RP1A, RP1B
1-phase PCB mount solid state relays
Main features
•
•
•
•
•
•
•
•
•
•
AC Solid State Relay for PCB mounting
Zero switching or instant-on
Rated operational current: 3, 5 or 5.5 AACrms
Rated operational voltage: Up to 480 VACrms
Surface mount technology
Flexible encapsulation for extended life
Control voltage: 3 to 32 VDC / 16 to 32 VAC
Opto-isolation: > 4000 VACrms
Blocking voltage: Up to 1000 Vp
Non-repetitive surge current: Up to 250 Ap
Description
The RP1 is an SSR series for socket- or PCBmounting, providing an ideal interface between
logic controls and AC loads.
The RP1 is designed for resistive and inductive
loads up to 480 VACrms.
Internally this new series enjoys an improved
technical design with the introduction of stress-free
flexible encapsulation and automated assembly of
components.
The Solid State technology used can withstand
peak voltages of 1000 V, making the RP1 series
suitable to drive AC loads such as valve solenoids
and small induction motors.
Applications
These relays can be used to switch heaters, motors, lights, valves or solenoids.
Main functions
• Zero cross or Instant on AC switching
• Ratings up to 480 VACrms, 5.5 AACrms
• 3-32 VDC or 16-32 VAC control voltage
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
1
RP1A, RP1B
References
Order code
RP1
Enter the code entering the corresponding option instead of
Code
R
P
1
Option
A
B
23
40
48
Description
Notes
Solid State Relay (PCB)
Number of poles
Switching mode: zero switching
Switching mode: instant-On switching
Rated operational voltage: 230 VACrms
Rated operational voltage: 400 VACrms
Rated operational voltage: 480 VACrms
D
Control voltage: 3 to 32 VDC
A
3
5
6
Control voltage: 16 to 32 VAC
Rated operational current: 3 AACrms
Rated operational current: 5 AACrms
Rated operational current: 5.5 AACrms
M1 = Mounting on DIN EN adaptor RPM1
M2 = Mounting on DIN EN adaptor RPM2
Mx
4 to 32 VDC for RP1A48..
4 to 32 VDC for RP1B40.. and RP1B48..
Only available for 230V, 5.5 A
Max. 250V
Max. 600V
Selection guide
Rated operational voltage
Blocking voltage
230 VACrms
650 Vp
400 VACrms
850 Vp
480 VACrms
1000 Vp
Control voltage
3 to 32 VDC
16 to 32 VAC
3 to 32 VDC
4 to 32 VDC
4 to 32 VDC
3 AACrms
RP1A23D3
RP1B23D3
RP1A40D3
RP1B40D3
RP1A48D3
RP1B48D3
Rated operational current
5 AACrms
5.5 AACrms
RP1A23D5
RP1A23D6
RP1B23D5
RP1B23D6
RP1A23A6
RP1A40D5
RP1A40D6
RP1B40D5
RP1B40D6
RP1A48D5
RP1A48D6
RP1B48D5
RP1B48D6
Selection Guide (mounted on DIN EN adaptor)
Rated operational voltage
Blocking voltage
230 VACrms
650 Vp
480 VACrms
1000 Vp
Control voltage
5 to 34 VDC
16 to 32 VAC
6 to 34 VDC
Rated operational current
3 AACrms
5 AACrms
5.5 AACrms
RP1A23D3M1
RP1A23D5M1
RP1A23D6M1
RP1B23D3M1
RP1B23D5M1
RP1B23D6M1
RP1A23A6M1*
-
RP1A48D5M2
-
* Version RP1A23A6M1 does not include an LED on the DIN adaptor.
