Miniature Circuit Breakers and
Supplementary Protectors
Miniature Circuit Breakers and
Supplementary Protectors
1.1
Industrial Circuit Breakers
QUICKLAG®. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW . . . . . . . . . . .
QUICKLAG Plug-On Ground Fault and Equipment Protectors,
Types QPHGFT, QPHGFT, QPGFEP, QPHGFEP . . . . . . . . . . . . . . . . .
Bolt-On Types BAB, QBHW, HBAX, HBAW. . . . . . . . . . . . . . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types QBAF, QBCAF . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP. . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment Protectors,
Types QCGFT, QCHGFT, QCGFEP, QCHGFEP. . . . . . . . . . . . . . . . . .
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . . . . . . . . . . . . .
Solenoid Operator—Remote-Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . . . . . . . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC. . . . . . . . . . .
Special Application Breakers, Types HQP, BA, QC . . . . . . . . . . . . . . .
1.2
1.4
1
V4-T1-8
1
V4-T1-11
V4-T1-14
1
V4-T1-17
1
V4-T1-20
1
V4-T1-24
1
V4-T1-28
1
V4-T1-31
1
V4-T1-34
1
V4-T1-37
V4-T1-40
V4-T1-49
UL 1077 DIN Rail Supplementary Protectors
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-67
UL 1053 DIN Rail RCCB
UL 1053 DIN Rail RCCB 480/277 Vac . . . . . . . . . . . . . . . . . . . . . . . . .
UL 1053 DIN Rail RCCB 208Y/120 Vac . . . . . . . . . . . . . . . . . . . . . . . .
1
V4-T1-5
UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3
V4-T1-2
V4-T1-87
V4-T1-93
1
1
1
1
1
1
1
1
Learn
Online
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-1
Revision notes
Volume 4—Circuit Protectors, CA08100005E
Tab 1—Miniature Circuit Breakers and Supplementary Protectors
Revision date
Section
Change page(s)
Description
11/30/2016
1.3
V4-T1-70
Content edit
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
Miniature Circuit Breakers and Supplementary Protectors
Description
1
Quick Reference
1
1
1
1
1
1
1
1
1
1
1
1
QUICKLAG
1
Quick Reference
1
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out
1
Circuit
Breaker
Type
1
Circuit Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
Number
of
Poles
Vac
Interrupting Ratings rms Symmetrical Amperes
Vdc
Federal
Spec.
W-C-375b
120
120/240
240
24–48
62.5
80
Page
Number
V4-T1-6
Vdc Ratings 2
Vac Ratings
HQP
P
10–70
1
120/240
24, 48, 62.5
10a, 11a, 12a
—
10,000
—
5000
3
—
1
HQP
P
10–125
2
120/240
24, 48, 80
10a, 12a
—
10,000
—
5000
5000
5000
V4-T1-6
HQP
P
10–100
2, 3
240
—
10b, 11b, 12b
—
—
10,000
—
—
—
V4-T1-6
1
QPHW
P
15–70
1
120/240
24, 48, 62.5
14a
—
22,000
—
5000
3
—
V4-T1-6
1
QPHW
P
15–125
2
120/240
24, 48, 80
14a
—
22,000
—
5000
5000
5000
V4-T1-6
QPHW
P
15–100
2, 3
240
—
14b
—
—
22,000
—
—
—
V4-T1-6
QHPX
P
15–70
1
120/240
24, 48, 62.5
—
—
42,000
—
5000
3
—
V4-T1-7
QHPX
P
15–100
2
120/240
24, 48, 80
—
—
42,000
—
5000
5000
5000
V4-T1-7
V4-T1-7
1
1
1
1
1
1
1
1
QHPX
P
15–100
3
240
—
—
—
—
42,000
—
—
—
QHPW
P
15–30
1
120/240
24, 48, 62.5
15a
—
65,000
—
5000
3
—
V4-T1-7
QHPW
P
15–30
2
120/240
24, 48, 80
15a
—
65,000
—
5000
5000
5000
V4-T1-7
QHPW
P
15–20
3
240
—
15b
—
—
65,000
—
—
—
V4-T1-7
QPGFT
P, GF
15–40
1
120
—
10a, 11a, 12a
10,000
—
—
—
—
—
V4-T1-9
QPGFT
P, GF
15–50
2
120/240
—
10a, 11a, 12a
—
10,000
—
—
—
—
V4-T1-9
Notes
1 QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL® listed.
3 62.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
1
V4-T1-2
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued
Circuit
Breaker
Type
Circuit Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
1
Interrupting Ratings rms Symmetrical Amperes
Number
of
Poles
Vac
Vdc
Federal
Spec.
W-C-375b
Vac Ratings
120
120/240
Vdc Ratings
240
24–48
2
62.5
80
Page
Number
QPHGFT
P, GF
15–30
1
120
—
10a, 11a, 12a
22,000
—
—
—
—
—
V4-T1-9
QPHGFT
P, GF
15–50
2
120/240
—
10a, 11a, 12a
—
22,000
—
—
—
—
V4-T1-9
QPGFEP
P, GFEP
15–40
1
120
—
—
10,000
—
—
—
—
—
V4-T1-9
QPGFEP
P, GFEP
15–50
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-9
QPHGFEP
P, GFEP
15–30
1
120
—
—
22,000
—
—
—
—
—
V4-T1-9
BABRSP
B
15–30
1
120
—
—
10,000
—
—
—
—
—
V4-T1-12
BABRSP
B
15–30
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-12
BRRP
P
15–30
1
120
—
—
10,000
—
—
—
—
—
V4-T1-32
BRRP
P
15–30
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-32
CLRP
P
15–30
1
120
—
—
10,000
—
—
—
—
—
V4-T1-32
CLRP
P
15–30
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-32
BAB
B
10–70
1
120/240
24, 48, 62.5
10a, 11a, 12a
—
10,000
—
5000
3
—
V4-T1-12
BAB
B
10–125
2
120/240
24, 48, 80
10a, 12a
—
10,000
—
5000
5000
5000
V4-T1-12
BAB
B
10–100
2, 3
240
—
10b, 11b, 12b
—
—
10,000
—
—
—
V4-T1-12
BABRP
B
15–30
1
120
—
—
10,000
—
—
—
—
—
V4-T1-32
BABRP
B
15–30
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-32
QBAF
B, AF
15–20
1, 2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-15
QBCAF
B, AF, GF
15–20
1, 2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-15
QBHW
B
15–70
1
120/240
24, 48, 62.5
14a
—
22,000
—
5000
3
—
V4-T1-12
QBHW
B
15–125
2
120/240
24, 48, 80
14a
—
22,000
—
5000
5000
5000
V4-T1-12
QBHW
B
15–100
2, 3
240
—
14b
—
—
22,000
—
—
—
V4-T1-12
3
HBAX
B
15–70
1
120/240
24, 48, 62.5
—
—
42,000
—
5000
—
V4-T1-13
HBAX
B
15–100
2
120/240
24, 48, 80
—
—
42,000
—
5000
5000
5000
V4-T1-13
HBAX
B
15–100
3
240
—
—
—
42,000
—
—
—
V4-T1-13
HBAW
B
15–30
1
120/240
24, 48, 62.5
15a
—
65,000
—
5000
3
—
V4-T1-13
HBAW
B
15–30
2
120/240
24, 48, 80
15a
—
65,000
—
5000
5000
5000
V4-T1-13
HBAW
B
15–20
3
240
—
15b
—
—
65,000
—
—
—
V4-T1-13
QBGFT
B, GF
15–40
1
120
—
10a, 11a, 12a
10,000
—
—
—
—
—
V4-T1-18
QBGFT
B, GF
15–50
2
120/240
—
10a, 11a, 12a
—
10,000
—
—
—
—
V4-T1-18
QBHGFT
B, GF
15–30
1
120
—
10a, 11a, 12a
22,000
—
—
—
—
—
V4-T1-18
QBHGFT
B, GF
15–30
1
120/240
—
10a, 11a, 12a
—
22,000
—
—
—
—
V4-T1-18
QBGFEP
B, GFEP
15–40
1
120
—
—
10,000
—
—
—
—
—
V4-T1-18
QBGFEP
B, GFEP
15–50
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-18
QBHGFEP
B, GFEP
15–30
1
120
—
—
22,000
—
—
—
—
—
V4-T1-18
QBHGFEP
B, GFEP
15–30
2
120/240
—
—
22,000
22,000
—
—
—
—
V4-T1-18
QC
C
10–70
1
120/240
24, 48, 62.5
10a, 11a, 12a
—
10,000
—
5000
3
—
V4-T1-41
QC
C
10–100
2
120/240
24, 48, 80
10a, 12a
—
10,000
—
5000
5000
5000
V4-T1-41
QC
C
10–100
2, 3, 4
240
—
10b, 11b, 12b
—
—
10,000
—
—
—
V4-T1-41
QCD
C
10–60
1, 2
120/240
24, 48, 62.5
—
10,000
10,000
—
3000
3000
—
V4-T1-23
QCD
C
10–100
2, 3
240
24, 48, 62.5
—
—
10,000
—
3000
3000
—
V4-T1-23
QCF
C
10–60
1, 2
120/240
24, 48, 62.5
—
10,000
10,000
—
3000
3000
—
V4-T1-42
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Notes
1 QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
3 62.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
1
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-3
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued
1
Circuit
Breaker
Type
1
QCF
C
15–20
1, 2
1
QCF
C
15–30
2, 3
QCR
C
10–60
1, 2
1
QCR
C
15–20
QCR
C
QCHW
QCHW
1
1
1
1
Circuit
Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
Interrupting Ratings rms Symmetrical Amperes
Number
of
Poles
Vac Ratings
Vdc
Federal
Spec.
W-C-375b
120
120/240
240
24–48
62.5
80
Page
Number
120/240
24, 48, 62.5
—
22,000
—
—
3000
3000
—
V4-T1-27
240
24, 48, 62.5
—
—
10,000
—
3000
3000
—
V4-T1-27
120/240
24, 48, 62.5
—
10,000
10,000
—
3000
3000
—
V4-T1-27
1, 2
120/240
24, 48, 62.5
—
22,000
—
—
3000
3000
—
V4-T1-27
15–30
2, 3
240
24, 48, 62.5
—
—
10,000
—
3000
3000
—
V4-T1-27
C
15–70
1
120/240
24, 48, 62.5
14a
—
22,000
—
5000
—
V4-T1-22
C
15–100
2
120/240
24, 48, 80
14a
—
22,000
—
5000
5000
5000
V4-T1-22
—
—
V4-T1-22
3
—
V4-T1-22
Vac
Vdc Ratings 2
3
QCHW
C
15–100
2, 3
240
—
14b
—
—
22,000
—
QHCX
C
15–70
1
120/240
24, 48, 62.5
—
—
42,000
—
5000
QHCX
C
15–100
2
120/240
24, 48, 80
—
—
42,000
—
5000
5000
5000
V4-T1-22
—
—
V4-T1-22
3
—
V4-T1-22
QHCX
C
15–100
3
240
—
—
—
—
42,000
—
QHCW
C
15–30
1
120/240
24, 48, 62.5
15a
—
65,000
—
5000
QHCW
C
15–30
2
120/240
24, 48, 80
15a
—
65,000
—
5000
5000
5000
V4-T1-22
1
QHCW
C
15–20
3
240
—
15b
—
—
65,000
—
—
—
V4-T1-22
QCGFT
C, GF
15–40
1
120
—
—
10,000
—
—
—
—
—
V4-T1-29
1
QCGFT
C, GF
15–50
2
120/240
—
—
—
10,000
—
—
—
—
V4-T1-29
QCHGFT
C, GF
15–30
1
120
—
—
22,000
—
—
—
—
—
V4-T1-29
QCHGFT
C, GF
15–30
2
120/240
—
—
—
22,000
—
—
—
—
V4-T1-29
QCGFEP
C, GFEP
15–40
1
120
—
—
10,000
—
—
—
—
—
V4-T1-29
V4-T1-29
1
1
1
1
1
QCGFEP
C, GFEP
15–50
2
120/240
—
—
—
10,000
—
—
—
—
QCHGFEP
C, GFEP
15–30
1
120
—
—
22,000
—
—
—
—
—
V4-T1-29
QCHGFEP
C, GFEP
15–30
2
120/240
—
—
—
22,000
—
—
—
—
V4-T1-29
1
Notes
1 QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
3 62.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
1
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-4
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Contents
QUICKLAG Type HQP Single-Pole
Description
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-6
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-7
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP. . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . .
V4-T1-40
1
1
1
1
1
1
1
1
1
1
1
1
1
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
1
Product Description
1
●
●
All products 15–100A are
HACR rated
Switching duty rated for
120 Vac fluorescent light
applications
Standards and Certifications
●
●
Built and listed to UL 489
All products UL and
CSA® listed
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-5
1.1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type HQP
Single-Pole
QUICKLAG Type: HQP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
10
HQP1010
HQP2010
—
HQP3010H 3
1
15
HQP1015 12
HQP2015
HQP2015H
HQP3015H
20
HQP1020 12
HQP2020
HQP2020H
HQP3020H
1
25
HQP1025
HQP2025
HQP2025H
HQP3025H
30
HQP1030
HQP2030
HQP2030H
HQP3030H
1
35
HQP1035
HQP2035
HQP2035H
HQP3035H
40
HQP1040
HQP2040
HQP2040H
HQP3040H
1
45
HQP1045
HQP2045
HQP2045H
HQP3045H
50
HQP1050
HQP2050
HQP2050H
HQP3050H
1
55
HQP1055
HQP2055
HQP2055H
HQP3055H
60
HQP1060
HQP2060
HQP2060H
HQP3060H
1
70
HQP1070
HQP2070
HQP2070H
HQP3070H
80
—
HQP2080
HQP2080H
HQP3080H
1
90
—
HQP2090
HQP2090H
HQP3090H
100
HQP1100
HQP2100
HQP2100H
HQP3100H
1
110
—
HQP2110
—
—
125
—
HQP2125
—
—
1
150
—
HQP2150
—
—
Three-Pole
Continuous
Ampere Rating
at 40°C
1
1
QUICKLAG Type: HQP Non-Automatic Switches
1
Continuous
Ampere Rating
at 40°C
1
1
Single-Pole
Two-Pole
Two-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
50
HQP1050N
—
HQP2050N
HQP3050N
60
HQP1060N
—
HQP2060N
HQP3060N
100
HQP1100N
—
HQP2100N
HQP3100N
1
QUICKLAG Type: QPHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers
1
Single-Pole
Two-Pole
Two-Pole
1
Continuous
Ampere Rating
at 40°C
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
15
20
QPHW1015 1
QPHW1020 1
QPHW2015
QPHW2015H
QPHW3015H
QPHW2020
QPHW2020H
QPHW3020H
1
25
QPHW1025
QPHW2025
QPHW2025H
QPHW3025H
1
1
1
1
1
1
1
30
QPHW1030
QPHW2030
QPHW2030H
QPHW3030H
35
QPHW1035
QPHW2035
QPHW2035H
QPHW3035H
40
QPHW1040
QPHW2040
QPHW2040H
QPHW3040H
45
QPHW1045
QPHW2045
QPHW2045H
QPHW3045H
50
QPHW1050
QPHW2050
QPHW2050H
QPHW3050H
55
QPHW1055
QPHW2055
QPHW2055H
QPHW3055H
60
QPHW1060
QPHW2060
QPHW2060H
QPHW3060H
70
QPHW1070
QPHW2070
QPHW2070H
QPHW3070H
80
—
QPHW2080
QPHW2080H
QPHW3080H
90
—
QPHW2090
QPHW2090H
QPHW3090H
100
—
QPHW2100
QPHW2100H
QPHW3100H
110
—
QPHW2110
—
—
125
—
QPHW2125
—
—
Notes
1 Switching duty rated for 120 Vac fluorescent light applications.
2 For special low-magnetic breaker, order HQP1015L1 or HQP1020L1.
3 Not UL listed.
1
V4-T1-6
Three-Pole
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
QUICKLAG Type: QHPX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
15
QHPX1015
1
QHPX2015
—
QHPX3015H
20
QHPX1020 1
QHPX2020
—
QHPX3020H
25
QHPX1025
QHPX2025
—
QHPX3025H
30
QHPX1030
QHPX2030
—
QHPX3030H
35
QHPX1035
QHPX2035
—
QHPX3035H
40
QHPX1040
QHPX2040
—
QHPX3040H
45
QHPX1045
QHPX2045
—
QHPX3045H
50
QHPX1050
QHPX2050
—
QHPX3050H
55
QHPX1055
QHPX2055
—
QHPX3055H
60
QHPX1060
QHPX2060
—
QHPX3060H
70
QHPX1070
QHPX2070
—
QHPX3070H
Continuous
Ampere Rating
at 40°C
80
—
QHPX2080
—
QHPX3080H
90
—
QHPX2090
—
QHPX3090H
100
—
QHPX2100
—
QHPX3100H
1
1
1
1
1
1
1
1
1
1
QUICKLAG Type: QHPW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
QHPW2015
—
QHPW3015H
—
QHPW3020H
Continuous
Ampere Rating
at 40°C
Catalog Number
15
QHPW1015 1
20
QHPW1020 1
QHPW2020
25
QHPW1025
QHPW2025
—
—
30
QHPW1030
QHPW2030
—
—
1
1
1
1
1
1
Dimensions
Approximate Dimensions in Inches (mm)
1
Shipping Data
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg)
Dimensions
1
24
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2
12
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3
8
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1
1
1
1
Note
1 Switching duty rated for 120 Vac fluorescent light applications.
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-7
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
QUICKLAG Type QPGFT Single-Pole
Ground Fault Circuit Breaker
Description
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP
V4-T1-9
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-10
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . .
