple Switches
Connect the poles of multiple switches, such as E-Stop switches, as shown in the following hookup figures. The switches are shown
in the "armed" position with both contacts closed. Multiple switches connected to one Safety Module must be series connected.
Figure 2. Series connection of multiple E-stop switches
E-Stop
S11
S21
E-Stop
S22
S12
WARNING:
• Test multiple safety devices individually
• Failure to test each safety device individually could result in undetected faults and create an unsafe
condition that could result in serious injury or death.
• When two or more safety devices are used, individually actuate each device, causing a stop or opencontact condition, then reset/rearm the safety module (if using manual reset mode). This allows the
monitoring circuits to check each device and its wiring to detect faults.
Note: The minimum amount of time for the Module to detect a STOP condition is 15 milliseconds. This "recovery
time" (OFF state) is required for the internal integrity tests to complete, allowing a reliable reset to occur. A
lockout may occur if the Module is cycled too quickly. To clear the lockout, the inputs must be re-cycled, meeting
the minimum recovery time requirements.
Connection of Safety Switches
The Safety Module may be used to monitor safety interlocking
switches that determine the position of a guard or gate. To achieve
Category 4 operation per ISO 13849-1 (EN 954-1), two positiveopening safety switches must operate concurrently when the guard
or gate is opened.
The Safety Module verifies concurrent opening of two contacts –
one from each safety switch. Reset of the Safety Module is not
possible if one switch fails to open or if a short circuit between the
safety interlocking switches occurs.
Figure 3. Wiring using contacts from two safety switches
S11
P/N 122365 Rev. G
Safety Gate or Guard with
end-of-travel stops and two
individually mounted
Safety Interlocking Switches
OPEN
www.bannerengineering.com - Tel: + 1 888 373 6767
S21
S22
S12
5
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Connection of Reset Switch
The reset circuit switch can be any mechanical switch, such as a normally open momentary switch, or a two-position key switch. The
reset switch must be capable of reliably switching 12 to 30 V DC at 20 to 50 milliamps. As shown in the wiring diagrams, the reset
switch connects between Safety Module terminals S33 and S34.
The reset switch must be located outside of – and not be accessible from – the area of dangerous motion, and must be positioned
so that any area of dangerous motion may be observed by the switch operator during the reset procedure. See warning below.
WARNING:
• Install reset switches properly
• Failure to properly install reset switches could result in serious injury or death.
• Install reset switches so that they are accessible only from outside, and in full view of, the safeguarded
space. Reset switches cannot be accessible from within the safeguarded space. Protect reset switches
against unauthorized or inadvertent operation (for example, through the use of rings or guards). If there
are any hazardous areas that are not visible from the reset switches, provide additional safeguarding.
Automatic Reset Mode
The Safety Module may be configured (via hookup) for automatic reset. Leave terminals S33 and S34 open and install a jumper
between terminals S32 and S35 (see hookups). The Safety Module will reset (and its outputs energize) as soon as the switch
returns to its armed (closed-contact) position.
Automatic reset is useful for some automated processes. However, if automatic reset is used, it is necessary to provide a
means of preventing resumption of hazardous machine motion, until an alternate reset procedure is performed. The
alternate procedure must include a reset/restart switch, located outside the area of dangerous motion and positioned so that any
area of dangerous motion may be observed by the switch operator during the reset procedure.
WARNING:
• Reset routine required
• Failure to prevent the machine from restarting without actuating the normal start command/device can
create an unsafe condition that could result in serious injury or death.
• Do not allow the machine to restart without actuating the normal start command/device. Perform the
reset routine after clearing the cause of a stop condition, as required by U.S. and international
standards.
Connection to the Machine to be Controlled
The machine hookup diagram shows a generic connection of the Safety Module's redundant output circuits to the master stop
control elements (MSCs). An MSC is defined as an electrically powered device, external to the Safety Module, which stops the
machinery being controlled by immediately removing electrical power to the machine and (when necessary) by applying braking to
dangerous motion. This stopping action is accomplished by removing power to the actuator of either MSC.
External Device Monitoring
To satisfy the requirements of Control Reliability (OSHA and ANSI), Category 3 and 4 of ISO 13849-1 (EN 954-1), the Machine
Primary Control Elements (MPCEs) must each offer a normally closed, forced-guided (mechanically linked) monitor contact. Connect
one normally closed monitor contact from each Machine Primary Control Element as shown in the appropriate hookup drawing
(circuit between terminals S31 and S32, jumper if no MSC contacts are monitored).