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
2
RP1A, RP1B
CARLO GAVAZZI compatible components
Purpose
DIN adaptors
Component name/code
RPM1*
RPM1V*
RPM1P
RPM1PD*
RPM2
Notes
DIN adaptor 250V with LED
DIN adaptor 250V with LED + varistor
DIN adaptor 250V with pins for removal of RP
DIN adaptor 250V with pins for removal of RP + LED
DIN adaptor 600V with LED
*not suitable for use with RP1A23A6
Further reading
Information
-
04/12/2019 RP1A, RP1B DS ENG
Where to find it
-
Carlo Gavazzi LTD
3
RP1A, RP1B
Features
General
Material
Potting compound
Weight
Isolation: input to output
Insulation resistance
Insulation capacitance
PBT, RAL7035
Flame-retardant flexible silicone rubber
Approx. 20 g
4 kVACrms
1010
8 pF
Dimensions
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
4
RP1A, RP1B
Performance
Mains supply
Operational voltage range
RP1A
RP1B
Operational frequency range
Blocking voltage
Zero voltage turn-on
RP1.23
RP1.40
RP1.48
12 - 265 VACrms
12 - 265 VACrms
20 - 440 VACrms
12 - 440 VACrms
45 - 65 Hz
850 Vp
< 10 V
20 - 530 VACrms
12 - 530 VACrms
RP1....3
RP1....5
RP1....6
3A
2A
5A
3A
20 mA
> 0.5
12 AACrms
80 Ap
< 1 mA
50 A2s
5.5 A
5A
650 Vp
1000 Vp
Outputs
Rated operational current
AC 51 @ Ta = 25°C
AC 53a @ Ta = 25°C
Min. operational load current
Power factor
Rep. overload current t=1 s
Non-rep. surge current t=20 ms
Off-state leakage current
I2t for fusing t=10 ms
Critical dV/dt off state min.
On-state voltage drop @ rated
current
10 AACrms
65 Ap
20 A2s
250 V/μs
16 AACrms
250 Ap
500 V/μs
340 A2s
< 1.2 Vrms
Inputs
Control voltage
RP1.23.. RP1A40..
RP1B40.. RP1.48..
Pick-up voltage
RP1.23.. RP1A40..
RP1B40.. RP1.48..
Drop-out voltage
Max. input curent
RP1A...
RP1B...
Max. reverse voltage
Response time pick-up
RP1A...
RP1B...
Response time drop-out
RP1A...
RP1B...
04/12/2019 RP1A, RP1B DS ENG
RP1..D
RP1..D..Mx
3-32 VDC
4-32 VDC
5-34 VDC
6-34 VDC
2.8 VDC
3.8 VDC
4.8 VDC
5.8 VDC
1.2 VDC
10 mADC
15 mADC
32 VDC
34 VDC
< 10 ms
< 160 μs (12 VDC/ 50 Hz)
< 320 μs (5 VDC/ 50 Hz)
< 10 ms
< 10 ms
RP1A23A6
16 - 32 VAC
10 VAC
5 VAC
13 mAAC
< 20 ms
< 20 ms
-
Carlo Gavazzi LTD
5
RP1A, RP1B
Derating curve
Load current (AACrms)
6
5
4
3
D6
D5
2
D3
1
0
20
30
40
50
60
70
Surrounding temp. (°C)
Derating curve is used for finding max. load current at an elevated ambient temperature. The 3 lines in the
graph represent the 3 nominal current ratings of the RP1 series (RP1...D3/D5/D6).
When used at full load current, the relays must be placed vertically. If more than one relay is mounted, please
allow a minimum distance of 20 mm in between for sufficient air cooling.
Increased Current Options
Ipeak
Inom
Tamb = 25oC
I peak (Amps)
D5 : t (minutes)
D6 : t (minutes
t
6
15
15
8
5
5
10
3
3
Note: even though the D3 can withstand a slight increase in current for a limited time, it is not recommended
for this purpose.