V4-T1-40
QUICKLAG Plug-On Ground Fault and Equipment Protectors,
Types QPGFT, QPHGFT, QPGFEP, QPHGFEP
Product Description
Standards and Certifications
●
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment Protectors
●
30 mA trip sensitivity
1
Built and listed to UL 489
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
Built and tested to UL 943
QUICKLAG Ground Fault
Equipment Protectors
●
Built and listed to UL 1053
1
1
1
1
1
1
1
1
1
1
V4-T1-8
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Product Selection
QUICKLAG Type QPGFT
Single-Pole
1
1
Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG Type:
QPGFT 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QPGFT1015
QPGFT2015
20
QPGFT1020
QPGFT2020
25
QPGFT1025
QPGFT2025
30
QPGFT1030
QPGFT2030
40
QPGFT1040
QPGFT2040
50
—
QPGFT2050
Continuous
Ampere Rating
at 40°C
1
1
1
1
1
1
1
QUICKLAG Type: QPHGFT 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QPHGF1015
QPHGF2015
20
QPHGF1020
QPHGF2020
25
QPHGF1025
QPHGF2025
30
QPHGF1030
QPHGF2030
Continuous
Ampere Rating
at 40°C
1
1
1
1
1
1
Ground Fault Equipment Breakers—30 mA Sensitivity QUICKLAG Type:
QPGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QPGFEP1015
QPGFEP2015
20
QPGFEP1020
QPGFEP2020
25
QPGFEP1025
QPGFEP2025
30
QPGFEP1030
QPGFEP2030
40
QPGFEP1040
QPGFEP2040
50
—
QPGFEP2050
1
1
1
1
1
1
1
QUICKLAG Type: QPHGFEP 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QPHGFEP1015
QPHGFEP2015
20
QPHGFEP1020
QPHGFEP2020
25
QPHGFEP1025
QPHGFEP2025
30
QPHGFEP1030
QPHGFEP2030
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-9
1.1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Special Application Ground Fault Circuit Protectors—5 mA Sensitivity
QUICKLAG Type: QPGFT 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
1
15
QPGFT1015W1
QPGFT2015W1
20
QPGFT1020W1
QPGFT2020W1
1
25
QPGFT1025W1
QPGFT2025W1
30
QPGFT1030W1
QPGFT2030W1
1
40
—
QPGFT2040W1
50
—
QPGFT2050W1
1
15
QPGFT1015W2
—
20
QPGFT1020W2
—
1
25
QPGFT1025W2
—
30
QPGFT1030W2
—
1
1
1
1
Special Application Ground Fault Circuit Protectors—30 mA Sensitivity
QUICKLAG Type: QPGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
1
15
QPGFEP1015W1
QPGFEP2015W1
20
QPGFEP1020W1
QPGFEP2020W1
1
25
QPGFEP1025W1
QPGFEP2025W1
30
QPGFEP1030W1
QPGFEP2030W1
1
40
—
QPGFEP2040W1
1
1
50
—
QPGFEP2050W1
15
QPGFEP1015W2
—
20
QPGFEP1020W2
—
25
QPGFEP1025W2
—
30
QPGFEP1030W2
—
1
1
Wiring Diagram
1
Bell Alarm and Auxiliary Contact Schematic
Blue
1
Ground
Fault
Breaker
1
1
1
1
Blue Wire
NC
Red
Dimensions
Approximate Dimensions in Inches (mm)
1
Shipping Data
1
1
Red Wire
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
1
1
Black Wire
NO
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg)
1
24
11.00 (5.0)
12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
2
5
5.00 (2.3)
15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
Dimensions
Note
Shipped individually or in carton quantities.
V4-T1-10
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Contents
QUICKLAG Type BAB Single-Pole
Description
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW
V4-T1-12
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-13
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP. . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . .
V4-T1-40
1
1
1
1
1
1
1
1
1
1
1
1
1
Bolt-On Types BAB, QBHW, HBAX, HBAW
1
Product Description
1
●
●
All products 15–100A are
HACR rated
Switching duty rated
for 120 Vac fluorescent
light applications
Standards and Certifications
●
●
Built and listed to UL 489
All products UL and
CSA listed
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-11
1.1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type BAB
Single-Pole
QUICKLAG Type: BA 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
1
10
1
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
BAB1010
BAB2010
BAB2010H 3
BAB3010H 3
15
BAB1015 12
BAB2015
BAB2015H
BAB3015H
20
BAB1020 12
BAB2020
BAB2020H
BAB3020H
1
25
BAB1025
BAB2025
BAB2025H
BAB3025H
30
BAB1030
BAB2030
BAB2030H
BAB3030H
1
35
BAB1035
BAB2035
BAB2035H
BAB3035H
40
BAB1040
BAB2040
BAB2040H
BAB3040H
45
BAB1045
BAB2045
BAB2045H
BAB3045H
1
1
1
1
1
1
50
BAB1050
BAB2050
BAB2050H
BAB3050H
55
BAB1055
BAB2055
BAB2055H
BAB3055H
60
BAB1060
BAB2060
BAB2060H
BAB3060H
70
BAB1070
BAB2070
BAB2070H
BAB3070H
80
—
BAB2080
BAB2080H
BAB3080H
90
—
BAB2090
BAB2090H
BAB3090H
100
BAB1100
BAB2100
BAB2100H
BAB3100H
110
—
BAB2110
—
—
125
—
BAB2125
—
—
Three-Pole
QUICKLAG Type: BA Non-Automatic Switches
1
Single-Pole
Two-Pole
Two-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
Continuous
Ampere Rating
at 40°C
1
50
BAB1050N
—
BAB2050N
BAB3050N
60
BAB1060N
—
BAB2060N
BAB3060N
100
BAB1100N
—
BAB2100N
BAB3100N
1
1
QUICKLAG Type: QBHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers
1
Continuous
Ampere Rating
at 40°C
1
Single-Pole
Two-Pole
Two-Pole
120/240 Vac
120/240 Vac
240 Vac
Three-Pole
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
15
QBHW1015 1
QBHW2015
QBHW2015H
QBHW3015H
1
20
QBHW1020 1
QBHW2020
QBHW2020H
QBHW3020H
25
QBHW1025
QBHW2025
QBHW2025H
QBHW3025H
1
30
QBHW1030
QBHW2030
QBHW2030H
QBHW3030H
35
QBHW1035
QBHW2035
QBHW2035H
QBHW3035H
1
40
QBHW1040
QBHW2040
QBHW2040H
QBHW3040H
45
QBHW1045
QBHW2045
QBHW2045H
QBHW3045H
1
50
QBHW1050
QBHW2050
QBHW2050H
QBHW3050H
55
QBHW1055
QBHW2055
QBHW2055H
QBHW3055H
1
60
QBHW1060
QBHW2060
QBHW2060H
QBHW3060H
1
1
1
70
QBHW1070
QBHW2070
QBHW2070H
QBHW3070H
80
—
QBHW2080
QBHW2080H
QBHW3080H
90
—
QBHW2090
QBHW2090H
QBHW3090H
100
—
QBHW2100
QBHW2100H
QBHW3100H
110
—
QBHW2110
—
—
125
—
QBHW2125
—
—
Notes
1 Switching duty rated for 120 Vac fluorescent light applications.
2 For special low-magnetic breaker, order BAB1015L1 or BAB1020L1.
3 Not UL listed.
1
1
V4-T1-12
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
QUICKLAG Type: HBAX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
Single-Pole
Two-Pole
Two-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
15
HBAX1015
1
HBAX2015
—
HBAX3015H
20
HBAX1020 1
HBAX2020
—
HBAX3020H
25
HBAX1025
HBAX2025
—
HBAX3025H
30
HBAX1030
HBAX2030
—
HBAX3030H
35
HBAX1035
HBAX2035
—
HBAX3035H
40
HBAX1040
HBAX2040
—
HBAX3040H
45
HBAX1045
HBAX2045
—
HBAX3045H
50
HBAX1050
HBAX2050
—
HBAX3050H
55
HBAX1055
HBAX2055
—
HBAX3055H
60
HBAX1060
HBAX2060
—
HBAX3060H
70
HBAX1070
HBAX2070
—
HBAX3070H
80
—
HBAX2080
—
HBAX3080H
80
—
HBAX2080
—
HBAX3080H
90
—
HBAX2090
—
HBAX3090H
100
—
HBAX2100
—
HBAX3100H
Continuous
Ampere Rating
at 40°C
1
Three-Pole
1
1
1
1
1
1
1
1
1
1
1
QUICKLAG Type: HBAW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
15
HBAW1015 1
HBAW2015
—
HBAW3015H
20
HBAW1020 1
HBAW2020
—
HBAW3020H
25
HBAW1025
HBAW2025
—
—
30
HBAW1030
HBAW2030
—
—
1
1
1
1
1
1
Dimensions
Approximate Dimensions in Inches (mm)
1
Shipping Data
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg)
Dimensions
1
24
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2
12
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3
8
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1
1
1
1
Note
1 Switching duty rated for 120 Vac fluorescent light applications.
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-13
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Bolt-On Arc Fault Circuit Interrupter QUICKLAG Types QBAF, QBCAF
Contents
Description
1
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF
V4-T1-15
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-16
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . .
V4-T1-40
1
1
1
1
1
1
1
1
1
1
1
1
Bolt-On Arc Fault Circuit Interrupter Types QBAF, QBCAF
1
Product Description
●
All products HACR rated
1
Features, Benefits and
Functions
●
1
●
●
1
●
10 and 22 kAIC rating at
120V and 120/240V
Single-pole AFCI
HID ratings for HID (High
Intensity Discharge) lighting
All models are HACR rated
Standards and Certifications
●
●
Built and listed to UL 489
UL File E7819 for QBAF
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-14
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Product Selection
1
QBCAF and QBAF Type AFCIs
Effective immediately, Eaton
AFCIs are available for use in
Sumter panels with a 22 kAIC
rating. This higher rated
breaker will allow us to
win jobs where AFCIs are
specified at higher than
10 kAIC. This breaker
provides standard thermal-
QBHCAF
magnetic protection of
branch circuits. This product
will have the same form, fit
and function of the current
bolt-on AFCI (QBCAF and
QBAF Type). Product scope is
below. These breakers are in
Bid Manager™ for Pow-RLine 1a, Pow-R-Line 1a-LX,
1
Pow-R-Line 3a and Pow-RLine 4a panelboards. For
series rated combinations,
continue to use the less
expensive 10 kAIC QBCAF
and QBAF offerings.
1
1
1
Breakers can also be ordered
from Vista.
1
1
1-Inch (25.4 mm) Wide Bolt-On Arc Fault Circuit Interrupter
Poles
kAIC
Rating
Ampere
Rating
Configuration
Catalog Number
Combination AFCI
QBCAF1015
1
1
Type QBCAF Combination AFCI
Single-pole
10 kAIC
15
20
Combination AFCI
QBCAF1020
22 kAIC
15
Combination AFCI
QBHCAF1015
20
Combination AFCI
QBHCAF1020
15
Branch Feeder AFCI
QBAF1015
20
Branch Feeder AFCI
QBAF1020
15
Branch Feeder AFCI
QBHAF1015
20
Branch Feeder AFCI
QBHAF1020
1
1
1
Type QBAF Branch Feeder AFCI
Single-pole
10 kAIC
22 kAIC
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-15
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1
Wiring Diagrams
1
Single-Pole 120V Load Application
Sourced by 120/240 Vac
1
1
120/240 Vac
Source
N A B
Line B
1
1
1
Single-Pole
Neutral
120V
Duplex
Receptacle
Neutral
1
Equipment Ground
1
1
1
1
Single-Pole Shared Neutral with
Multi-Duplex Receptacle Application
120/240 Vac
Source
N A B
1
Line B
1
Two-Pole
1
1
Neutral
Neutral
1
Two 120V
Duplex
Receptacles
Line A
1
Equipment Ground
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-16
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Contents
QUICKLAG Type QBGFT Single-Pole
Ground Fault Circuit Breaker
Description
Page
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP
V4-T1-18
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-19
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-19
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . .
V4-T1-40
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP
Product Description
Built and tested to UL 489
1
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
Built and tested to UL 943
1
QUICKLAG Ground Fault
Equipment Protectors
●
Built and tested to UL 1053
1
●
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment
Protectors
●
30 mA trip sensitivity
1
Standards and Certifications
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-17
1.1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type QBGFT
Single-Pole
Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG Type:
QBGFT 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QBGFT1015
QBGFT2015
20
QBGFT1020
QBGFT2020
25
QBGFT1025
QBGFT2025
1
30
QBGFT1030
QBGFT2030
40
QBGFT1040
QBGFT2040
1
50
—
QBGFT2050
1
1
1
1
QUICKLAG Type: QBHGFT 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
1
Continuous
Ampere Rating
at 40°C
1
1
1
1
1
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QBHGF1015
QBHGF2015
20
QBHGF1020
QBHGF2020
25
QBHGF1025
QBHGF2025
30
QBHGF1030
QBHGF2030
Ground Fault Equipment Breakers—30 mA Sensitivity QUICKLAG Type:
QBGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
1
Continuous
Ampere Rating
at 40°C
1
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
1
15
QBGFEP1015
QBGFEP2015
20
QBGFEP1020
QBGFEP2020
1
25
QBGFEP1025
QBGFEP2025
30
QBGFEP1030
QBGFEP2030
40
QBGFEP1040
QBGFEP2040
50
—
QBGFEP2050
1
1
1
QUICKLAG Type: QBHGFEP 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
1
Continuous
Ampere Rating
at 40°C
1
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
1
15
QBHGFEP1015
QBHGFEP2015
20
QBHGFEP1020
QBHGFEP2020
1
25
QBHGFEP1025
QBHGFEP2025
30
QBHGFEP1030
QBHGFEP2030
1
1
1
1
V4-T1-18
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Special Application Ground Fault Circuit Protectors—5 mA Sensitivity QUICKLAG Type:
QBGFT 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Single-Pole
Continuous
Ampere Rating
at 40°C
1
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QBGFT1015W1
QBGFT2015W1
20
QBGFT1020W1
QBGFT2020W1
25
QBGFT1025W1
QBGFT2025W1
30
QBGFT1030W1
QBGFT2030W1
40
—
QBGFT2040W1
50
—
QBGFT2050W1
15
QBGFT1015W2
—
20
QBGFT1020W2
—
25
QBGFT1025W2
—
30
QBGFT1030W2
—
1
1
1
1
1
1
1
1
Special Application Ground Fault Circuit Protectors—30 mA Sensitivity QUICKLAG Type:
QBGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Single-Pole
Continuous
Ampere Rating
at 40°C
1
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
15
QBGFEP1015W1
QBGFEP2015W1
20
QBGFEP1020W1
QBGFEP2020W1
25
QBGFEP1025W1
QBGFEP2025W1
30
QBGFEP1030W1
QBGFEP2030W1
40
—
QBGFEP2040W1
50
—
QBGFEP2050W1
15
QBGFEP1015W2
—
20
QBGFEP1020W2
—
25
QBGFEP1025W2
—
30
QBGFEP1030W2
—
1
1
1
1
1
1
1
Wiring Diagram
1
Bell Alarm and Auxiliary Contact Schematic
1
Blue
Ground
Fault
Breaker
Red
1
Blue Wire
NC
Black Wire
1
NO
Red Wire
1
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
1
1
Dimensions
1
Approximate Dimensions in Inches (mm)
1
Shipping Data
Number of Poles
Approximate Weight Lbs (kg)
Dimensions
1
11.00 (5.0)
12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
2
5.00 (2.3)
15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
1
1
Note
Shipped individually or in carton quantities.
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-19
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
QUICKLAG Type QC Single-Pole
Description
1
1
1
1
1
1
1
1
1
1
1
1
1
Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW
1
Product Description
1
1
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW
V4-T1-21
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-23
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . .
V4-T1-40
●
●
All products 10–100A are
HACR rated
Switching duty rated for
120 Vac fluorescent light
applications only
Standards and Certifications
●
●
Built and listed to UL 489
All products UL and
CSA listed
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-20
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG
Type QC Single-Pole
1
1
QUICKLAG Type: QC 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
Four-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
240 Vac
1
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
5
QC1005 1
QC2005 1
—
—
—
10
QC1010
QC2010
QC2010H 1
QC3010H 1
—
15
QC1015 2
QC2015
QC2015H
QC3015H
QC4015H
20
QC1020 2
QC2020
QC2020H
QC3020H
QC4020H
25
QC1025
QC2025
QC2025H
QC3025H
QC4025H
30
QC1030
QC2030
QC2030H
QC3030H
QC4030H
35
QC1035
QC2035
QC2035H
QC3035H
QC4035H
40
QC1040
QC2040
QC2040H
QC3040H
QC4040H
45
QC1045
QC2045
QC2045H
QC3045H
QC4045H
50
QC1050
QC2050
QC2050H
QC3050H
QC4050H
55
QC1055
QC2055
QC2055H
QC3055H
QC4055H
60
QC1060
QC2060
QC2060H
QC3060H
QC4060H
70
QC1070
QC2070
QC2070H
QC3070H
QC4070H
70
—
QC2080
QC2080H
QC3080H
QC4080H
90
—
QC2090
QC2090H
QC3090H
QC4090H
100
QC1100
QC2100
QC2100H
QC3100H
QC4100H
1
1
1
1
1
1
1
1
1
1
1
QUICKLAG Type: QC Non-Automatic Switches
1
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
Four-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
50
QC1050N
—
QC2050N
QC3050N
—
60
QC1060N
—
QC2060N
QC3060N
—
100
QC1100N
—
QC2100N
QC3100N
—
1
1
1
Notes
1 Not UL listed.
2 Switching duty rated for 120 Vac fluorescent light applications only.
1
1
For special low-magnetic breaker, order QC1015L1 or QC1020L1.Non-automatic switches, see Page V4-T1-42.
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-21
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type: QCHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers
1
Single-Pole
Two-Pole
Two-Pole
Three-Pole
1
Continuous
Ampere Rating
at 40°C
120/240 Vac
120/240 Vac
240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
15
QCHW1015 1
QCHW2015
QCHW2015H
QCHW3015H
QCHW4015H
1
20
QCHW1020 1
QCHW2020
QCHW2020H
QCHW3020H
QCHW4020H
25
QCHW1025
QCHW2025
QCHW2025H
QCHW3025H
QCHW4025H
1
30
QCHW1030
QCHW2030
QCHW2030H
QCHW3030H
QCHW4030H
35
QCHW1035
QCHW2035
QCHW2035H
QCHW3035H
QCHW4035H
1
40
QCHW1040
QCHW2040
QCHW2040H
QCHW3040H
QCHW4040H
45
QCHW1045
QCHW2045
QCHW2045H
QCHW3045H
QCHW4045H
1
50
QCHW1050
QCHW2050
QCHW2050H
QCHW3050H
QCHW4050H
1
55
QCHW1055
QCHW2055
QCHW2055H
QCHW3055H
QCHW4055H
60
QCHW1060
QCHW2060
QCHW2060H
QCHW3060H
QCHW4060H
1
1
1
Four-Pole
70
QCHW1070
QCHW2070
QCHW2070H
QCHW3070H
QCHW4070H
70
—
QCHW2080
QCHW2080H
QCHW3080H
QCHW4080H
90
—
QCHW2090
QCHW2090H
QCHW3090H
QCHW4090H
100
—
QCHW2100
QCHW2100H
QCHW3100H
QCHW4100H
1
QUICKLAG Type: QHCX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
1
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
15
QHCX1015 1
QHCX2015
—
QHCX3015H
—
1
20
QHCX1020
1
QHCX2020
—
QHCX3020H
—
25
QHCX1025
QHCX2025
—
QHCX3025H
—
1
30
QHCX1030
QHCX2030
—
QHCX3030H
—
QHCX1035
QHCX2035
—
QHCX3035H
—
1
35
40
QHCX1040
QHCX2040
—
QHCX3040H
—
1
45
QHCX1045
QHCX2045
—
QHCX3045H
—
50
QHCX1050
QHCX2050
—
QHCX3050H
—
1
55
QHCX1055
QHCX2055
—
QHCX3055H
—
60
QHCX1060
QHCX2060
—
QHCX3060H
—
1
70
QHCX1070
QHCX2070
—
QHCX3070H
—
1
70
—
QHCX2080
—
QHCX3080H
—
90
—
QHCX2090
—
QHCX3090H
—
100
—
QHCX2100
—
QHCX3100H
—
1
1
1
Four-Pole
QUICKLAG Type: QHCW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
1
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
15
QHCW1015 1
QHCW2015
—
QHCW3015H
—
1
20
QHCW1020 1
QHCW2020
—
QHCW3020H
—
1
25
QHCW1025
QHCW2025
—
—
—
30
QHCW1030
QHCW2030
—
—
—
1
1
Notes
1 Switching duty rated for 120 Vac fluorescent light applications only.
1
Non-automatic switches, see Page V4-T1-42.
1
V4-T1-22
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Four-Pole
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
QUICKLAG Type QCD Miniature Circuit Breakers
●
Flexible power feed
QCD breakers are used
primarily in HVAC and
connection:
industrial applications.
wire size, position
●
●
Single-, two- and
Same breaker size for
three-pole options
entire rating range
●
●
Modular construction
Field mountable
accessories:
●
DIN mounted
finger shroud proof, quick
(symmetrical rail 35 x
connect terminals
7.5 DIN/EN 50 022)
●
Other accessories:
●
QCD same profile as
jumper unit
Type QCR
QUICKLAG Type QCD
Miniature Circuit
Breaker
1
1
1
1
1
1
1
QUICKLAG Type QCD 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
10
QCD1010
QCD2010
—
—
15
QCD1015
QCD2015
QCD2015H
QCD3015H
20
QCD1020
QCD2020
QCD2020H
QCD3020H
25
QCD1025
QCD2025
QCD2025H
QCD3025H
30
QCD1030
QCD2030
QCD2030H
QCD3030H
35
QCD1035
QCD2035
QCD2035H
QCD3035H
40
QCD1040
QCD2040
QCD2040H
QCD3040H
45
QCD1045
QCD2045
QCD2045H
QCD3045H
50
QCD1050
QCD2050
QCD2050H
QCD3050H
55
QCD1055
QCD2055
QCD2055H
QCD3055H
60
QCD1060
QCD2060
QCD2060H
QCD3060H
70
—
QCD2070
QCD2070H
QCD3070H
80
—
QCD2080
QCD2080H
QCD3080H
90
—
QCD2090
QCD2090H
QCD3090H
100
—
QCD2090
QCD2090H
QCD3100H
—
QCD2100
QCD2100H
—
1
1
1
1
1
1
1
1
1
1
1
1
1
QUICKLAG Type QCD Non-Automatic Switches
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
60
—
—
QCD2060NA
—
100
—
—
—
—
1
1
1
1
Dimensions
Approximate Dimensions in Inches (mm)
1
Shipping Data
Number
of Poles
Carton
Quantity
1
Approximate
Weight Lbs (kg)
Dimensions
1
24
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2
12
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3
8
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-23
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF, QCRH, QCFH
Description
1
1
1
1
1
Single-Pole
Two-Pole
QCR (Rear-Mounted Breakers)
Single-Pole
Two-Pole
QCF (Front-Mounted Breakers)
1
1
1
1
1
1
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH
V4-T1-25
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
QCR and QCF Options and Accessories . . . . . . .
V4-T1-27
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . .
V4-T1-40
1
1
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF, QCRH, QCFH
1
Product Description
Application Description
Eaton Type QCR circuit
breakers have as a standard
feature provisions for 35 mm
DIN rail rear mounting with
a spring-loaded release.
Optional clips for individual
mounting are available as a
separate accessory.
QCR and QCF circuit breakers
are only 1/2-inch (12.7 mm)
wide per pole and are
excellent for general purpose
industrial applications where
space savings is required.
1
1
1
1
1
1
1
1
Type QCF have two threaded
steel inserts to facilitate front
mounting with #6–32 steel
screws. The clamp type
terminals are accessible from
the rear of the breaker so that
cables can be accessed
without removal of the
breaker from the front cover.
Features, Benefits
and Functions
●
●
●
●
●
1/2-inch (12.7 mm) wide
per pole
Cable-in/cable-out
Black cases with black
handles
Three position handle:
ON, Tripped (center), OFF
Thermal-magnetic
protection
1
1
1
1
1
1
1
V4-T1-24
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Standards and Certifications
●
●
●
●
●
Built and listed to UL 489
UL File No. E7819
CSA File No. LR48907
Type QCR and QCF circuit
breakers are UL listed
circuit breakers that are
suitable for use as branch
circuit protectors
All ratings 15–60A are
HACR rated
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Product Selection
Cable-In/Cable-Out,
1/2-Inch Wide
1
1
QCR Breaker Catalog Numbers 1234
Continuous
Ampere Rating
at 40°C
Three-Pole
1
Catalog Number
Catalog Number
1
Single-Pole
Two-Pole
Two-Pole
120/240 Vac
120/240 Vac
240 Vac 5
Catalog Number
Catalog Number
QCR Breaker 10 kAIC Interrupting Ratings
10
15
20
25
30
QCR1010
QCR2010
—
—
QCR1010T
QCR2010T
—
—
—
QCR2010P
—
—
QCR1015 6
QCR2015
QCR2015H
QCR3015H
QCR1015T 6
QCR2015T
QCR2015HT
QCR3015HT
—
QCR2015P
—
—
QCR1020 6
QCR2020
QCR2020H
QCR3020H
QCR1020T 6
QCR2020T
QCR2020HT
QCR3020HT
—
QCR2020P
—
—
QCR1025
QCR2025
QCR2025H
QCR3025H
QCR1025T
QCR2025T
QCR2025HT
QCR3025HT
—
QCR2025P
—
—
QCR1030
QCR2030
QCR2030H
QCR3030H
QCR1030T
QCR2030T
QCR2030HT
QCR3030HT
—
QCR2030P
—
—
QCR1035
QCR2035
—
—
—
QCR2035P
—
—
QCR1040
QCR2040
—
—
—
QCR2040P
—
—
QCR1045
QCR2045
—
—
—
QCR2045P
—
—
QCR1050
QCR2050
—
—
—
QCR2050P
—
—
55
QCR1055
QCR2055
—
—
—
QCR2055P
—
—
60 7
QCR1060
QCR2060
—
—
—
QCR2060P
—
—
—
—
QCRH2015T
—
—
QCRH2020
—
—
QCRH2020T
—
—
35
40
45
50
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
QCR Breaker 22 kAIC Interrupting Ratings
15
QCRH1015 6
QCRH1015T
20
6
QCRH1020 6
QCRH1020T
6
QCRH2015
1
1
1
Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection
(#10–32 plus/minus terminal screw provided).
3 Breakers with P Catalog Number Suffix are suitable for terminating two 10 AWG Quick-Connect Type Terminals per
phase on breaker load side.
4 Breakers with Shunt Trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole.
Contact the Customer Support Center at 1-800-356-1243.
5 Breakers with H Catalog Suffix have 240 Vac construction.
6 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications.
7 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-25
1.1
1
Cable-In/Cable-Out,
1/2-Inch Wide
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QCF Breaker Catalog Numbers 123
Single-Pole
Two-Pole
Two-Pole
120/240 Vac
120/240 Vac
240 Vac 4
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
Continuous
Ampere Rating
at 40°C
1
QCF Breaker 10 kAIC Interrupting Ratings
10
1
1
15
1
20
Three-Pole
QCF1010
QCF2010
—
—
QCF1010T
QCF2010T
—
—
QCF1015 5
QCF2015
QCF2015H
QCF3015H
QCF1015T 5
QCF2015T
QCF2015HT
QCF3015HT
QCF1020 5
QCF2020
QCF2020H
QCF3020H
QCF1020T 5
QCF2020T
QCF2020HT
QCF3020HT
QCF1025
QCF2025
QCF2025H
QCF3025H
QCF1025T
QCF2025T
QCF2025HT
QCF3025HT
QCF2030
QCF2030H
QCF3030H
1
25
1
30
QCF1030
1
QCF1030T
QCF2030T
QCF2030HT
QCF3030HT
35
QCF1035
QCF2035
—
—
40
QCF1040
QCF2040
—
—
1
1
1
1
45
QCF1045
QCF2045
—
—
50
QCF1050
QCF2050
—
—
55
QCF1055
QCF2055
—
—
60 6
QCF1060
QCF2060
—
—
QCF Breaker 22 kAIC Interrupting Ratings
15
1
20
1
QCFH1015 5
QCFH2015
—
—
QCFH1015T 5
QCFH2015T
—
—
QCFH1020 5
QCFH2020
—
—
QCFH2020T
—
—
QCFH1020T
1
5
Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection
(#10–32 plus/minus terminal screw provided).
3 Breakers with Shunt Trip Attachment (extra pole required on breaker right-hand side) are available.
Contact the Customer Support Center.
4 Breakers with H Catalog Suffix have 240 Vac construction.
5 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications.
6 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-26
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
QCR and QCF Options and Accessories
QCR and QCF Standard Box
Terminals
Factory-installed line and load
side breaker terminal to
accommodate14 AWG to
4 AWG wire.
Standard Box Terminals
1
QCR and QCF Ring or Spade Lug
Terminals (10 to 30A Ratings
Only)
Factory-installed line and load
side terminals each equipped
with a #10–32 screw suitable
for terminating one 10 AWG
wire with insulated ring or
spade type terminal as shown.
Catalog Suffix “T”
QCR Quick-Connect Terminals
Factory-installed two-prong
quick-connect terminal on
breaker load side suitable for
terminating two 10 AWG wire
with insulated slip-on
terminals as shown. Line side
terminal is the standard type.
Available QCR and QCF
Breaker Accessories
1
Catalog
Number
1
Steel mounting clip
mounts QCR breaker if
individual mounting is
required. Quantity two
required for single- and twopole and four required
for three-pole breakers.
QCRMTGFT
1
Removable padlock
device for single-pole
QCR or QCF breaker.
QCRFPL1P
Removable padlock
device for multi-pole
QCR or QCF breaker.
QCRFPLMP
Padlock bracket assembly for QCR or QCF
single- or multi-pole
breakers (OFF only).
QCRFLOFF
Padlock bracket for
QCR, lock-off only.
QCRPLOFF
Description
1
1
1
1
1
1
1
1
Catalog Suffix “P”
1
1
1
1
Technical Data and Specifications
●
●
●
●
Single-, two- and
three-pole
10 kAIC at 120/240 Vac,
10–60A
22 kAIC at 120/240 Vac,
15–20A
10 kAIC at 240 Vac, 10–30A
●
●
●
3 kAIC at 62.5 Vdc
(single-pole)
3 kAIC at 130 Vdc
(two poles in series)
Normal operating
environment:
●
0–40°C
●
5–95% humidity
(noncondensing)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-27
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
QUICKLAG Type QCGFT Single-Pole
Ground Fault Circuit Breaker
Description
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP
V4-T1-29
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-30
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-30
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . .
V4-T1-40
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP
Product Description
Standards and Certifications
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
5 mA trip sensitivity
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
●
Built and tested to UL 943
QUICKLAG Ground Fault
Equipment Protectors
●
30 mA trip sensitivity
QUICKLAG Ground Fault
Equipment Protectors
●
Built and tested to
UL 1053
1
1
1
1
1
1
1
1
1
1
1
V4-T1-28
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Product Selection
QUICKLAG Type QCGFT
Single-Pole Ground
Fault Circuit Breaker
1
Breaker Catalog Numbers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
120 Vac
120/240 Vac
Catalog Number
Catalog Number
1
1
1
Ground Fault Circuit Breakers—5 mA Sensitivity
QUICKLAG Type: QCGFT 10,000A Interrupting Capacity Thermal-Magnetic Breakers
15
QCGFT1015
QCGFT2015
20
QCGFT1020
QCGFT2020
25
QCGFT1025
QCGFT2025
30
QCGFT1030
QCGFT2030
40
QCGFT1040
QCGFT2040
50
—
QCGFT2050
1
1
1
1
QUICKLAG Type: QCHGFT 22,000A Interrupting Capacity Thermal-Magnetic Breakers
15
QCHGFT1015
QCHGFT2015
20
QCHGFT1020
QCHGFT2020
25
QCHGFT1025
QCHGFT2025
30
QCHGFT1030
QCHGFT2030
1
1
Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
1
15
QCGFEP1015
QCGFEP2015
20
QCGFEP1020
QCGFEP2020
1
25
QCGFEP1025
QCGFEP2025
30
QCGFEP1030
QCGFEP2030
40
QCGFEP1040
QCGFEP2040
50
—
QCGFEP2050
1
1
1
QUICKLAG Type: QCHGFEP 22,000A Interrupting Capacity Thermal-Magnetic Breakers
15
QCHGFEP1015
QCHGFEP2015
20
QCHGFEP1020
QCHGFEP2020
25
QCHGFEP1025
QCHGFEP2025
30
QCHGFEP1030
QCHGFEP2030
1
1
1
Special Application Ground Fault Circuit Protector—5 mA Sensitivity
QUICKLAG Type: QCGFT 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
15
QCGFT1015W1
QCGFT2015W1
20
QCGFT1020W1
QCGFT2020W1
25
QCGFT1025W1
QCGFT2025W1
30
QCGFT1030W1
QCGFT2030W1
40
—
QCGFT2040W1
50
—
QCGFT2050W1
15
QCGFT1015W2
—
20
QCGFT1020W2
—
25
QCGFT1025W2
—
30
QCGFT1030W2
—
1
1
1
1
1
1
Special Application Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
15
QCGFEP1015W1
QCGFEP2015W1
20
QCGFEP1020W1
QCGFEP2020W1
25
QCGFEP1025W1
QCGFEP2025W1
30
QCGFEP1030W1
QCGFEP2030W1
40
—
QCGFEP2040W1
50
—
QCGFEP2050W1
15
QCGFEP1015W2
—
20
QCGFEP1020W2
—
25
QCGFEP1025W2
—
30
QCGFEP1030W2
—
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1
1
1
1
1
1
V4-T1-29
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1
Wiring Diagram
1
Bell Alarm and Auxiliary Contact Schematic
1
Blue
Ground
Fault
Breaker
1
1
1
1
1
Blue Wire
NC
Red
Black Wire
NO
Red Wire
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Dimensions
Approximate Dimensions in Inches (mm)
1
Shipping Data
1
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg)
Dimensions
1
1
20
11.00 (5.0)
12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
2
5
5.00 (2.3)
15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-30
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Contents
BABRP and BABRSP Breakers—
Single- and Two-Pole
Description
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP. . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP
V4-T1-32
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . .
V4-T1-33
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-33
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . .
V4-T1-40
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP
Product Description
Application Description
Features, Benefits and Functions
The BABRP and BABRSP
are bolt-on branch circuit
breakers designed for use in
panelboards. The BRRP is a
plug-on branch circuit breaker
designed for use in loadcenters not manufactured
with breakers with a 1-inch
wide format and are listed on
the “Compatibility list for
Classified Applications”—
Pub. 26271. In addition to
providing conventional branch
circuit protection, they include
a unique solenoid-operated
mechanism that provides for
efficient breaker pulse-on and
pulse-off operation when used
with a suitable controller like
Eaton’s Pow-R-Command™
lighting control system.
These breakers can also be
controlled by pushbutton or
a PLC unit.
Eaton’s BABRP, BABRSP,
BRRP and CLRP breakers are
remotely operated molded
case circuit breakers ideally
suited for lighting control
applications or energy
management applications.
●
●
●
●
●
●
●
●
Bolt-on line-side terminal
(BABRP, BABRSP—
Type BA)
Plug-on line-side terminal
(BRRP—Type BR, CLRP—
Type CL)
Cable connected load-side
terminal
Four-position control
terminal
Bi-metal assembly for
thermal overload
protection
Fast-acting short-circuit
protection
Arc-chute assembly for
fast-acting arc extinction
Three-position handle: OFF,
TRIP (Center), ON
1
●
●
●
●
●
●
●
Handle permits manual
switching when control
power is lost
Mechanical trip indicator
15 and 20A breakers SWD
(switching duty) rated
HID ratings for HID (high
intensity discharge) lighting
All models HACR rated
Status feedback of control
circuit (BABRSP)
Series rated (BABRP,
BABRSP only)
●
BRRP series rated same
as BR breakers
●
BABRP, BABRSP same
as BA breakers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-31
1.1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type QCGFT
Single-Pole Ground
Fault Circuit Breaker
BABRP UL 489 and CSA 22.2 Interrupting
Ratings
BRRP UL 489 and CSA 22.2 Interrupting
Ratings
Interrupting Capacity (Symmetrical Amperes)
Interrupting Capacity (Symmetrical Amperes)
1
Catalog
Number Ampere Vac (50/60 Hz)
120/240 277/480 Number
of Poles Rating 1 120
Number Ampere
of Poles Rating
Vac (50/60 Hz)
120
120/240
Catalog
Number
1
1
1
15
10,000 —
—
BABRP1015
15
10,000
—
BRRP115
20
10,000 —
—
BABRP1020
20
10,000
—
BRRP120
25
10,000 —
—
BABRP1025
25
10,000
—
BRRP125
30
10,000 —
—
BABRP1030
30
10,000
—
BRRP130
15
—
10,000
—
BABRP2015
15
—
10,000
BRRP215
1
20
—
10,000
—
BABRP2020
20
—
10,000
BRRP220
25
—
10,000
—
BABRP2025
25
—
10,000
BRRP225
1
30
—
10,000
—
BABRP2030
30
—
10,000
BRRP230
1
1
2
1
BABRP and BABRSP Wire Harness
1
Catalog
Number
Description
1
This 60-inch (1524.0 mm) wire pigtail provides
SLBKRPTL1
a connection from a single BABRP’s control plug to
a customer’s pushbutton, relay or PLC. Each box
contains 12 pigtails. Wires are 22 AWG, 600V.
Order in multiples of 12.
1
2
CLRP UL 489 and CSA 22.2 Interrupting
Ratings
Interrupting Capacity (Symmetrical Amperes)
Number Ampere
of Poles Rating
1
1
BABRSP UL 489 and CSA 22.2 Interrupting
Ratings
1
1
Interrupting Capacity (Symmetrical Amperes)
Vac (50/60 Hz)
Number Ampere
of Poles Rating 1 120
1
1
Catalog
120/240 277/480 Number
15
10,000 —
—
BABRSP1015
1
20
10,000 —
—
BABRSP1020
1
25
10,000 —
—
BABRSP1025
30
10,000 —
—
BABRSP1030
15
—
10,000
—
BABRSP2015
20
—
10,000
—
BABRSP2020
25
—
10,000
—
BABRSP2025
30
—
10,000
—
BABRSP2030
2
1
1
2
120
120/240
Catalog
Number
15
10,000
—
CLRP115
20
10,000
—
CLRP120
25
10,000
—
CLRP125
30
10,000
—
CLRP130
15
—
10,000
CLRP215
20
—
10,000
CLRP220
25
—
10,000
CLRP225
30
—
10,000
CLRP230
Note
1 Continuous current rating at 40°C.
1
1
1
1
1
1
1
1
1
V4-T1-32
Vac (50/60 Hz)
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Technical Data and Specifications
1
1
Control Circuit for the BABRP and BABRSP
BABRP
BABRSP
Remote
Contact
Remote
Contact
Line
Load
Breaker
Contact
RM
a
1
BKR
a
Red
Black
Off Remote
Coil Status
Blue
Yellow
RM
b
On
Coil
Off Remote
Coil Status
1
1
Blue
RM
a
On
Coil
1
Line
Breaker
Contact
RM
b
1
Yellow
Load
Black
Operation
●
Tripping system—the
BABRP, BABRSP, BRRP
and CLRP circuit breakers
have a permanent trip
unit that contains a factory
preset thermal (overload)
trip element in each pole
●
Operating mechanism—
the BABRP, BABRSP, BRRP
and CLRP circuit breakers
have an over-center toggle
mechanism that provides
quick-make, quick-break
operation. The operating
mechanism is trip free. An
internal cross-bar provides
a common tripping of all
multi-pole circuit breakers
Red
Solenoid Operating Data
●
Power requirements: 24
Vac/dc (20.4V minimum–
30V maximum)
●
Controlled signal:
+AC/DC 8 ms minimum
with zero cross, 300 ms
maximum
●
AC: 1.3 cycles minimum,
18 cycles or 300 ms
maximum
●
DC: 8 ms minimum,
300 ms maximum
●
Maximum duty cycle of
6 OPEN/CLOSE cycles
per minute
●
Current draw: open 1A,
close 3/4A
●
Blue wire: power input
(see power requirements)
●
Black wire: remote opening
●
Red wire: remote closing
●
Yellow wire: feedback
status from power input,
maximum 0.50A draw
(BABRSP only)
Wiring Diagrams
1
1
1
Operating/Application Data
●
Ambient temperature:
0 to 40°C
●
Nominal pulse magnitude:
24 Vac/dc
●
Frequency: 50/60 Hz
●
Maximum breaker cycling:
6 operations per minute
●
Tolerance: +10% to –15%
of nominal voltage
●
Humidity: 0 to 95%
noncondensing
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-33
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
GHBS and GHQRSP
Description
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers
V4-T1-35
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . . . .
V4-T1-36
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-36
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . .
V4-T1-40
Solenoid Operator—Remote-Controlled Latching
for Type GHBS, GBHS and GHQRSP Breakers
Product Description
Eaton’s GHBS, GBHS and
GHQRSP circuit breakers
are bolt-on branch circuit
breakers designed for use
in 277/480 Vac panelboards.
In addition to providing
conventional branch circuit
protection, they include a
unique solenoid-operated
mechanism that provides
for efficient breaker pulse-on
and pulse-off operation
when used with a suitable
controller like Eaton’s
Pow-R-Command lighting
control system.
Features, Benefits
and Functions
●
●
●
●
●
●
●
1
Bolt-on line-side terminal
Cable-connected load-side
terminal
Status switch—remote
status and breaker status
available from internal
auxiliary switches
Bi-metal assembly for
thermal overload
protection
Fast-acting short-circuit
protection
Arc-runner and arc-chute
assembly for fast-acting arc
extinction
Three-position breaker
handle: OFF, TRIP (Center),
ON
●
●
●
●
●
●
Visual indication of the
remotely operated
contact’s position (open,
closed or trip)
Remote override handle
permits manual switching
when control power is lost
15 and 20A breakers SWD
(switching duty) rated.
15 and 20A breakers HID
rated for HID (High
intensity discharge) lighting
All models HACR rated
Series rated with various
Eaton main circuit breakers
1
1
1
1
1
1
V4-T1-34
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Product Selection
GHBS—Single-Pole
1
1
GHBS UL 489 Interrupting Ratings
1
Interrupting Capacity (Symmetrical Amperes)
Number
of Poles
Ampere
Rating 1
Vac (50/60 Hz)
120
240
277/480
Catalog Number
1
15
65,000
—
14,000
GHBS1015D
20
65,000
—
14,000
GHBS1020D
30
65,000
—
14,000
GHBS1030D
15
—
65,000
14,000
GHBS2015D
20
—
65,000
14,000
GHBS2020D
30
—
65,000
14,000
GHBS2030D
2
1
1
1
1
1
GBHS CSA 22.2 Interrupting Ratings (Not UL Listed)
1
Interrupting Capacity (Symmetrical Amperes)
Number
of Poles
1
2
Ampere
Rating 1
1
Vac (50/60 Hz)
347/600
Catalog Number
15
10,000
GBHS1015D
20
10,000
GBHS1020D
15
10,000
GBHS2015D
20
10,000
GBHS2020D
1
1
1
1
GHQRSP UL 489 and CSA 22.2 Interrupting Ratings
Interrupting Capacity (Symmetrical Amperes)
Number
of Poles
Ampere
Rating 1
Vac (50/60 Hz)
120
120/240
277
480Y/277
Catalog Number 2
1
15
65,000
65,000
14,000
14,000
GHQRSP1015
20
65,000
65,000
14,000
14,000
GHQRSP1020
30
65,000
65,000
14,000
14,000
GHQRSP1030
15
65,000
65,000
14,000
14,000
GHQRSP2015
20
65,000
65,000
14,000
14,000
GHQRSP2020
30
65,000
65,000
14,000
14,000
GHQRSP2030
2
1
1
1
1
1
1
Notes
1 Continuous current rating at 40°C.
2 All UL listed circuit breakers are HID (high intensity discharge) rated.
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-35
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1
Technical Data and Specifications
1
1
Solenoid Operating Data
●
Power requirements: 24
Vac/dc (20.4V minimum–
30V maximum)
●
Controlled signal: +AC/
DC 8 ms minimum with
zero cross, 300 ms
maximum
●
AC: 1.3 cycles minimum,
18 cycles or 300 ms
maximum
●
DC: 8 ms minimum,
300 ms maximum
●
Maximum duty cycle of
6 OPEN/CLOSE cycles
per minute
●
Current draw: open 1A,
close 3/4A
●
Blue wire: power input
(see power requirements)
●
Black wire: remote opening
1
Terminal Type
1
Circuit Breaker
Type
Circuit Breaker
Amperes
Screw
Head Type
Terminal
Type
Range
1
GHQRSP
15–20
Slotted
Clamp
#14–#4 AWG
1
1
1
1
1
1
1
1
●
●
Wiring Diagrams
Red wire: remote closing
Yellow wire: feedback
status from power input,
maximum 0.50A draw
Operation
Mechanism manually
operated by external handle
allowing ON, OFF and RESET
operation. Handle assumes a
center TRIP position after
performing protective
response.
Operating/Application Data
●
Ambient temperature:
0–40°C
●
Frequency: 48–62 Hz
●
Humidity: 0–95%
noncondensing
Typical Single-Pole Circuit Breaker Schematic Diagram for
GHBS and GBHS Breakers
Circuit Breaker
Solenoid
Common
AMP Inc.
Conductor
Plug 1
a
Solenoid
Auxiliary
/ Cycle
Maximum
28 Vac
Pulse Source
1 2
28 Vac
Circuit Breaker
Open/Closed
Status
Typical Single-Pole Circuit Breaker Schematic Diagram for
GHQRSP Breakers
GHQRSP
Remote
Breaker
Contact
Contact
Load
Line
1
Status
Blue
1
Black
Yellow
1
Red
1
On
Coil
Off
Coil
Power
Input
1
1
Dimensions
1
Approximate Dimensions in Inches (mm)
1
Dimensions per Pole
1
1
Circuit Breaker Type
Width
Height 2
Length 3
GHQRSP
1.00 (25.4)
4.63 (117.6)
2.81 (71.4)
Notes
1 Purchase separate AMP Inc. conductor plug #640426-3.
2 Excluding line terminal.
3 Excluding handle.
1
1
1
1
1
1
V4-T1-36
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Contents
International Rated
Description
Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . .
V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP. . . . . .
V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . .
V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC
V4-T1-38
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . .
V4-T1-39
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-39
Special Application Breakers, Types HQP, BA, QC . . . .
V4-T1-40
1
1
1
1
1
1
1
1
1
1
1
1
1
International Rated Types HQP, BA, QC, GFMB, GFXBC
1
Product Description
Standards and Certifications
1
QUICKLAG International Circuit
Breakers
●
Bolt-on Type BA
QUICKLAG International Circuit
Breakers
●
Built and test certified to
BS3871, Pt. 1
●
50/60 Hz, 40°C
1
QUICKLAG International Ground
Fault Circuit Breakers
●
Plug-on Type GFMB
●
Cable-in/cable-out Type
GFXBC
1
1
QUICKLAG International Ground
Fault Circuit Breakers
●
Built and test certified to
BS3871, Pt. 1; BS3871,
Section 31-C; BS4293
●
50/60 Hz, 40°C; 30 mA
sensitivity
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-37
1.1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
BAB
Breaker Catalog Numbers
Single-Pole
Two-Pole
Three-Pole
240/415 Vac
240/415 Vac
240/415 Vac
Catalog Number
Catalog Number
Catalog Number
1
Continuous
Ampere Rating
at 40°C
1
3000A Interrupting Capacity (M3) Bolt-On Thermal-Magnetic Circuit Breakers
1
10
BAB1010E
BAB2010E
15
BAB1015E
BAB2015E
BAB3015E
1
16
—
—
—
20
BAB1020E
BAB2020E
BAB3020E
1
25
BAB1025E
BAB2025E
BAB3025E
30
BAB1030E
BAB2030E
BAB3030E
1
32
—
—
—
1
40
BAB1040E
BAB2040E
BAB3040E
50
BAB1050E
BAB2050E
BAB3050E
1
60
BAB1060E
BAB2060E
BAB3060E
70
BAB1070E
BAB2070E
BAB3070E
1
90
—
BAB2090E
BAB3090E
1
100
—
BAB2100E
BAB3100E
6000A Interrupting Capacity (M6) Bolt-On Thermal-Magnetic Circuit Breakers
BAB3010E
1
15
BAB1015HE
BAB2015HE
BAB3015HE
20
BAB1020HE
BAB2020HE
BAB3020HE
1
25
BAB1025HE
BAB2025HE
BAB3025HE
30
BAB1030HE
BAB2030HE
BAB3030HE
1
40
BAB1040HE
BAB2040HE
BAB3040HE
1
50
BAB1050HE
BAB2050HE
BAB3050HE
60
BAB1060HE
BAB2060HE
BAB3060HE
1
70
BAB1070HE
BAB2070HE
BAB3070HE
90
—
BAB2090HE
BAB3090HE
1
100
—
BAB2100HE
BAB3100HE
1
Breaker Catalog Numbers—Ground Fault Single-Pole 30 mA Sensitivity
1
Continuous
Ampere Rating
at 40°C
1
240/415 Vac
Catalog Number
3000A Interrupting Capacity (M3) Plug-On Thermal-Magnetic Circuit Breakers
1
10
GFMB110B2
1
15
GFMB115B2
16
GFMB116B2
1
20
GFMB120B2
25
GFMB125B2
1
30
GFMB130B2
32
GFMB132B2
1
40
GFMB140B2
1
Note
For other 240/415V applications, please contact the Customer Support Center at 1-800-356-1243.