In operation, if one of the switching contacts of either MPCE fails in the energized condition, the associated monitor contact will
remain open. Therefore, it will not be possible to reset the Primary Safety Device. If no MPCE-monitor contacts are monitored, it is
the user's responsibility to ensure that any single failure will not result in a hazardous condition and will prevent a successive
machine cycle.
6
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 122365 Rev. G
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Wiring Drawings
Figure 4. Wiring for 2-Channel E-Stop Applications
Auto Reset
Manual Reset
AC Power shown
DC Power shown
dc
common
+V
115 ac or 230V ac
(depending on model)
A1
12-24V dc
ES-UA-5A
A2
ES-VA-5A
B2
AC or DC power
connections shown
are valid for either
auto or manual reset.
115V ac
B1
A1
ES-UA-5A
A2
ES-VA-5A
B2
12-24V dc
B1
230V ac
12-24V dc
E-Stop Switch
E-Stop Switch
S11
S11
S21
S21
MSC1 MSC3
S22
MSC1 MSC3
S22
S31
S12
S34
S31
MSC Monitor
Contacts
or Jumper for No
Monitoring S32
Reset Switch
MSC Monitor
Contacts
or Jumper for No
Monitoring S32
S12
S34
MSC2 MSC4
S33
MSC2 MSC4
S33
Jumper
S32
S32
Jumper
Machine
Master Stop
Control Elements
S35
6A max.
L1
K1A
K2B
23
24
34
33
43
Non-safety
Auxiliary Monitor
Contact
44
K1E
*
34
Arc Suppressors
(see WARNING )
Non-safety
Auxiliary Monitor
Contact
44
K1E
P/N 122365 Rev. G
*
52
*
Arc Suppressors
(see WARNING )
K2E
Y30
100 mA max.
each Output
Non-safety
Monitor Outputs
Y35
Y32
Power Supply
Fault
Outputs
Energized
12-24V dc
+V
MSC4
5A max.
51
Y31
100 mA max.
each Output
Non-safety
Monitor Outputs
Y32
*
K2D
43
Y30
Outputs
Energized
MSC3
6A max.
K2E
Y31
*
K2C
K1D
*
52
MSC2
6A max.
K1C
33
MSC4
5A max.
51
24
*
K2D
K2B
23
MSC3
6A max.
K1D
*
6A max.
Machine
Control
Circuits
L2
MSC1
14
K1B
*
K2C
K2A
13
MSC2
6A max.
K1C
K1A
*
6A max.
K1B
6A max.
L1
MSC1
14
Machine
Control
Circuits
L2
K2A
13
Machine
Master Stop
Control Elements
S35
Y35
Power Supply
Fault
12-24V dc
dc common
+V
www.bannerengineering.com - Tel: + 1 888 373 6767
dc common
7
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Figure 5. Wiring for 1-Channel E-Stop Applications
Auto Reset
Manual Reset
AC Power shown
DC Power shown
+V
115V ac or 230V ac
(depending on model)
dc
common
12-24V dc
E-Stop
Switch
A1
ES-UA-5A
A2
ES-VA-5A
B2
E-Stop
Switch
AC or DC power
connections shown
are valid for either
auto or manual reset.
115V ac
B1
230V ac
A1
ES-UA-5A
A2
ES-VA-5A
B2
12-24V dc
B1
12-24V dc
ES-UA-5A
12-24V dc/115V ac
ES-VA-5A
S11
12-24V dc/230V ac
ES-UA-5A
12-24V dc/115V ac
ES-VA-5A
S11
12-24V dc/230V ac
S21
S21
MSC1 MSC3
S22
MSC1 MSC3
S22
S31
S31
MSC Monitor
Contacts
or Jumper for
No Monitoring S32
S12
S34
Reset Switch
MSC Monitor
Contacts
or Jumper for
No Monitoring S32
S12
S34
MSC2 MSC4
S33
MSC2 MSC4
S33
Jumper
S32
S32
Jumper
Machine
Master Stop
Control Elements
S35
6A max.
