COOLING
PRODUCT CATALOG - STEGO, Inc.
> New air-flap outlet technology for
high airflow
> Easy mounting
> Protection type/Environmental
ratings by independent testing
agencies (VDE & UL)
www.stegousa.com
FILTER FAN PLUS
FPI/FPO 018 | up to 606.8 cfm (11.5 x 11.5")
> Two optional systems for optimal
airflow (FPI/FPO)
> Industry-common enclosure cut-out
sizes (5 sizes)
> Single filter mat system design
> Two fan speeds
Filter fans are used to provide "cooling" by forced air-circulation in enclosures and cabinets containing eletrical/
electronic and other components. The interior temperature of an enclosure can be reduced by channelling cooler,
filtered outside air into the enclosure, thus expelling hot inside air. The resulting airflow prevents formation of
localized hot pockets and protects electronic components from overheating.
The Filter Fan Plus series encompasses a new air-flap technology on the air outlet side, thereby reaching an
unparalleled high degree of airflow. A unique ratchet mechanism is used for easy installation. It provides safe and
secure mounting while guaranteeing a tight seal. Depending on the requirements, there are two optional systems
available – the FPI or the FPO system (FPI = "in", FPO = "out"). The FPI system is the more commonly known
installation system, where a filter fan located in the lower part of the enclosure draws cleaner, cooler air into the
enclosure (airflow direction "In"). This system consists of a filter fan and exhaust filter. On opposite, with the newer
FPO system, the filter fan will be located in the upper area of the enclosure to draw warmer air out of the enclosure
(airflow direction "Out"). The FPO system consists of an intake filter and exhaust filter fan. The Filter Fan Plus series
may also be used outdoors with appropriate protective measures or when equipped with weather proof accessories,
e.g. Hose-proof Hood FFH 086.
TECHNICAL DATA
11.5" (291 mm)
ENCLOSURE CUT-OUT
1
Axial fan, ball bearing
fan speed 1: service life L10 at +104 °F (+40 °C): min. 76,000 h
metal impeller
fan speed 2: service life L10 at +104 °F (+40 °C): min. 54,000 h
plastic impeller
Connection
3-pole clamp for AWG 14 (2.5 mm²), clamping torque 0.8 Nm max.
Housing, hood, flaps
plastic UL 94V-0, light grey;
UV light resistant according to UL 746C (f1)
Enclosure cut-out
11.5 x 11.5+0.04 inches (291 x 291+1 mm)
Mounting frame
4 built-in ratchet push levers for mounting (6 ratchet stops to
accommodate for wall thicknesses Gauge 9 to 19 or 1 – 4 mm).
Additional screw mounting possible if needed1.
Filter mat
ISO coarse 55% acc. to ISO 16890 (G3), init. grav. arrestance 57%
Filter material
synthetic mesh with progressive construction,
temperature resistant to +212 °F (+100 °C), self-extinguishing class F1,
moisture resistant to 100 % RH, reusable
Operating temperature
fan speed 1 & 2, 50 Hz: -13 to +131 °F (-25 to +55 °C)
fan speed 1, 60 Hz: -13 to +95 °F (-25 to +35 °C)
fan speed 2, 60 Hz: -13 to +122 °F (-25 to +50 °C)
Storage temperature
-40 to +158 °F (-40 to +70 °C)
Operating/Storage humidity
max. 75 % RH (non-condensing)
Protection type/Protection class
IP54 / I (grounded)
Environmental rating UL/NEMA
UL TYPE 12 / NEMA 12
Approvals
UL File No. E234324, VDE, EAC
Note
other voltages on request
Drilling hole markings for screw mounting are indicated on mounting frame.
28.07.2020 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
54
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
55
www.stegousa.com
COOLING
PRODUCT CATALOG - STEGO, Inc.
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
warm
SYSTEM FPI
1.14"1.14"
(29mm)
(29mm)
6.30"
6.30"
(160mm)
(160mm)
12.68"
12.68"
(322mm)
(322mm)
Exhaust Filter FPI 118
1.97"1.97"1.14"1.14"
(50mm)
(50mm)
(29mm)
(29mm)
11.46" (291mm)
11.46" (291mm)
11.46" (291mm)
11.46" (291mm)
Air-flaps
Filter Fan FPI 018
FPI 018
cold
Filter mat
FPI 118
Part No.