1
1
1
V4-T1-38
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Technical Data and Specifications
1
Interrupting Ratings
Ratings
Suffix E
1
Suffix HE
1
International Circuit Breakers
NEMA®
120/240 Vac
10,000 AIC
10,000 AIC
BS3871 220/380,
240/415 Vac
3000 AIC
6000 AIC
1
1
International Ground Fault Circuit Breakers
BS3871 220/380,
240/415 Vac
1
3000 AIC
1
1
Dimensions
Approximate Dimensions in Inches (mm)
1
Shipping Data
Miniature
Circuit Breaker
QUICKLAG Type B
Number
of Poles
Standard Carton
Quantity
Approximate Carton
Weight Lbs (kg)
1
Approximate
Standard Carton
1
1
24
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2
12
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3
8
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1
20
11.00 (5.0)
12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
1
QUICKLAG Ground Fault
Type P—All
1
Types B and C—All
1
20
11.00 (5.0)
12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7)
Types P and B—All
2
5
5.00 (2.3)
12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-39
1.1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Contents
QUICKLAG Type P Switching Neutral
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGFT, QPHGFT, QPGFEP, QPHGFEP
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . .
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bolt-On Ground Fault and Equipment Protectors,
Types QBGFT, QBHGFT, QBGFEP, QBHGFEP . . . . .
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGFT, QCHGFT, QCGFEP, QCHGFEP
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . .
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . .
International Rated Types HQP, BA, QC, GFMB, GFXBC
Special Application Breakers, Types HQP, BA, QC
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory Modifications and Installed Terminals . .
Technical Data and Specifications . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1
1
1
1
1
1
1
1
1
1
1
1
Special Application Breakers, Types HQP, BA, QC
1
Product Description
1
Breakers
●
Plug-on Type HQP:
10–30A, single- and
two-pole, 10 kAIC
●
Bolt-on Type BA: 10–30A,
single- and two-pole,
10 kAIC
●
Cable-in Type QC: 10–30A,
single- and two-pole,
10 kAIC
1
1
1
1
1
1
1
1
1
QUICKLAG HID (High Intensity
Discharge) Breakers
●
Plug-on Type HQP:
15–60A, single- and
two-pole, 10 kAIC
●
Bolt-on Type BA: 15–60A,
single- and two-pole,
10 kAIC
●
Cable-in Type QC: 15–60A,
single- and two-pole,
10 kAIC
Breakers designed
specifically for use with high
intensity discharge (HID)
lighting applications. (UL
listed as standard lighting
breakers.)
Molded Case Switches—Nonautomatic QUICKLAG Molded
Case Switch
●
Plug-on Type HQP: 50,
60,100A, single-, two- and
three-pole
●
Bolt-on Type BA: 50,
60,100A, single-, two- and
three-pole
●
Cable-in Type QC: 50,
60,100A, single-, two- and
three-pole
1
1
1
1
1
V4-T1-40
V4-T1-8
V4-T1-11
V4-T1-14
V4-T1-17
V4-T1-20
V4-T1-24
V4-T1-28
V4-T1-31
V4-T1-34
V4-T1-37
V4-T1-41
V4-T1-43
V4-T1-46
V4-T1-47
V4-T1-48
Standards and Certifications
●
Switching neutral QUICKLAG
breakers available in singleand two-pole configurations,
plus neutral pole for
applications in accordance
with NEC® 514.5, 240.22 and
380.2. A single-pole device
takes two pole spaces, and a
two-pole device takes three
pole spaces.
Page
V4-T1-2
V4-T1-5
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
All products UL and
CSA listed
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1.1
Product Selection
QUICKLAG Type P
Switching Neutral
1
1
Breaker Catalog Numbers
Continuous
Ampere Rating
at 40°C
Single-Pole
Two-Pole
Two-Pole
Three-Pole
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
1
QUICKLAG Type: HQP Switching Neutral Thermal-Magnetic Breakers
10
HQP2010B
HQP3010B
—
—
15
HQP2015B
HQP3015B
—
—
20
HQP2020B
HQP3020B
—
—
25
HQP2025B
HQP3025B
—
—
30
HQP2030B
HQP3030B
—
—
1
1
1
1
QUICKLAG Type: BA Switching Neutral Thermal-Magnetic Breakers
10
BAB2010C
BAB3010C
—
—
15
BAB2015C
BAB3015C
—
—
20
BAB2020C
BAB3020C
—
—
25
BAB2025C
BAB3025C
—
—
30
BAB2030C
BAB3030C
—
—
1
1
1
QUICKLAG Type: QC Switching Neutral Thermal-Magnetic Breakers
10
QC2010B
QC3010B
—
—
15
QC2015B
QC3015B
—
—
20
QC2020B
QC3020B
—
—
25
QC2025B
QC3025B
—
—
30
QC2030B
QC3030B
—
—
1
1
1
QUICKLAG Type: HQP HID (High Intensity Discharge) Thermal-Magnetic Breakers
15
HQP1015D
HQP2015D
—
—
20
HQP1020D
HQP2020D
—
—
25
HQP1025D
HQP2025D
—
—
30
HQP1030D
HQP2030D
—
—
35
HQP1035D
HQP2035D
—
—
40
HQP1040D
HQP2040D
—
—
50
HQP1050D
HQP2050D
—
—
60
HQP1060D
HQP2060D
—
—
1
1
1
1
1
QUICKLAG Type: BA HID (High Intensity Discharge) Thermal-Magnetic Breakers
15
BAB1015D
BAB2015D
—
—
20
BAB1020D
BAB2020D
—
—
25
BAB1025D
BAB2025D
—
—
30
BAB1030D
BAB2030D
—
—
35
BAB1035D
BAB2035D
—
—
40
BAB1040D
BAB2040D
—
—
50
BAB1050D
BAB2050D
—
—
60
BAB1060D
BAB2060D
—
—
1
1
1
1
1
1
QUICKLAG Type: QC HID (High Intensity Discharge) Thermal-Magnetic Breakers
15
QC1015D
QC2015D
—
—
20
QC1020D
QC2020D
—
—
25
QC1025D
QC2025D
—
—
30
QC1030D
QC2030D
—
—
35
QC1035D
QC2035D
—
—
40
QC1040D
QC2040D
—
—
50
QC1050D
QC2050D
—
—
60
QC1060D
QC2060D
—
—
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-41
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1
Breaker Catalog Numbers, continued
Single-Pole
Two-Pole
Two-Pole
1
Continuous
Ampere Rating
at 40°C
120/240 Vac
120/240 Vac
240 Vac
240 Vac
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
QUICKLAG Type: HQP Non-Automatic Switches
1
50
HQP1050N
—
HQP2050N
HQP3050N
60
HQP1060N
—
HQP2060N
HQP3060N
1
100
HQP1100N
—
HQP2100N
HQP3100N
1
50
BAB1050N
—
BAB2050N
BAB3050N
60
BAB1060N
—
BAB2060N
BAB3060N
1
100
BAB1100N
—
BAB2100N
BAB3100N
1
50
QC1050N
—
QC2050N
QC3050N
1
60
QC1060N
—
QC2060N
QC3060N
100
QC1100N
—
QC2100N
QC3100N
1
QUICKLAG Type: QCD Non-Automatic Switches
1
60
—
—
QCD2060NA
—
100
—
—
—
—
Three-Pole
QUICKLAG Type: BA Non-Automatic Switches
QUICKLAG Type: QC Non-Automatic Switches
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-42
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Accessories 1
1
1
Handle Locks: Non-Padlockable 2
QL1NPL
Description
Order in Multiples of
Catalog Number
QUICKLAG Type P, B, C—single-pole
10
QL1NPL
1
1
1
1
QL23NPL
QUICKLAG Type P, B, C—two- and three-pole
10
1
QL23NPL
1
1
1
1
1
Handle Locks: Padlockable 2
QL1PL
Description
Order in Multiples of
Catalog Number
QUICKLAG Type P, B, C—single-pole
10
QL1PL
1
1
1
1
1
QL123PL
QUICKLAG Type P, B and ground fault—single-, two- and three-pole
10
1
QL123PL
1
1
1
QC123PL
QUICKLAG Type C —single-, two- and three-pole
10
1
QC123PL
1
1
1
QUICKLAG Type P, B—single-, two- and three-pole (off only)
10
QL123PLOFF
QUICKLAG Type C—single-, two- and three-pole (off only)
10
QC123PLOFF
1
1
Notes
1 See Page V4-T1-27 for QCR and QCF accessories.
2 Can lock in ON or OFF position.
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-43
1.1
Industrial Circuit Breakers
Mounting Hardware
1
1
Miniature Circuit Breakers and Supplementary Protectors
Description
Order in Multiples of
Catalog Number
QCFCLIP
QUICKLAG Type C face mounting clip
24
QCFCLIP
QC1FP
QUICKLAG Type C face mounting plate—single-pole
10
QC1FP
QC2FP
QUICKLAG Type C face mounting plate—two-pole
10
QC2FP
QC3FP
QUICKLAG Type C face mounting plate—three-pole
10
QC3FP
QUICKLAG Type C face mounting plate and lock-off (off only)—two-pole 1
10
QC2FPLOFF
QUICKLAG Type C face mounting plate and lock-off (off only)—three-pole
10
QC3FPLOFF
QCBCLIP
QUICKLAG Type C base mounting clamp
10
QCBCLIP
QC6BP
QUICKLAG Type mounting plate—six poles total
10
QC6BP
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Note
1 Suitable for ground fault breakers.
1
1
V4-T1-44
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Mounting Hardware, continued
Description
QCDJ4
Order in Multiples of
Catalog Number
QUICKLAG Type C base mounting plate—six poles total—heavy-duty screw-secured
10
QC6BPS
QUICKLAG Type C (QCD) 2-way jumper unit with cover
10
QCDJ2
QUICKLAG Type C (QCD) 4-way jumper unit with cover
10
QCDJ4
1
1
1
1
1
QCDINADAPT
1
QUICKLAG Type C (QCD) 6-way jumper unit with cover
10
QCDJ6
QUICKLAG Type C (QCD) 2-way jumper unit, no cover
10
QCDJ2T
QUICKLAG Type C (QCD) 4-way jumper unit, no cover
10
QCDJ4T
QUICKLAG Type C (QCD) 6-way jumper unit, no cover
10
QCDJ6T
QUICKLAG Type QCD Finger protection attachment
10
QCDFP
QUICKLAG Type QCD 4-prong Quick Connect
10
QCDQUICK
QUICKLAG Type C DIN rail adapter
6
QCDINADAPT
1
1
1
1
1
QCDRING
QUICKLAG Type QCD ring lug attachment
10
1
QCDRING
1
1
1
1
Dummy Breakers
Description
Order in Multiples of
Catalog Number
QUICKLAG Type P
1
HQP1000
QUICKLAG Type B
1
BAB1000
QUICKLAG Type C
1
QC1000
QUICKLAG Type C clear choice breaker
4
QC30SAMPLE
1
1
1
1
QCRSPACER
Miscellaneous
Description
Order in Multiples of
Catalog Number
QUICKLAG Type C Spacer
1
QCRSPACER
1
1
1
1
1
QL1HT
Handle Tie
Description
Order in Multiples of
Catalog Number
QUICKLAG handle tie—single-pole
100
QL1HT
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-45
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
1
Factory Modifications and Installed Terminals
1
Factory Modifications 1
Type of Modification
Breaker Type
Catalog Suffix
Shunt trip (requires one extra pole space on right side)
120, 208, 240 Vac
Draws 2.6A at 120V, draws 11A at 24 Vdc
QUICKLAG Types P, B and C
S
Shunt trip (requires one extra pole space on right side)
24, 48 Vac/dc
Draws 2.6A at 120V, draws 11A at 24 Vdc
QUICKLAG Types P, B and C
S1
Special calibration (50°C) (no UL)
QUICKLAG Types P, B and C
V
Shock testing
QUICKLAG Types P, B and C
L
1
Freeze testing
QUICKLAG Types P, B and C
Y
Moisture-fungus treatment
QUICKLAG Types P, B, C and ground fault
F
1
Marine duty
QUICKLAG Types P, B, C
H08
1
Naval duty
QUICKLAG Types P, B, C
H09
400 Hz calibration
QUICKLAG Types P, B, C
G
Specific DC ratings (breaker marked with a max. Vdc rating)
QUICKLAG Types P, B, C
Q thru Q9 2
Description
Order in Multiples of
Catalog Number
1
1
1
1
1
1
1
Spare Terminal Hardware Screws (Lugs not Included)
Terminal Type
1
QUICKLAG terminal screw
10
QLLDTSA
1
2
QUICKLAG terminal screw
10
QLLDTSB
1
3
QUICKLAG terminal screw
10
QLLDTSC
5
QUICKLAG binding head terminal screw and clamp
10
QLBHTSE
6 and 7
QUICKLAG terminal screw
10
QLLNTSFG
1
1
Notes
1 Contact Eaton for factory modifications available for QCR and QCF breakers.
2 Q = 32 Vdc; Q1 = 32–40 Vdc; Q2 = 37.5 Vdc; Q3 = 45 Vdc; Q4 = 48 Vdc; Q5 = 50 Vdc; Q6 = 62.5 Vdc; Q7 = 75 Vdc (2P); Q8 = 80 Vdc (2P); Q9 = 125 Vdc (QCR 2P); Q10 = 62.5 Vdc (QCR 1P).
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-46
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Technical Data and Specifications
1
Factory-Installed Breaker Terminals
Continuous
Ampere
Rating
Standard Line Terminal
Standard Load Terminal
Terminal Wire
Type
Type
Terminal
Type
Wire
Type
Wire
Range (AWG)
Line
Load
QUICKLAG Type P
HQP, QPHW,
QHPX, QHPW
10–30
Plug-on female clips that mate
with the bus stabs
1
Cu/Al
14–4
N/A
3
2
Cu/Al
14–4
N/A
3
3
Cu/Al
8–1/0
N/A
—
QUICKLAG ground fault
QPGFT, QPGFEP,
QPHGFT, QPHGFEP
10–40
Plug-on female clips that mate
with the bus stabs
1 (single-pole)
Cu/Al
14–4
N/A
3
1
Cu/Al
—
N/A
3
1
Cu
14–8
N/A
—
Extended tangs that bolt
directly to the bus
1 (single- and two-pole)
Cu/Al
14–4
N/A
3
2 (three-pole)
Cu/Al
14–4
N/A
3
3
Cu/Al
8–1/0
N/A
—
1 (single-pole)
Cu/Al
14–4
N/A
N/A
Breaker
Type
35–50
Wire
Range (AWG)
55–125
10–40
10–30
QUICKLAG Type B
BAB, QBHW,
HBAX, HBAW
10–40
35–50
55–125
QUICKLAG ground fault
QBGFT, QBGFEP,
QBHGFEP, QBHGFT
10–40
10–40
Extended tangs that bolt
directly to the bus
10–30
QUICKLAG Type C
QC, QCHW,
QHCX, QHCW
QUICKLAG
QCR, QCF
QUICKLAG ground fault
QCGFT, QCGFEP,
QCHGFT, QCHGFEP
QUICKLAG
QCD
1
Optional Terminals
1
Cu/Al
14–8
N/A
N/A
1
Cu
14–8
N/A
N/A
1
1
1
1
1
1
5
Cu/Al
TBD
5
Cu/Al
14–10
6, 7
6, 7, 8
25–60
6
Cu/Al
TBD
2
Cu/Al
14–4
5, 7
5, 6, 7, 8
70–100
7
Cu/Al
TBD
3
Cu/Al
8–1/0
5
5, 7, 8
10–55
1
Cu/Al
TBD
1
Cu/Al
14–4
N/A
N/A
60
1
Cu
TBD
1
Cu
14–4
N/A
N/A
10–20
6
Cu/Al
TBD
14–8
Cu/Al
14–4
6, 7
5
6
Cu/Al
TBD
1
Cu/Al
14–4
5, 7
5
—
10–30
6
—
—
—
—
—
—
10–60
9
Cu/Al
14–4
9
Cu/Al
14–4
See Accessories
70–100
10
Cu
4–1/0
10
Cu
4–1/0
See Accessories
2
3
1
1
10–20
25–50
1
1
1
1
1
1
1
1
5
1
1
Steel Box Lug
6
Steel Box Lug
7
Steel Box Lug
8
1
Steel Ring Type
9
1
10
1
4-Prong Quick Connect
Aluminum Box Lug
Aluminum Box Lug
QCD Terminal Assembly
10–60A
QCD Terminal Assembly
70–100A
1
1
Note
1 Clamp on line side only.
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-47
1.1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Miniature
Circuit Breaker
Number
of Poles
Standard
Carton
Quantity
Approximate
Carton Weight
Lbs (kg)
Approximate Standard
Carton
QUICKLAG Types B, P, C–all
1
24
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1
QUICKLAG Types B, P, C–all
2
12
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1
QUICKLAG Types B, P, C–all
3
8
9.00 (4.1)
12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
QUICKLAG ground fault Type P–all
1
20
11.00 (5.0)
12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
1
1
Types B and C–all
1
20
11.00 (5.0)
12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7)
Types P and B–all
2
5
5.00 (2.3)
12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-48
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
1.2
Contents
FAZ-NA Circuit Breakers
Description
Page
FAZ-NA Circuit Breakers
Catalog Number Selection . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .
V4-T1-50
V4-T1-51
V4-T1-55
V4-T1-57
V4-T1-66
1
1
1
1
1
1
1
1
Optimum and Efficient Protection for Every Application
1
1
1
FAZ-NA Circuit Breakers
Product Overview
Features
Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s FAZ-NA DIN rail
mountable circuit breaker is
designed for use in branch
service applications.
●
Powerful Offering for Machine
and System Builders
The FAZ-NA is available with
B, C and D characteristics in
accordance with UL® 489,
CSA® C22.2 No.5; UL 1077,
CSA C22.2 No.235 and IEC
60947-2. These devices are
CE marked.
Application Description
●
●
●
●
●
Feeder and branch circuit
protection for:
●
●
●
●
●
●
●
●
●
●
●
Convenience receptacle
circuits (internal/external)
Motor control circuits
Load circuits leaving the
equipment (external)
HACR internal/external
equipment (heating, air
conditioning, refrigeration)
PLC I/O points
Computers
Power supplies
Control instrumentation
Relays
UPS
Power conditioners
●
●
Complete range of UL 489
listed DIN rail mounted
miniature circuit breakers
up to 40A current rating
Standard ratings of 10 kAIC
up to 277/480 Vac
Select amperages available
at 14 kAIC up to 277/480
Vac and 10 kAIC up to 125
Vdc per pole
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage the
circuit
Suitable for branch circuit
device protection
Thermal-magnetic
overcurrent protection
●
Three levels of shortcircuit protection,
categorized by B, C
and D curves
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
●
●
●
●
●
●
●
●
●
SWD (switching duty)—
suitable for switching
fluorescent lighting loads
(In ≤ 20A)
Fulfill UL 489, CSA C22.2
No.5 and also IEC 60947-2
Standard
For use in applications for
which UL 1077 or CSA
C22.2 No.235 are also
allowed
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Separate version for ringtongue connection (Type
FAZ-RT), terminal screws
can be removed (on
both sides)
Module width of only
17.7 mm (per pole)
Contact Position Indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing the
toggle in ON or OFF
position
1
Device Printing on Front and Side
Installation options
1
These branch circuit breakers
are available in two terminal
configurations: standard box
terminals that accept multiple
conductors and ring-tongue
terminals, ideally suited to
demanding requirements of
the semi-conductor industry.
All breakers mount on
standard 35 mm DIN rail.
Bus connectors and feeder
terminal facilitate mounting
and wiring of multiple
miniature circuit breaker
arrays in control panel
assemblies. These circuit
breakers can also be
reverse feed.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-49
1.2
1
1
1
FAZ-NA complies with
the latest national and
international standards.
1
1
1
1
●
●
UL 489
●
Standard for molded
case circuit breakers
(MCCB) for feeder and
branch circuit protection
●
Products meet the
requirements of the
National Electrical Code®
(NEC®)
●
CSA C22.2 No.5
●
Standard for molded
case circuit breakers
(MCCB) for feeder and
branch circuit protection
(corresponds closely to
UL 489 Standard)
●
Products meet the
requirements of the
Canadian Electrical Code
(CEC)
1
1
●
●
1
1
UL 489 DIN Rail Miniature Circuit Breakers
Standards and Certifications
1
1
Miniature Circuit Breakers and Supplementary Protectors
RoHS compliant
VDE compliant
ABS compliant
Catalog Number Selection
1
FAZ C 6 / 1 NA SP
1
Breaker Family
1
FAZ = FAZ UL
circuit breaker
Single Package
Trip
Characteristics 1
B = 3–5X In
C = 5–10X In
D = 10–20X In
1
1
1
1
1
1
Terminal
Ampere Rating 2
0.5 =
1 =
1.5 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
0.5A
1A
1.5A
2A
3A
4A
5A
6A
7A
8A
10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
35 = 32A
40 = 40A
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
Notes
1 I = Rated current for instantaneous trip characteristics.
n
2 B curve starts at 1 ampere.
1
1
1
1
1
1
1
1
V4-T1-50
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
NA = UL 489 branch
circuit with screw
terminals
RT = UL 489 branch
circuit with ring
tongue terminals
DC = UL 489 branch
circuit at 125 Vdc
per pole
SP
= Single package for
C and D curve
single-pole only
Blank = Standard
packaging
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
1
1.45
FAZ-NA B Curve
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
●
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
●
Current limiting device
●
UL file number E235139
1.13
Product Selection
2.55 I :
N
1
Type B: 3 x I : t > 0.1 s
N
1
7200
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
600
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Specified tripping current
IT = 1.45 x IN for t < 1 h
300
Type B: 5 x I : t < 0.1 s
N
1
120
1
60
1
30
1
t [sec]
10
5
1
2
1
1
0.5
1
0.2
3
0.1
1
B
2
0.05
0.02
1
0.01
0.005
1
0.002
0.001
1
0.0005
1
2
3
4
5
6 7 8 9 10
15
20
30
40
50
1
I / IN
Single-Pole
FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC B Curve (15–25A)
Single-Pole 1
Catalog
Amperes Number
Two-Pole
Three-Pole
Catalog
Number
Catalog
Number
Single-Pole
Single-Pole 1 Two-Pole
Catalog
Amperes Number
B Curve (3–5X In Current Rating)
Two-Pole
Three-Pole
1
FAZ-B1/1-NA
FAZ-B1/2-NA
1.5
FAZ-B1.5/1-NA FAZ-B1.5/2-NA FAZ-B1.5/3-NA
2
FAZ-B2/1-NA
FAZ-B2/2-NA
FAZ-B2/3-NA
3
FAZ-B3/1-NA
FAZ-B3/2-NA
FAZ-B3/3-NA
4
FAZ-B4/1-NA
FAZ-B4/2-NA
FAZ-B4/3-NA
5
FAZ-B5/1-NA
FAZ-B5/2-NA
FAZ-B5/3-NA
6
FAZ-B6/1-NA
FAZ-B6/2-NA
FAZ-B6/3-NA
7
FAZ-B7/1-NA
FAZ-B7/2-NA
FAZ-B7/3-NA
8
FAZ-B8/1-NA
FAZ-B8/2-NA
FAZ-B8/3-NA
10
FAZ-B10/1-NA FAZ-B10/2-NA FAZ-B10/3-NA
FAZ-B13/1-NA FAZ-B13/2-NA FAZ-B13/3-NA
15
FAZ-B15/1-NA FAZ-B15/2-NA FAZ-B15/3-NA
16
FAZ-B16/1-NA FAZ-B16/2-NA FAZ-B16/3-NA
20
FAZ-B20/1-NA FAZ-B20/2-NA FAZ-B20/3-NA
25
FAZ-B25/1-NA FAZ-B25/2-NA FAZ-B25/3-NA
30
FAZ-B30/1-NA FAZ-B30/2-NA FAZ-B30/3-NA
32
FAZ-B32/1-NA FAZ-B32/2-NA FAZ-B32/3-NA
35 2
FAZ-B35/1-NA FAZ-B35/2-NA FAZ-B35/3-NA
2
FAZ-B40/1-NA FAZ-B40/2-NA FAZ-B40/3-NA
40
Catalog
Number
Two-Pole
Three-Pole
FAZ-B1/2-RT
1
Catalog
Number
1
1
1
FAZ-B1/1-RT
1.5
FAZ-B1.5/1-RT FAZ-B1.5/2-RT FAZ-B1.5/3-RT
2
FAZ-B2/1-RT
FAZ-B2/2-RT
FAZ-B2/3-RT
3
FAZ-B3/1-RT
FAZ-B3/2-RT
FAZ-B3/3-RT
4
FAZ-B4/1-RT
FAZ-B4/2-RT
FAZ-B4/3-RT
5
FAZ-B5/1-RT
FAZ-B5/2-RT
FAZ-B5/3-RT
6
FAZ-B6/1-RT
FAZ-B6/2-RT
FAZ-B6/3-RT
7
FAZ-B7/1-RT
FAZ-B7/2-RT
FAZ-B7/3-RT
8
FAZ-B8/1-RT
FAZ-B8/2-RT
FAZ-B8/3-RT
10
FAZ-B10/1-RT
FAZ-B10/2-RT
FAZ-B10/3-RT
13
FAZ-B13/1-RT
FAZ-B13/2-RT
FAZ-B13/3-RT
15
FAZ-B15/1-RT
FAZ-B15/2-RT
FAZ-B15/3-RT
16
FAZ-B16/1-RT
FAZ-B16/2-RT
FAZ-B16/3-RT
20
FAZ-B20/1-RT
FAZ-B20/2-RT
FAZ-B20/3-RT
25
FAZ-B25/1-RT
FAZ-B25/2-RT
FAZ-B25/3-RT
30
FAZ-B30/1-RT
FAZ-B30/2-RT
FAZ-B30/3-RT
32
FAZ-B32/1-RT
FAZ-B32/2-RT
FAZ-B32/3-RT
35 2
FAZ-B35/1-RT
FAZ-B35/2-RT
FAZ-B35/3-RT
40 2
FAZ-B40/1-RT
FAZ-B40/2-RT
FAZ-B40/3-RT
FAZ-B1/3-RT
1
1
1
1
1
1
1
1
1
1
1
1
Notes
1 Two-piece order. Quantities of two per box.
2 240 Vac rated only.
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1
Three-Pole
B Curve with Ring-Tongue Terminals
(3–5X In Current Rating)
FAZ-B1/3-NA
13
FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
B Curve (15–25A)
1
V4-T1-51
1.2
1
1
FAZ-NA C Curve
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
●
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
●
Current limiting device
●
UL file number E235139
7200
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
300
60
30
t [sec]
10
1
5
2
1
1
0.5
0.2
1
2
0.1
1
0.05
1
C
0.02
0.01
0.005
1
0.002
0.001
1
0.0005
1
1
2
3
4
5
6 7 8 9 10
15
20
30
40
50
I / IN
Single-Pole
1
FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC C Curve (15–25A)
Single-Pole 1
1
Catalog
Amperes Number
1
Two-Pole
Three-Pole
Catalog
Number
Catalog
Number
Single-Pole
FAZ-C0.5/1-NA-SP FAZ-C0.5/2-NA FAZ-C0.5/3-NA
1
FAZ-C1/1-NA-SP
1.5
FAZ-C1.5/1-NA-SP FAZ-C1.5/2-NA FAZ-C1.5/3-NA
2
FAZ-C2/1-NA-SP
FAZ-C2/2-NA
FAZ-C2/3-NA
3
FAZ-C3/1-NA-SP
FAZ-C3/2-NA
FAZ-C3/3-NA
4
FAZ-C4/1-NA-SP
FAZ-C4/2-NA
FAZ-C4/3-NA
5
FAZ-C5/1-NA-SP
FAZ-C5/2-NA
FAZ-C5/3-NA
6
FAZ-C6/1-NA-SP
FAZ-C6/2-NA
FAZ-C6/3-NA
7
FAZ-C7/1-NA-SP
FAZ-C7/2-NA
FAZ-C7/3-NA
8
FAZ-C8/1-NA-SP
FAZ-C8/2-NA
FAZ-C8/3-NA
10
FAZ-C10/1-NA-SP FAZ-C10/2-NA FAZ-C10/3-NA
13
FAZ-C13/1-NA-SP FAZ-C13/2-NA FAZ-C13/3-NA
15
FAZ-C15/1-NA-SP FAZ-C15/2-NA FAZ-C15/3-NA
1
16
FAZ-C16/1-NA-SP FAZ-C16/2-NA FAZ-C16/3-NA
1
20
FAZ-C20/1-NA-SP FAZ-C20/2-NA FAZ-C20/3-NA
25
FAZ-C25/1-NA-SP FAZ-C25/2-NA FAZ-C25/3-NA
1
30
FAZ-C30/1-NA-SP FAZ-C30/2-NA FAZ-C30/3-NA
32
FAZ-C32/1-NA-SP FAZ-C32/2-NA FAZ-C32/3-NA
1
35 2
FAZ-C35/1-NA-SP FAZ-C35/2-NA FAZ-C35/3-NA
40 2
FAZ-C40/1-NA-SP FAZ-C40/2-NA FAZ-C40/3-NA
1
Two-Pole
1
1
1
Three-Pole
1
1
FAZ-C1/2-NA
FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
C Curve (15–25A)
Single-Pole 1
Catalog
Amperes Number
C Curve (5–10X In Current Rating)
0.5
1
Type C: 10 x I : t < 0.1 s
N
120
1
1
Type C: 5 x I : t > 0.1 s
N
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
1
1
1.45
UL 489 DIN Rail Miniature Circuit Breakers
1.13
1
Miniature Circuit Breakers and Supplementary Protectors
Two-Pole
Three-Pole
Catalog
Number
Catalog
Number
C Curve with Ring-Tongue Terminals
(5–10X In Current Rating)
FAZ-C1/3-NA
Two-Pole
Three-Pole
1
0.5
FAZ-C0.5/1-RT-SP FAZ-C0.5/2-RT FAZ-C0.5/3-RT
1
FAZ-C1/1-RT-SP
1.5
FAZ-C1.5/1-RT-SP FAZ-C1.5/2-RT FAZ-C1.5/3-RT
2
FAZ-C2/1-RT-SP
FAZ-C2/2-RT
FAZ-C2/3-RT
3
FAZ-C3/1-RT-SP
FAZ-C3/2-RT
FAZ-C3/3-RT
4
FAZ-C4/1-RT-SP
FAZ-C4/2-RT
FAZ-C4/3-RT
5
FAZ-C5/1-RT-SP
FAZ-C5/2-RT
FAZ-C5/3-RT
6
FAZ-C6/1-RT-SP
FAZ-C6/2-RT
FAZ-C6/3-RT
7
FAZ-C7/1-RT-SP
FAZ-C7/2-RT
FAZ-C7/3-RT
8
FAZ-C8/1-RT-SP
FAZ-C8/2-RT
FAZ-C8/3-RT
10
FAZ-C10/1-RT-SP FAZ-C10/2-RT FAZ-C10/3-RT
13
FAZ-C13/1-RT-SP FAZ-C13/2-RT FAZ-C13/3-RT
15
FAZ-C15/1-RT-SP FAZ-C15/2-RT FAZ-C15/3-RT
16
FAZ-C16/1-RT-SP FAZ-C16/2-RT FAZ-C16/3-RT
20
FAZ-C20/1-RT-SP FAZ-C20/2-RT FAZ-C20/3-RT
25
FAZ-C25/1-RT-SP FAZ-C25/2-RT FAZ-C25/3-RT
30
FAZ-C30/1-RT-SP FAZ-C30/2-RT FAZ-C30/3-RT
FAZ-C1/2-RT
FAZ-C1/3-RT
32
FAZ-C32/1-RT-SP FAZ-C32/2-RT FAZ-C32/3-RT
35 2
FAZ-C35/1-RT-SP FAZ-C35/2-RT FAZ-C35/3-RT
40 2
FAZ-C40/1-RT-SP FAZ-C40/2-RT FAZ-C40/3-RT
Notes
1 Option for single packaging on single-pole C and D curves only;
add suffix SP when ordering.
2 240 Vac rated only.