L1
K1A
K2A
13
K2B
24
23
Machine
Control
Circuits
34
43
Non-safety
Auxiliary Monitor
Contact
44
K1E
24
*
Arc Suppressors
(see WARNING )
Non-safety
Auxiliary Monitor
Contact
44
K1E
8
*
52
*
Arc Suppressors
(see WARNING )
K2E
Y30
100 mA max.
each Output
Non-safety
Monitor Outputs
Y35
Y32
Power Supply
Fault
Outputs
Energized
12-24V dc
+V
MSC4
5A max.
51
Y31
100 mA max.
each Output
Non-safety
Monitor Outputs
Y32
*
K2D
43
Y30
Outputs
Energized
MSC3
6A max.
K2E
Y31
*
K2C
34
K1D
*
52
MSC2
6A max.
K1C
33
MSC4
5A max.
51
K2B
23
Machine
Control
Circuits
*
K2D
*
6A max.
MSC3
6A max.
K1D
MSC1
14
K1B
L2
K2A
13
*
K2C
33
K1A
MSC2
6A max.
K1C
6A max.
L1
*
6A max.
K1B
L2
MSC1
14
Machine
Master Stop
Control Elements
S35
Y35
Power Supply
Fault
12-24V dc
dc common
+V
www.bannerengineering.com - Tel: + 1 888 373 6767
dc common
P/N 122365 Rev. G
ES-UA-5A and ES-VA-5A E-Stop Safety Module
WARNING:
• Properly install arc or transient suppressors
• Failure to follow these instructions could result in serious injury or death.
• Install any suppressors as shown across the coils of the machine primary control elements. Do not
install suppressors directly across the output contacts of the safety or interface module. In such a
configuration, it is possible for suppressors to fail as a short circuit.
WARNING:
• Interfacing master stop controls
• Failure to follow these instructions could result in serious injury or death.
• Unless the same degree of safety is maintained, never wire an intermediate device(s) (PLC, PES, PC)
between the safety module outputs and the master stop control element it switches such that a failure
causes a loss of the safety stop command or the failure allows the safety function to be suspended,
overridden, or defeated.
• When forced-guided, mechanically linked relays are added as intermediate switching devices, a
normally closed (N.C.) forced-guided monitor contact from each relay must be added to the series
feedback loop or properly wired external device monitoring channel.
Overvoltage Category II and III Installations (EN 50178 and IEC 60664-1)
The ES-xA-5A E-Stop Safety Module is rated for Overvoltage Category III when voltages of 1 V to 150 V AC/DC are applied to the
output relay contacts. It is rated for Overvoltage Category II when voltages of 151 V to 250 V AC/DC are applied to the output relay
contacts and no additional precautions are taken to attenuate possible overvoltage situations in the supply voltage. The ES-xA-5A EStop Safety Module can be used in an Overvoltage Category III environment (with voltages of 151 V to 250 V AC/DC) if care is taken
either to reduce the level of electrical disturbances seen by the ES-xA-5A E-Stop Safety Module to Overvoltage Category II levels by
installing surge suppressor devices (for example, arc suppressors), or to install extra external insulation in order to isolate both the
ES-xA-5A E-Stop Safety Module and the user from the higher voltage levels of a Category III environment.
For Overvoltage Category III installations with applied voltages from 151 V to 250 V AC/DC applied to the output contact(s):
the ES-xA-5A E-Stop Safety Module may be used under the conditions of a higher overvoltage category where appropriate
overvoltage reduction is provided. Appropriate methods include:
• An overvoltage protective device
• A transformer with isolated windings
• A distribution system with multiple branch circuits (capable of diverting energy of surges)
• A capacitance capable of absorbing energy of surges
• A resistance or similar damping device capable of dissipating the energy of surges
When switching inductive AC loads, it is good practice to protect the ES-xA-5A E-Stop Safety Module outputs by installing
appropriately-sized arc suppressors. However, if arc suppressors are used, they must be installed across the load being switched
(for example, across the coils of external safety relays), and never across the ES-xA-5A E-Stop Safety Module’s output contacts.