Operating
voltage
Fan
speed
Air volume,
free blowing
Air volume
with exhaust filter
Current consumption
Power
(50/60 Hz)
consumption
01874.0-30
AC 230 V, 50/60 Hz
1
254.8 cfm (433 m³/h) 219.5 cfm (373 m³/h)
400/480 mA
01874.0-31
AC 230 V, 50/60 Hz
2
367.3 cfm (624 m³/h) 329.6 cfm (560 m³/h)
550/700 mA
01874.9-30
AC 115 V, 50/60 Hz
1
231.9 cfm (394 m³/h)
199.5 cfm (339 m³/h)
660/800 mA
01874.9-31
AC 115 V, 50/60 Hz
2
391.4 cfm (665 m³/h)
349 cfm (593 m³/h)
1100/1450 mA
Average noise level
(DIN EN ISO 4871)
Mounting
depth
Weight
(approx.)
Filter
mat
95 W
62 dB (A)
6.3" (160 mm)
6.8 lbs. (3.1 kg)
G3
140 W
70 dB (A)
6.3" (160 mm)
7.3 lbs. (3.3 kg)
G3
90 W
61 dB (A)
6.3" (160 mm)
6.8 lbs. (3.1 kg)
G3
165 W
72 dB (A)
6.3" (160 mm)
7.3 lbs. (3.3 kg)
G3
AIRFLOW DIRECTION "IN": EXHAUST FILTER FPI 118
Part No.
Mounting depth
Weight (approx.)
Air outlet
11874.0-00
2.0" (50 mm)
2.2 lbs. (1.0 kg)
air-flap outlet technology
warm
SYSTEM FPO
0.98"
0.98"
(25mm)
(25mm)
1.14"1.14"
1.14"1.14"
6.30"
6.30"
(160mm)
(160mm)(29mm)
(29mm)
(29mm)
(29mm)
12.68"
12.68"
(322mm)
(322mm)
Filter Fan FPO 018
11.46" (291mm)
11.46" (291mm)
11.46" (291mm)
11.46" (291mm)
Air-flaps
Intake Filter FPO 118
FPO 018
cold
Filter mat
FPO 118
AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018
Part No.
Operating
voltage
01884.0-00
AC 230 V, 50/60 Hz
01884.0-01
AC 230 V, 50/60 Hz
01884.9-00
AC 115 V, 50/60 Hz
01884.9-01
AC 115 V, 50/60 Hz
Fan
speed
Air volume,
free blowing
Air volume
with intake filter
Current consumption
Power
Average noise level
(50/60 Hz)
consumption (DIN EN ISO 4871)
1
427.9 cfm (727 m³/h)
243.1 cfm (413 m³/h)
400/480 mA
95 W
2
594.5 cfm (1010 m³/h) 352.6 cfm (599 m³/h)
550/700 mA
140 W
1
413.8 cfm (703 m³/h)
230.1 cfm (391 m³/h)
660/800 mA
90 W
2
606.8 cfm (1031 m³/h)
358.4 cfm (609 m³/h
1100/1450 mA
165 W
Mounting
depth
Weight
(approx.)
Air
outlet
63 dB (A)
6.3" (160 mm)
7.0 lbs. (3.2 kg)
air-flaps
70 dB (A)
6.3" (160 mm)
7.0 lbs. (3.2 kg)
air-flaps
62 dB (A)
6.3" (160 mm)
7.0 lbs. (3.2 kg)
air-flaps
71 dB (A)
6.3" (160 mm)
7.0 lbs. (3.2 kg)
air-flaps
AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118
Part No.
Mounting depth
Weight (approx.)
Filter mat
11884.0-30
1.0" (25 mm)
1.8 lbs. (0.8 kg)
ISO coarse 55 % acc. to ISO 16890 (G3), initial gravimetric arrestance 57 %
FILTER MAT FM 086
Filter class
11.14 x 11.14" (283 x 283 mm)
Initial gravimetric arrestance
1 packing unit
ISO coarse 55% acc. to ISO 16890 (G3)
Part No. 08637.0-00
57 %
5 pieces
28.07.2020 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.