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
6
RP1A, RP1B
Compatibility and conformity
Standards compliance
LVD: EN 60947-4-3
EMCD: EN 61000-6-2, EN 61000-6-4
UL508
C22.2 No. 14-13
VDE 0700, VDE 0805 (excluding RP1A23A6)
Approvals
Electromagnetic compatibility (EMC) - immunity
EN/IEC 61000-4-2
Electrostatic discharge (ESD)
8 kV air discharge, 4 kV contact (PC1)
EN/IEC 61000-4-3
10 V/m, from 80 MHz to 1 GHz (PC1)
Radiated radio frequency
10 V/m, from 1.4 to 2 GHz (PC1)
10 V/m, from 2 to 2.7 GHz (PC1)
EN/IEC 61000-4-4
Electrical fast transient (burst) Output: 2 kV, 5 kHz (PC2)
Input: 1 kV, 5 kHz (PC2)
EN/IEC 61000-4-6
Conducted radio frequency
10V/m, from 0.15 to 80 MHz (PC1)
EN/IEC 61000-4-5
Output, line to line: 1 kV (PC2)
Electrical surge
Output, line to earth: 1 kV (PC2)1
Input, line to line: 500 V (PC2)2
Input, line to earth: 500 V (PC2)2
EN/IEC 61000-4-11
0% for 0.5, 1 cycle (PC2)
Voltage dips
40% for 10 cycles (PC2)
70% for 25 cycles (PC2)
EN/IEC 61000-4-11
Voltage Interruptions
0% for 5000ms (PC2)
Electromagnetic compatibility (EMC) - emissions
Radio interference field emisEN/IEC 55011
sion (radiated)
Class A: from 30 to 1000 MHz
From 0.15 to 30 MHz
EN/IEC 55011
Radio interference voltage
Class A (industrial) with filter capacitor across the Mains supply
emissions (conducted)
EN/IEC 60947-4-3
Class A (no filtering needed)
Note:
• Performance Criteria 1 (PC1): no degradation of performance or loss of function is allowed when the product is operated
as intended.
• Performance Criteria 2 (PC2): during the test, degradation of performance or partial loss of function is allowed. However
when the test is complete the product should return operating as intended by itself.
• Performance Criteria 3 (PC3): temporary loss of function is allowed, provided the function can be restored by manual
operation of the controls.
• Control input lines must be installed together to maintain products' susceptability to Radio Frequency interference.
• 1 A suppression device, such as a varistor, needs to be connected across the output terminals L1, T1 for immunity against
higher voltage levels.
• 2 A suppression device, such as a transil, needs to be connected across the control terminals A1, A2 for immunity against
higher voltage levels.
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
7
RP1A, RP1B
Environmental specifications
Operating temperature
-20° to +70°C (-4° to +158°F)
Storage temperature
-40° to +100°C (-40° to +212°F)
Pollution degree
2
EU RoHS compliant
Yes
25
China RoHS
The declaration in this section is prepared in compliance with People’s Republic of China Electronic Industry Standard SJ/
T11364-2014: Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products.
Toxic or Harardous Substances and Elements
Part Name
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr(Vl))
Polybrominated biphenyls
(PBB)
Polybrominated diphenyl
ethers (PBDE)
Power Unit
Assembly
x
O
O
O
O
O
O: Indicates that said hazardous substance contained in homogeneous materials fot this part are below the limit
requirement of GB/T 26572.
X: Indicates that said hazardous substance contained in one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.
这份申明根据中华人民共和国电子工业标准
SJ/T11364-2014:标注在电子电气产品中限定使用的有害物质
有毒或有害物质与元素
零件名称
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(Vl))
多溴化联苯
(PBB)
多溴联苯醚
(PBDE)
功率单元
x
O
O
O
O
O
O:此零件所有材料中含有的该有害物低于GB/T 26572的限定。
X: 此零件某种材料中含有的该有害物高于GB/T 26572的限定。
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
8
RP1A, RP1B
RP1... Functional diagram
(+) 3
1
REGULATION
ZC
Control
input
*
IO
2
(-) 4
ZC - Zero Crossing
IO - Instant On
RP..Mx Functional diagram
RP..Mx
RP1...
(+) 3
Control
input
(-) 4
(+) 3
Control
input
(-) 4
3
(+)
(+) 3
REGULATION
4
(-)
Control
input
11
1
REGULATION
ZC
IO
ZC
IO
2
(-) 4
ZC - Zero Crossing
IO - Instant On
*
*
22
ZC - Zero Crossing
IO - Instant On
* The varistor is not included in the solid state relay. Connecting a varistor across terminals 1-2 helps protect
the solid state relay against damages by over-voltage
Connection specifications
Terminals
Terminals soldering temperature
Copper alloy, tin-plated
max. 300°C for 5 seconds
COPYRIGHT ©2019
Content subject to change. Download the PDF: www.productselection.net
04/12/2019 RP1A, RP1B DS ENG
Carlo Gavazzi LTD
9