Auxiliary Monitor Contact/Solid-State Monitor Outputs Connection
The action of the auxiliary monitor contact, terminals 51-52, inversely "follows" the action of the safety outputs. Two additional solidstate monitor outputs (at terminals Y32 and Y35) each are capable of switching up to 100 mA at 12- 24 V dc. The output at terminal
Y32 follows the action of the output circuits (K1 and K2); the output at terminal Y35 opens (low signal) when there is a loss of power
or a fault is detected. These outputs are to be used only for nonsafety functions (typically, to communicate the status of the
Safety Module to a programmable logic controller). See the appropriate figure for wiring information.
Initial Checkout Procedure
CAUTION:
• Disconnect power prior to checkout
• Dangerous voltages might be present along the module wiring barriers whenever power to the machine
control elements is on.
• Before performing the initial checkout procedure, disconnect all power from the machine to be
controlled. Exercise extreme caution whenever machine control power is or might be present. Always
disconnect power to the machine control elements before opening the enclosure housing of the module.
1. Remove power from the machine primary control elements.
2. Ensure the safety device is in a STOP or "open-contact" state (for example, actuate the E-stop switch to open its contacts).
3. Apply power to the Safety Module at terminals A1 and A2 or B1 and B2.Verify that only the Input Power indicator is ON. If
either input channel 1 or input channel 2 indicators are ON at this point, disconnect the input power and check all wiring.
Return to step 2 after the cause of the problem has been corrected.
4. Reset or otherwise cause the safety device to reach an ON or "closed-contact" state (for example, arm the E-stop switch to
close its contacts).
5. Manual Reset mode: Ch1 and Ch2 indicators should be flashing. Close and reopen the Reset switch.
6. Verify that the Ch1 and Ch2 indicators both come ON. If only one indicator comes ON or if any indicator is flashing, refer to
the Troubleshooting section for more information. Return to step 2 after correcting the problem.
P/N 122365 Rev. G
www.bannerengineering.com - Tel: + 1 888 373 6767
9
ES-UA-5A and ES-VA-5A E-Stop Safety Module
7. Cause the safety device to generate a STOP or "open-contact" state (for example, actuate the E-stop switch to open its
contacts). The Ch1 and Ch2 indicators should turn OFF simultaneously. If either indicator remains ON, disconnect the input
power and check all wiring. Return to step 2 after the cause of the problem has been corrected. Refer to the Troubleshooting
section for more information.
8. If more than one safety device is series-connected to the Safety Module, run the above checkout procedure individually for
EACH device.
9. Close and secure the enclosure in which the Safety Module is mounted. Apply power to the machine control elements and
perform the Periodic Checkout Procedure.
WARNING:
• Test multiple safety devices individually
• Failure to test each safety device individually could result in undetected faults and create an unsafe
condition that could result in serious injury or death.
• When two or more safety devices are used, individually actuate each device, causing a stop or opencontact condition, then reset/rearm the safety module (if using manual reset mode). This allows the
monitoring circuits to check each device and its wiring to detect faults.
Specifications
Supply Voltage and Current
AI-A2: 115 V AC (model ES-UA-5A) or 230 V ac (model ES-VA-5A) ±15% ,
50/60 Hz
BI-B2: 11 V DC to 27.6 V DC
Power consumption: approx. 4 W/7 VA
The Safety Module should be connected only to a SELV (safety extra-low
voltage, for circuits without earth ground) or a PELV (protected extra-low voltage,
for circuits with earth ground) power supply.
Supply Protection Circuitry
Protected against transient voltages and reverse polarity
Overvoltage Category
Output relay contact voltage of 1 V to 150 V AC/DC: category III
Output relay contact voltage of 151 V to 250 V AC/DC: category III, if
appropriate overvoltage reduction is provided (see Overvoltage Category III
Installations).
Pollution Degree
2
Required Overcurrent Protection
WARNING: Electrical connections must be
made by qualified personnel in accordance with
local and national electrical codes and
regulations.
Overcurrent protection is required to be provided by end product application
per the supplied table.
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
Required Overcurrent Protection (Amps)
Supply Wiring (AWG)
20
5.0
22
3.0
24
2.0
26
1.0
28
0.8
30
0.5
Relay Outputs
Relay Outputs
4 normally open (N.O.) output channels and 1 normally closed (N.C.)
auxiliary output
Contacts: AgNi, 5 μm gold-plated
Each normally open output channel is a series connection of contacts from two forcedguided (mechanically linked) relays, K1-K2. The normally closed Aux. output channel is
a parallel connection of contacts from two forced-guided relays, K1-K2.