1
V4-T1-52
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.2
Miniature Circuit Breakers and Supplementary Protectors
1
1.45
FAZ-NA D Curve
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
●
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
●
Current limiting device
●
UL file number E235139
1.13
UL 489 DIN Rail Miniature Circuit Breakers
7200
2.55 I :
N
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
300
1
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Type D: 10 x I : t > 0.1 s
N
1
Type D: 20 x I : t < 0.1 s
N
1
120
1
60
30
1
t [sec]
10
5
1
2
1
1
1
0.5
0.2
1
3
0.1
2
0.05
D
1
0.02
0.01
0.005
1
0.002
0.001
1
0.0005
1
2
3
4
5
6 7 8 9 10
15
20
30
40
50
1
I / IN
Single-Pole
FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC D Curve (13–20A)
Single-Pole 1
Catalog
Amperes Number
Two-Pole
Catalog
Number
Single-Pole
Three-Pole
Single-Pole
Catalog
Number
Two-Pole
Three-Pole
FAZ-D0.5/1-NA-SP FAZ-D0.5/2-NA FAZ-D0.5/3-NA
1
FAZ-D1/1-NA-SP
1.5
FAZ-D1.5/1-NA-SP FAZ-D1.5/2-NA FAZ-D1.5/3-NA
2
FAZ-D2/1-NA-SP
FAZ-D2/2-NA FAZ-D2/3-NA
3
FAZ-D3/1-NA-SP
FAZ-D3/2-NA FAZ-D3/3-NA
4
FAZ-D4/1-NA-SP
FAZ-D4/2-NA FAZ-D4/3-NA
5
FAZ-D5/1-NA-SP
FAZ-D5/2-NA FAZ-D5/3-NA
6
FAZ-D6/1-NA-SP
FAZ-D6/2-NA FAZ-D6/3-NA
7
FAZ-D7/1-NA-SP
FAZ-D7/2-NA FAZ-D7/3-NA
8
FAZ-D8/1-NA-SP
FAZ-D8/2-NA FAZ-D8/3-NA
10
FAZ-D10/1-NA-SP FAZ-D10/2-NA FAZ-D10/3-NA
13
FAZ-D13/1-NA-SP FAZ-D13/2-NA FAZ-D13/3-NA
15
FAZ-D15/1-NA-SP FAZ-D15/2-NA FAZ-D15/3-NA
16
FAZ-D16/1-NA-SP FAZ-D16/2-NA FAZ-D16/3-NA
20
FAZ-D20/1-NA-SP FAZ-D20/2-NA FAZ-D20/3-NA
25
FAZ-D25/1-NA-SP FAZ-D25/2-NA FAZ-D25/3-NA
30
FAZ-D30/1-NA-SP FAZ-D30/2-NA FAZ-D30/3-NA
32
FAZ-D32/1-NA-SP FAZ-D32/2-NA FAZ-D32/3-NA
35 2
FAZ-D35/1-NA-SP FAZ-D35/2-NA FAZ-D35/3-NA
40 2
FAZ-D40/1-NA-SP FAZ-D40/2-NA FAZ-D40/3-NA
1
Catalog
Amperes Number
D Curve (10–20X In Current Rating)
0.5
FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
D Curve (13–20A)
Two-Pole
Three-Pole
Catalog
Number
Catalog
Number
D Curve with Ring-Tongue Terminals
(10–20X In Current Rating)
FAZ-D1/2-NA FAZ-D1/3-NA
Two-Pole
Three-Pole
0.5
FAZ-D0.5/1-RT-SP FAZ-D0.5/2-RT FAZ-D0.5/3-RT
1
FAZ-D1/1-RT-SP
1.5
FAZ-D1.5/1-RT-SP FAZ-D1.5/2-RT FAZ-D1.5/3-RT
2
FAZ-D2/1-RT-SP
FAZ-D2/2-RT
FAZ-D2/3-RT
3
FAZ-D3/1-RT-SP
FAZ-D3/2-RT
FAZ-D3/3-RT
4
FAZ-D4/1-RT-SP
FAZ-D4/2-RT
FAZ-D4/3-RT
5
FAZ-D5/1-RT-SP
FAZ-D5/2-RT
FAZ-D5/3-RT
6
FAZ-D6/1-RT-SP
FAZ-D6/2-RT
FAZ-D6/3-RT
7
FAZ-D7/1-RT-SP
FAZ-D7/2-RT
FAZ-D7/3-RT
8
FAZ-D8/1-RT-SP
FAZ-D8/2-RT
FAZ-D8/3-RT
10
FAZ-D10/1-RT-SP FAZ-D10/2-RT FAZ-D10/3-RT
13
FAZ-D13/1-RT-SP FAZ-D13/2-RT FAZ-D13/3-RT
15
FAZ-D15/1-RT-SP FAZ-D15/2-RT FAZ-D15/3-RT
16
FAZ-D16/1-RT-SP FAZ-D16/2-RT FAZ-D16/3-RT
20
FAZ-D20/1-RT-SP FAZ-D20/2-RT FAZ-D20/3-RT
25
FAZ-D25/1-RT-SP FAZ-D25/2-RT FAZ-D25/3-RT
30
FAZ-D30/1-RT-SP FAZ-D30/2-RT FAZ-D30/3-RT
FAZ-D1/2-RT
FAZ-D1/3-RT
32
FAZ-D32/1-RT-SP FAZ-D32/2-RT FAZ-D32/3-RT
35 2
FAZ-D35/1-RT-SP FAZ-D35/2-RT FAZ-D35/3-RT
40 2
FAZ-D40/1-RT-SP FAZ-C40/2-RT
FAZ-D40/3-RT
Notes
1 Option for single packaging on single-pole C and D curves only;
add suffix SP when ordering.
2 240 Vac rated only.
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-53
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
1
●
●
1
●
1
1
UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA-DC C Curve
1
1
Miniature Circuit Breakers and Supplementary Protectors
●
●
●
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as Branch Circuit Breakers
Interrupting capacity: 10 kA at 125 Vdc UL/CSA, 10 kA
at 250 Vdc
125 Vdc for one-pole, 250 Vdc for two-pole in series
Current limiting device
Polarity (+/–) sensitive and not for use on photovoltaic
string application
UL file number E235139
1
1
1
1
1
1
1
1
1
Single-Pole
1
FAZ-NA-DC UL 489 Circuit Breakers—
10 kAIC at 125 Vdc Per Pole
Single-Pole 1
Catalog
Amperes Number
1
Two-Pole
Catalog
Number
C Curve (5–10X In Current Rating)
1
2
FAZ-C2/1-NA-DC-SP
FAZ-C2/2-NA-DC
3
FAZ-C3/1-NA-DC-SP
FAZ-C3/2-NA-DC
4
FAZ-C4/1-NA-DC-SP
FAZ-C4/2-NA-DC
1
5
FAZ-C5/1-NA-DC-SP
FAZ-C5/2-NA-DC
1
6
FAZ-C6/1-NA-DC-SP
FAZ-C6/2-NA-DC
7
FAZ-C7/1-NA-DC-SP
FAZ-C7/2-NA-DC
1
8
FAZ-C8/1-NA-DC-SP
FAZ-C8/2-NA-DC
10
FAZ-C10/1-NA-DC-SP
FAZ-C10/2-NA-DC
1
13
FAZ-C13/1-NA-DC-SP
FAZ-C13/2-NA-DC
15
FAZ-C15/1-NA-DC-SP
FAZ-C15/2-NA-DC
1
16
FAZ-C16/1-NA-DC-SP
FAZ-C16/2-NA-DC
1
20
FAZ-C20/1-NA-DC-SP
FAZ-C20/2-NA-DC
25
FAZ-C25/1-NA-DC-SP
FAZ-C25/2-NA-DC
1
30
FAZ-C30/1-NA-DC-SP
FAZ-C30/2-NA-DC
32
FAZ-C32/1-NA-DC-SP
FAZ-C32/2-NA-DC
1
35
FAZ-C35/1-NA-DC-SP
FAZ-C35/2-NA-DC
40
FAZ-C40/1-NA-DC-SP
FAZ-C40/2-NA-DC
1
Two-Pole
1
Note
1 Option for single packaging on single-pole C curves only; add
suffix SP when ordering.
1
1
V4-T1-54
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
1.2
Accessories
Contact
1
FAZ-NA UL 489 Breakers
FAZ-NA UL 489 Breakers, continued
Description
Catalog Number
Description
Two-pole contact or auxiliary
contact/trip indicating contact
Z-NHK 1
Busbar
Catalog Number
Busbar—single-pole, 6 terminals 2345 Z-SV/UL-16/1P-1TE/6
Busbar—single-pole, 12 terminals 2345 Z-SV/UL-16/1P-1TE/12
Busbar—single-pole, 18 terminals 2345 Z-SV/UL-16/1P-1TE/18
Busbar—two-pole, 6 terminals 2345
Z-SV/UL-16/2P-2TE/12
Busbar—two-pole, 18 terminals 2345
Z-SV/UL-16/2P-2TE/18
Busbar—three-pole, 6 terminals 2345
Z-SV/UL-16/3P-3TE/6
Busbar—two-pole, 12 terminals
Auxiliary Contact
Auxiliary contact
Z-SV/UL-16/2P-2TE/6
2345
Busbar—three-pole, 12 terminals 2345 Z-SV/UL-16/3P-3TE/12
Z-IHK-NA
Busbar—three-pole, 18 terminals 2345 Z-SV/UL-16/3P-3TE/18
Busbar Shroud
Three-pole busbar shroud
1
1
1
1
1
1
1
1
ZV-BS-UL
1
1
Extension Terminal
Shunt Trip
Shunt trip 110–415 Vac
FAZ-XAA-NA110-415VAC
Shunt trip 12–110 Vac
FAZ-XAA-NA12-110VAC
Extension terminal—
35 mm2 (10–1/0 AWG)
1
Z-EK/35/UL
1
1
1
Padlock Hasp
Padlock hasp
1
Z-IS/SPE-1TE
Bus Connector
Bus connector—conductors up to
50 mm2 (~1/0 AWG)
1
Z-EB/50/UL
1
Lockoff Device
UL lockoff device
FAZPLOFF
Notes
1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
2 Do not cut commoning link.
3 A maximum of three commoning links may be used in conjunction. Each breaker connected to
the commoning link must have the same number of poles for proper use.
4 Not for use with ring-tongue circuit breakers.
5 Bus may be center fed for high current capacity.
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-55
1.2
1
1
1
1
1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Tripping Signal Switch Z-NHK, Z-IHK-NA
●
Design according to IEC/EN 60947-5-1, IEC/EN 62019
●
Field installable
●
The specified minimum voltages are per contact—take into
account particularly in case of series connection
●
Self-cleaning contacts
●
Contact material and design particularly suitable for extra
low voltage
●
Z-NHK: the function of one of the two change-over
contacts can be switched from “auxiliary switch” to
“tripping signal switch”
●
Tripping signal contact transmits message of electric tripping,
not mechanical switch-off
●
Test key for contact function “electrical tripping”
●
Z-IHK-NA: will allow for > 480Y/277 Vac rating
1
Connection Diagram
Z-IHK-NA
Z-NHK
4.14/4.12
13
4.11
14
22
1.11
Same Polarity
1.14
1.12
Busbar Connection Example
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-56
21
4.12/4.14
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
1.2
Technical Data and Specifications
Trip Curve Chart
Eaton FAZ-NA branch circuit
breakers are available with
“B,” “C” and “D” tripping
characteristics. B-curve
devices are suitable for
applications where low
levels of inrush current
are expected.
C-curve devices are suitable
for applications where
medium levels of inrush
current are expected.
Applications include small
transformers, lighting, pilot
devices, control circuits and
coils. C-curve devices provide
a medium magnetic trip point.
1
Tripping Characteristics
1
D-curve devices are suitable
for applications where high
levels of inrush current are
expected. The high magnetic
trip point prevents nuisance
tripping in high inductive
applications such as motors,
transformers and power
supplies.
1
1
1
1
Eaton FAZ-NA devices are
current limiting, which means
they interrupt fault currents
within one half cycle of the
fault. Current limiting devices
offer superior protection by
reducing peak let-through
current and energy.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-57
1.2
1
1
Connection Diagrams
UL 489 DIN Rail Miniature Circuit Breakers
Miniature Circuit Breakers FAZ-NA Technical Data
Description
Single-Pole
Rated voltage FAZ-NA
UL/CSA
1
1
1
Two-Pole
Specification
Electrical
Design according to
1
1
Miniature Circuit Breakers and Supplementary Protectors
UL 489, CSA C22.2 No.5, IEC 60947-2
10 kAIC at 277/480V from 0.5A to 32A
14 kAIC at select amperages
B and C Curves (15–25A), D Curve (13–20A)
UL/CSA
10 kAIC at 240 Vac for 35A and 40A
UL/CSA
10 kAIC at 48 Vdc per pole
IEC 947-2
15 kAIC at 240/415 Vac
Rated voltage FAZ-NA-DC
UL/CSA
10 kAIC at 125 Vdc per pole (two poles maximum)
10 kAIC at 250 Vdc with two poles connected in series
1
Rated frequency
1
Characteristic
B, C, D
Endurance
≥ 20,000 operations
1
Line voltage connection
Suitable for reverse feed
1
Frame size
45 mm
Device height
105 mm
Device width
17.7 mm per pole
Terminal protection
Finger and hand touch safe according to BGV A3, OVE-EN 6
1
50/60 Hz
Mechanical
Three-Pole
1
1
1
1
1
Mounting
Quick fastening with two lock-in positions on IEC/EN 60715
Upper and lower terminals
Open mouth/lift terminals
Terminal capacity
One wire: AWG 18–6
Two wires: AWG 18–10
Terminal fastening torque
AWG 18–21: 21 lb-in
AWG 10–8: 25 lb-in
AWG 6: 36 lb-in
Mounting
Independent of position
Calibration temperature
UL 489, CSA C22.2 No.5
1
IEC 60947-2
40°C
30°C
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-58
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Power Loss at ln
Characteristic B
Characteristic C
1
Characteristic D
Single-Pole
Two-Pole
Three-Pole
Single-Pole
Two-Pole
Three-Pole
Single-Pole
Two-Pole
Three-Pole
In [A]
P [W]
P [W]
P [W]
P [W]
P [W]
P [W]
P [W]
P [W]
P [W]
0.5
—
—
—
1.6
3.2
4.7
1.6
3.2
4.8
1.0
1.1
2.2
3.4
1.1
2.2
3.4
0.8
1.5
2.3
1.5
2.2
4.4
6.6
1.3
2.6
3.9
1.0
2.1
3.1
2.0
1.4
2.8
4.3
1.4
2.8
4.3
1.0
2.1
3.1
3.0
2.1
4.2
6.4
1.2
2.4
3.6
1.2
2.4
3.6
4.0
1.4
2.9
4.3
1.4
2.9
4.3
1.4
2.9
4.3
5.0
1.8
3.7
5.5
1.9
3.7
5.6
1.5
2.9
4.4
6.0
1.7
3.5
5.2
1.2
2.3
3.5
1.2
2.3
3.5
7.0
2.0
4.0
6.0
1.4
2.8
4.3
1.4
2.8
4.3
8.0
2.0
3.9
5.9
1.4
2.8
4.2
1.2
2.4
3.7
10.0
1.8
3.6
5.3
1.8
3.6
5.3
1.5
3.0
4.5
13.0
2.4
4.7
7.1
2.4
4.7
7.1
2.0
4.1
6.1
15.0
1.9
3.8
5.6
1.9
3.8
5.6
1.5
3.1
4.6
16.0
2.1
4.3
6.4
2.1
4.3
6.4
1.7
3.5
5.2
20.0
2.9
5.8
8.7
2.9
5.8
8.7
1.8
3.7
5.5
25.0
3.1
6.2
9.3
3.1
6.2
9.3
2.6
5.1
7.7
30.0
3.0
6.0
9.0
3.0
6.0
9.0
2.7
5.4
8.1
32.0
3.4
6.8
10.2
3.4
6.8
10.2
3.1
6.2
9.3
35.0
4.0
8.1
12.1
3.7
7.4
11.0
3.8
7.6
11.3
40.0
4.0
8.1
12.1
4.0
8.1
12.1
3.9
7.8
11.6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-59
1.2
1
1
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Let-Through Energy
Characteristic B (1–32A), 277V
Characteristic B (35–40A), 240V
Characteristic C (0.5–32A), 277V
Characteristic C (40A), 240V
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-60
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Characteristic D (0.5–32A), 277V
1.2
Characteristic D (40A), 240V
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-61
1.2
1
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Influence of Ambient Temperature T on Load Carrying Capacity
Device Market
Current Rating In
(A) at 40°C
15°C
20°C
25°C
30°C
40°C
50°C
55°C
60°C
1
0.5
0.6
0.5
0.5
0.5
0.5
0.5
0.5
0.5
1.0
1.1
1.1
1.1
1.0
1.0
1.0
0.9
0.9
1
1.5
1.7
1.6
1.6
1.6
1.5
1.4
1.4
1.4
2.0
2.2
2.2
2.1
2.1
2.0
1.9
1.9
1.8
3.0
3.3
3.2
3.2
3.1
3.0
2.9
2.9
2.8
1
1
In (A) at Higher Ambient Temperature
1
4.0
4.4
4.3
4.2
4.2
4.0
3.8
3.8
3.7
5.0
5.5
5.4
5.3
5.2
5.0
4.8
4.7
4.6
1
6.0
6.6
6.5
6.4
6.2
6.0
5.8
5.6
5.5
7.0
7.7
7.6
7.4
7.3
7.0
6.7
6.6
6.4
8.0
8.8
8.6
8.5
8.3
8.0
7.7
7.5
7.4
1
10.0
11.0
10.8
10.6
10.4
10.0
9.6
9.4
9.2
13.0
14.3
14.0
13.8
13.5
13.0
12.5
12.5
12.0
1
15.0
16.5
16.2
15.9
15.6
15.0
14.4
14.1
13.8
1
1
1
1
16.0
17.6
17.3
17.0
16.6
16.0
15.4
15.0
14.7
20.0
22.0
21.6
21.2
20.8
20.0
19.2
18.8
18.4
25.0
27.5
27.0
26.5
26.0
25.0
24.0
23.3
23.0
27.6
30.0
33.0
32.4
31.8
31.2
30.0
28.8
28.2
32.0
35.2
34.6
33.9
33.3
32.0
30.7
30.1
29.4
40.0
44.0
43.2
42.4
41.6
40.0
38.4
37.6
36.8
1
Load Carrying Capacity of Adjoining Miniature
Circuit Breakers
1
1.00
1
1
1
Load Factor KT [I/IN]
1
Rated Diversity Factor
1
1
0.90
0.80
0.70
1
1
2
3
4
5
6
Number of Circuit Breakers
1
1