Low Current Rating: The 5 μm gold-plated contacts allow the switching of low current/low voltage. In these low-power applications, multiple contacts can also be
switched in series (for example, “dry switching”). To preserve the gold plating on the contacts, do not exceed the following max. values at any time:
Min.
Max.
Voltage
1 V AC/DC
60 V
Current
5 mA AC/DC
300 mA
Power
5 mW (5 mVA)
7 W (7 VA)
10
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 122365 Rev. G
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Relay Outputs
High Current Rating: If higher loads must be switched through one or more of the contacts, the minimum and maximum values of the contact(s) changes to:
Minimum
Maximum
Voltage
15 V AC/DC
Current
250 mA AC/DC
Power
5 W (5 VA)
N.O. Safety Contacts (13-14, 23-24, 33-34, 43-44): 250 V AC / 24
V DC, 6 A resistive
B300, Q300 (UL508)
N.C. Auxiliary Contact (51-52): 250 V AC/ 24 V DC, 5 A resistive
B300, Q300 (UL508)
Minimum
Maximum — IEC60947-5-1
Voltage
15V AC/DC
Current
250 mA AC/DC
Power
5 W (5 VA)
N.O. Safety Contacts:
AC-1: 250 V AC, 6 A; DC-1: 24 V DC, 6 A
AC-15: 230 V AC, 3 A; DC-13: 24 V DC, 4 A
N.C. Auxiliary Contact:
AC-1: 250 V AC, 5 A; DC-1: 24 V DC, 5 A
AC-15: 230 V AC, 2 A; DC-13: 24 V DC, 4 A
Mechanical Life
> 50,000,000 operations
Note: Transient suppression is recommended
when switching inductive loads. Install
suppressors across load. Never install
suppressors across output contacts (see
Warning, Wiring of Arc Suppressors).
Electrical Life
150,000 cycles at 1500 VA
1,000,000 cycles at 450 VA
2,000,000 cycles at 250 VA
5,000,000 cycles at 125 VA
Solid-State Outputs
Two non-safety solid-state DC outputs
Output circuits require application of +12 to 24 V DC ± 15% at terminal Y31;
dc common at Y30.
Max. switching current: 100 mA at 12 to 24 V DC
Output Response Time
35 ms max. (25 ms typical)
Both outputs are protected against short circuits.
Output at Y32 monitors state of outputs – conducts (output high) when both K1
and K2 are energized.
Output at Y35 conducts (output high) when in normal operation (no lockout).
I/O
General
Input Requirements
E-stop switch: must have normally closed contacts each capable of switching
20 to 50 mA at 12 to 30 V DC; and must be open longer than 15 ms for a
valid stop command.
Maximum input resistance 250 ohms per channel at 24 V DC supply voltage.
Maximum input resistance 25 ohms per channel at 12 V DC supply voltage.
Reset switch: must have one normally open contact capable of switching 20
to 50 mA at 12 to 30 V DC.
Indicators
3 green LED indicators: Power ON , Channel 1, Channel 2
1 red LED indicator: indicates a fault condition (see Troubleshooting)
OFF-State Recovery Time
350 ms maximum
Construction
Polycarbonate housing. Rated NEMA 1, IEC IP20
Mounting
Mounts to standard 35 mm DIN rail track. Safety Module must be installed
inside an enclosure rated NEMA 3 (IEC IP54), or better.
Operating Conditions
Standards and Certifications
Vibration Resistance
10 to 60 Hz at 0.35 mm peak displacement per UL 991
60 to 150 Hz at 5 g max.
Design Standards
Cat. 4 PL e per EN ISO 13849-1; SIL 3 per IEC 61508 and IEC 62061
Environment
Temperature: 0 °C to +50 °C (+32 °F to +122 °F), (surrounding air)
90% at +50 °C maximum relative humidity (non-condensing)
P/N 122365 Rev. G
www.bannerengineering.com - Tel: + 1 888 373 6767
11
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Dimensions
84 mm
(3.3")
118.0 mm
(4.6")
45 mm
(1.8")
All measurements are listed in millimeters [inches], unless noted otherwise.
Product Support and Maintenance
Troubleshooting
Module will not reset
Indicator Status
Possible Causes and Solutions
Power LED ON
Fault LED OFF
Ch1 LED Flashing
Ch2 LED Flashing
Waiting for manual reset:
• EDM monitoring contacts are not closed. Check MSCs.
• Check jumper at S32-S35 (auto reset) or S32-S33 (manual reset).
• Check reset button connection.
No Fault Indicated
Indicator Status
Possible Causes and Solutions
Power LED ON
Fault LED OFF
Ch1 LED OFF
Ch2 LED OFF
E-stop button open:
• Connector loose.
• Re-arm E-stop button.
Power LED ON
Fault LED OFF
Ch1 LED OFF
Ch2 LED ON
Ch.1 open; Ch. 2 closed:
• Check wiring to S11-S12.
• Check switch.
• Check connectors are properly seated.
Power LED ON
Fault LED OFF
Ch1 LED ON
Ch2 LED OFF
Ch.1 closed; Ch. 2 open:
• Check wiring to S21-S22.
• Check switch.
• Check connectors are properly seated.
12
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 122365 Rev. G
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Fault
Indicator Status
Possible Causes and Solutions
Power LED ON
Fault LED ON*
Ch1 and Ch2 LED flashing alternately
Input concurrency fault: Both inputs did not open concurrently. Both inputs are now
closed.
• Check switches/wiring at both inputs.
• Open both inputs to clear the fault.
Power LED ON
Fault LED ON*
Ch1 LED OFF
Ch2 LED Flashing
Input concurrency fault: Ch1 opened and closed and is now open while Ch2 remained
closed.
• Check switches/wiring at both inputs.
• Open both inputs to clear the fault.
Power LED ON
Fault LED ON*
Ch1 LED Flashing
Ch2 LED OFF
Input concurrency fault: Ch1 remained closed while Ch2 opened and closed and is now
open.
• Check switches/wiring at both inputs.
• Open both inputs to clear the fault.
Power LED ON
Possible input fault: Ch1 and Ch 2 are closed and are (or were) shorted together.
• Check wiring at both inputs.
• Open both inputs to clear the fault.
Possible internal fault: Return to factory for repair or replacement
Fault LED ON*
Ch1 LED ON
Ch2 LED ON
All LEDs OFF
Possible fault in machine control or wiring to module:
• Check input power connections or external fuses.
• Check connectors are properly seated.
Dim LEDs
Dim Power LED:
• Check power supply capacity and load.
Other LEDs dim:
• May glow during power-up (normal).
• Check power supply load and capacity.
* Fault LED Flickers
This is normal while the Fault LED is ON.
MSCs Do Not Energize
Indicator Status
Possible Causes and Solutions
Power LED ON
Fault LED OFF
Ch1 LED ON
Ch2 LED ON
Possible fault in machine control or an open circuit between machine control and MSCs:
• Check continuity of safety outputs (e.g. between terminals 13 and 14).
• Check control wires and connectors.
• Check MSCs.
Repairs
Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it contains no
field-replaceable parts or components. If the device, device part, or device component is determined to be defective by a Banner
Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization) procedure.
Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping is not
covered by warranty.
WARNING:
• Do not abuse the module after failure—If an internal fault has occurred and the module will not reset,
do not tap, strike, or otherwise attempt to correct the fault with a physical impact to the housing.
• Failure to follow these instructions could result in serious injury or death.
• An internal relay might have failed in such a manner that its replacement is required. If the module is not
immediately replaced or repaired, multiple simultaneous failures might accumulate such that the safety
function cannot be guaranteed.
EU Declaration of Conformity (DoC)
Banner Engineering Corp. herewith declares that these products are in conformity with the provisions of the listed directives and all
essential health and safety requirements have been met. For the complete DoC, please go to www.bannerengineering.com.
P/N 122365 Rev. G
www.bannerengineering.com - Tel: + 1 888 373 6767
13
ES-UA-5A and ES-VA-5A E-Stop Safety Module
Product
Directive
ES-UA-5A and ES-VA-5A Emergency Stop Module for industrial 2006/42/EC
control
Representative in EU: Peter Mertens, Managing Director, Banner Engineering BV. Address: Park Lane, Culliganlaan 2F, bus 3,1831
Diegem, Belgium.
Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or
replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not
cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR
TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO
BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL
DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY,
STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously
manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the
product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void