Ambient Temperature T [°C]
Maximum Load IL at ambient temperature T: IL (T) = IN KT(T)
1
1
1
1
1
1
V4-T1-62
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
7
8
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Z-NHK
1.2
Contact and Auxiliary Contact
Description
Z-NHK
Z-IHK-NA
Contact function
2CO
1NO + 1NC
Rated voltage
230V
250V
Frequency
50/60 Hz
50/60 Hz
Rated current
2A
6A
1
1
Electrical
Z-IHK-NA
1
1
Rated thermal current Ith
2A
6A
Utilization category AC13
Rated operational current Ie
1
3A/250 Vac
3A/250 Vac
Utilization category AC15
Rated operational current Ie
1
2A/250 Vac
2A/250 Vac
Utilization category DC12
Rated operational current Ie
1
0.5A/110 Vdc
0.5A/110 Vdc
0.25A/220 Vdc
1
Rated insulation voltage UI
250 Vac
250 Vac
Minimum operational voltage per contact Umin
5 Vdc
5 Vdc
1
Minimum operational current Imin
10 mA DC
10 mA AC/DC
Rated peak withstand voltage Uimp (1.2/50μ)
2.5 kV
4 kV
Conditional short-circuit current Ik with backup fuse 6A
1 kA
1 kA
Max. backup fuse, overload and short circuit
6A gL
—
1
1
1
Mechanical
Tripping indicator “electrical tripping”
Blue/white
—
Frame size
45 mm
45 mm
Device height
80 mm
80 mm
1
1
1
Device width
8.8 mm (0.5MU)
8.8 mm (0.5MU)
Mounting
Onto switching device
—
Degree of protection, built-in
IP40
IP40
Terminal protection
Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
1
Terminals
Lift terminals
Lift terminals
Terminal capacity
20–14 AWG
0.5–2.5 mm2
1
Terminal screws
M3 (Posidrive Z0)
M3 (Posidrive Z0)
Fastening torque of terminal screws
7 lb-in
Max. 1.2 Nm
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-63
1.2
1
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Shunt trip release FAZ-XAA-NA
●
Remote release for subsequent mounting onto FAZ-NA/RT
●
Additional installation of standard auxiliary switch is possible
●
Position indicator red–green
Connection Diagram
1
Shunt Trip Release FAZ-XAA-NA
Description
FAZ-XAA-NA12-110VAC
FAZ-XAA-NA110-415VAC
Can be
mounted onto
FAZ-NA / FAZ-NA-DC /
FAZ-RT
FAZ-NA / FAZ-NA-DC /
FAZ-RT
Operational
voltage range
12–110 Vac
12–60 Vdc
110–415 Vac
110–230 Vdc
Frequency
50/60 Hz
50/60 Hz
Electrical
1
1
2
1
1
Mechanical
Frame size
45 mm
45 mm
1
Device height
105 mm
105 mm
Device width
17.5 mm
17.5 mm
1
Mounting
Quick fastening with two lock-in positions on EN 50022
1
Terminal protection
Degree of protection, built-in IP40
1
1
1
1
1
1
1
Connection Diagrams
Three-Pole Busbar
Open mouthed/lift
Open mouthed/lift
Terminal capacity
One and two wires
18–10 AWG
18–10 AWG
Busbar Block UL 489 (Pin)
Description
UL 489
IEC/EN 60947-2
480/277 Vac
96 Vdc
—
Electrical
Rated operational voltage
1
Two-Pole Busbar
1
1
1
Terminals
Busbar block UL 489 (pin)
●
Tested according to UL 489
●
Do not cut
●
Extension terminal 35 mm2 Z-EK/35/UL for copper conductors
●
Incoming terminal 50 mm2 Z-EB/50/UL
●
For covering of not used pins, use busbar tag shrouds ZV-BS-UL
1
1
IP40
Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Single-Pole Busbar
1
1
1
1
1
Rated frequency
50/60 Hz
—
Rated voltage
480 Vac
690 Vac
Overvoltage category
—
III
Rated impulse withstand voltage Uimp
—
9.5 kV
Rated current
80A at 40°C
80A at 30°C
Rated conditional short-circuit current AC with 350A gG
—
15 kA
Short-circuit current
10 kA
—
Mechanical
Busbar cross section
—
16 mm2 Cu
Flame class according to UL 94
V0
—
Pollution degree
—
2
Comparative tracking index
—
CTI 600
Minimum clearance (internal/external)
—
> 9.5/25.4 mm
Minimum creepage distance (internal/external)
—
> 12.7/50.8 mm
Resistance to climatic conditions
—
According to
DIN/EN 60068
1
V4-T1-64
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Application Guidelines
1
Example of UL 489 and UL 1077 Application
1
1
UL 489
Breaker
1
1
1
UL 489
Branch
UL 1077
Internal Receptacle
1
External
Receptacle
1
1
Electronics
1
UL 489
Branch
UL 1077
Other
Sensitive
Devices
External
Motor
1
M
1
UL 489
Branch
1
UL 489
Branch
UL 1077
HACR
External
Motor
1
M
1
1
Motor
Controller
1
1
1
Example of UL 489 and UL 1077 Application
1
UL 489 circuit breakers
1
Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment
(heating, air conditioning and refrigeration).
1
UL 1077 supplementary protectors
1
Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection
is already provided or not required.
1
Note: UL 489 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-65
1.2
1
1
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Lockout Attachment—
Z-IS/SPE-1TE
Miniature Circuit Breakers
1
Single-Pole
Two-Pole
UL Lockoff Device—
FAZPLOFF
Three-Pole
1
1
1
4.13
(105.0)
1
4.13
(105.0)
1
1
.70 .70
(17.7) (17.7)
2.09
(53.1)
.70
(17.7)
1.39
(35.3)
.70
(17.7)
1
4.13
(105.0)
Accessories
1
Z-SV/UL-16/6
ZV-BS-UL
Z-SV/UL-18...12
1
1
1
1
1
1
Z-EK/35/UL
Z-SV/UL-16.../18
1
1
1
1
1
1
Z-EK/35/UL
1
Description
UL 489
IEC/EN 60947-2
1
Ue
480 Vac/96 Vdc
240/415 Vac
f
50/60 Hz
50/60 Hz
1
Uimp
—
9.5 kV
Z-EB/50/UL
Description
UL 489
IEC/EN 60947-2
Ue
480 Vac/96 Vdc
240/415 Vac
f
50/60 Hz
50/60 Hz
—
9.5 kV
115A at 40°C
160A at 30°C
#1–14 AWG 60/75°C Cu
1.5–50 mm2 Cu
0.56 in
14 mm
80A at 40°C
80A at 30°C
Uimp
1
10–1/0 AWG 60/75°C Cu
2.5–35 mm2 Cu
Ie
1
0.56 in
Ie
14 mm
1
1
V4-T1-66
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
1.3
Contents
FAZ Circuit Breakers
Description
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . .
Catalog Number Selection . . . . . . . . . . . . . . . . .
Standards and Certifications. . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
V4-T1-67
V4-T1-68
V4-T1-68
V4-T1-69
V4-T1-75
V4-T1-78
V4-T1-85
1
1
1
1
1
1
Optimum and Efficient Protection for Every Application
1
1
1
1
1
FAZ Circuit Breakers
Product Overview
Features
Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s FAZ DIN rail
mountable circuit breaker is
designed for use in control
panel applications.
●
●
●
Powerful offering for machine
and system builders
The FAZ is available with B,
C, D, K, S, and Z characteristics
in accordance with UL 1077,
CSA C22.2 No.235 and IEC
60947-2. These devices are
CE marked.
Application Description
●
●
●
●
●
Supplementary protection
Control circuits
Lighting
Business equipment
Appliances
Complete range of UL
1077 recognized DIN
rail mounted miniature
circuit breakers up to
63A current rating
Standard ratings of 10 kAIC
up to 277/480 Vac
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage
the circuit
●
Suitable for supplementary
protection
●
Thermal-magnetic
overcurrent protection
●
Six levels of short-circuit
protection, categorized
by B, C, D, K, S, and
Z curves
1
●
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
●
Captive screws cannot
be lost
1
●
Fulfill UL 1077, CSA C22.2
No.235 and also IEC
60947-2 Standard
1
●
Field-installable shunt trip
and auxiliary switch
subsequent mounting
●
Module width of only
17.7 mm (per pole)
●
Contact position indicator
(red/green)
●
Easy installation on DIN rail
●
Possibility for sealing
the toggle in ON or
OFF position
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-67
1.3
1
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Standards and Certifications
FAZ complies with the latest
national and international
standards.
Discover These Advanced Features
1
1
1
1
1
1
1
Captive Posidrive
terminal screws with
finger and back-ofhand protection (IP20)
Breakers install on
standard DIN rail
Available in one-, two-,
three-, four-pole, 1+N
and 3+N models
Trip-free design;
breaker cannot be
defeated by holding
the handle in the
ON position
Color-coded indicator
provides breaker
status for easy
troubleshooting
Breaker information
printed on the front of
the device for quick
identification
1
●
UL 1077, CSA C22.2
No. 235
●
Apply to supplementary
protectors intended for
use as overcurrent, or
overvoltage or
undervoltage protection
within an appliance or
other electrical
equipment where
branch circuit protection
is already provided, or is
not required
●
●
●
●
RoHS compliant
VDE compliant
●
Devices with B, C,
and D curves are
VDE compliant
CCC
●
Devices with B, C,
and D curves are
CCC compliant
ABS compliant
1
1
1
Catalog Number Selection
FAZ C 6 / 1 SP
1
1
1
Single Package
Breaker Family
FAZ = Supplementary
protector
Trip
Characteristics 1
B = 3–5X In
C = 5–10X In
D = 10–20X In
K = 8–12X In
S = 13–17X In
Z = 2–3X In
1
1
1
1
1
SP
Ampere Rating
0.5 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
10 =
0.5A
1A
2A
3A
4A
5A
6A
7A
8A
10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
40 = 40A
50 = 50A
63 = 63A
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
Note
1 I = Rated current for instantaneous trip characteristics.
n
1
1
1
1
1
1
1
1
1
1
V4-T1-68
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
4 = Single-pole
1N = Single-pole +
neutral
3N = Three-pole +
neutral
= Single packaging of singlepole curve B, C and D for
select amperes only
Blank = Standard packaging
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Product Selection
1.45
1
7200
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
600
Specified tripping current
IT = 1.45 x IN for t < 1 h
300
2.55 I :
N
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
1
Type B: 3 x I : t > 0.1 s
N
1
Type B: 5 x I : t < 0.1 s
N
120
1
1
60
30
1
10
t [sec]
Suitable for applications where protection against low-level
short-circuit faults in control wiring is desired. Instantaneous trip
is 3–5X continuous rating of device (In). Applications include PLC
wiring, business equipment, lighting, appliances and some
motors. Low magnetic trip point.
1.13
1
FAZ B curve (3–5X In current rating)
●
Designed for resistive or slightly inductive loads
●
Response time of instantaneous trip: 3–5X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451
5
1
2
1
1
0.5
1
0.2
3
0.1
1
B
2
0.05
0.02
1
0.01
0.005
1
0.002
0.001
1
0.0005
1
2
3
4
5
6 7 8 9 10
15
20
30
40
50
I / IN
Single-Pole
B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads 1
Single-Pole 2
Two-Pole
Three-Pole
Two-Pole
Three-Pole
Catalog
Amperes Number
Catalog
Number
Catalog
Number
1
FAZ-B1/1-SP
FAZ-B1/2
FAZ-B1/3
2
FAZ-B2/1-SP
FAZ-B2/2
3
FAZ-B3/1-SP
FAZ-B3/2
4
FAZ-B4/1-SP
FAZ-B4/2
FAZ-B4/3
Four-Pole
1
B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads, continued 1
1
Three-Pole
+ Neutral
Catalog
Amperes Number
Catalog
Number
Catalog
Number
1
FAZ-B2/3
1
FAZ-B1/4
FAZ-B1/1N
FAZ-B1/3N
2
FAZ-B2/4
FAZ-B2/1N
FAZ-B2/3N
1
FAZ-B3/3
3
FAZ-B3/4
FAZ-B3/1N
FAZ-B3/3N
FAZ-B4/4
FAZ-B4/1N
FAZ-B4/3N
Single-Pole + Neutral
5
FAZ-B5/1-SP
FAZ-B5/2
FAZ-B5/3
4
6
FAZ-B6/1-SP
FAZ-B6/2
FAZ-B6/3
5
FAZ-B5/4
FAZ-B5/1N
FAZ-B5/3N
7
FAZ-B7/1-SP
FAZ-B7/2
FAZ-B7/3
6
FAZ-B6/4
FAZ-B6/1N
FAZ-B6/3N
FAZ-B7/4
FAZ-B7/1N
FAZ-B7/3N
8
FAZ-B8/1-SP
FAZ-B8/2
FAZ-B8/3
7
10
FAZ-B10/1-SP
FAZ-B10/2
FAZ-B10/3
8
FAZ-B8/4
FAZ-B8/1N
FAZ-B8/3N
12
FAZ-B12/1-SP
FAZ-B12/2
FAZ-B12/3
10
FAZ-B10/4
FAZ-B10/1N
FAZ-B10/3N
13
FAZ-B13/1-SP
FAZ-B13/2
FAZ-B13/3
12
FAZ-B12/4
FAZ-B12/1N
FAZ-B12/3N
FAZ-B13/4
FAZ-B13/1N
FAZ-B13/3N
Three-Pole + Neutral
15
FAZ-B15/1-SP
FAZ-B15/2
FAZ-B15/3
13
16
FAZ-B16/1-SP
FAZ-B16/2
FAZ-B16/3
15
FAZ-B15/4
FAZ-B15/1N
FAZ-B15/3N
20
FAZ-B20/1-SP
FAZ-B20/2
FAZ-B20/3
16
FAZ-B16/4
FAZ-B16/1N
FAZ-B16/3N
FAZ-B20/4
FAZ-B20/1N
FAZ-B20/3N
25
FAZ-B25/1-SP
FAZ-B25/2
FAZ-B25/3
20
30
FAZ-B30/1-SP
FAZ-B30/2
FAZ-B30/3
25
FAZ-B25/4
FAZ-B25/1N
FAZ-B25/3N
FAZ-B30/4
FAZ-B30/1N
FAZ-B30/3N
32
FAZ-B32/1-SP
FAZ-B32/2
FAZ-B32/3
30
40
FAZ-B40/1-SP
FAZ-B40/2
FAZ-B40/3
32
FAZ-B32/4
FAZ-B32/1N
FAZ-B32/3N
50
FAZ-B50/1-SP
FAZ-B50/2
FAZ-B50/3
40
FAZ-B40/4
FAZ-B40/1N
FAZ-B40/3N
FAZ-B63/3
50
FAZ-B50/4
FAZ-B50/1N
FAZ-B50/3N
63
FAZ-B63/4
FAZ-B63/1N
FAZ-B63/3N
63
FAZ-B63/1-SP
FAZ-B63/2
1
Single-Pole
+ Neutral
Four-Pole
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-69
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
1
1
1
1
1
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 5–10X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.
1.45
FAZ C curve (5–10X In current rating)
●
Designed for inductive loads
●
Response time of instantaneous trip: 5–10X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451
1.13
UL 1077 DIN Rail Supplementary Protectors
7200
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
300
120
60
30
10
5
2
0.5
0.2
1
2
0.1
1
0.05
1
0.02
0.005
0.002
0.001
1
0.0005
1
2
3
4
1
5
6 7 8 9 10
15
20
30
40
50
I / IN
1
Single-Pole
C Curve (5–10X In Current Rating)—
Designed Inductive Loads 1
Single-Pole 2
1
1
1
Two-Pole
Three-Pole
Catalog
Amperes Number
Catalog
Number
Catalog
Number
0.5
FAZ-C0.5/1-SP
FAZ-C0.5/2
FAZ-C0.5/3
1
FAZ-C1/1-SP
FAZ-C1/2
FAZ-C1/3
1.6
Two-Pole
1
1
FAZ-C1.6/2
FAZ-C2/1-SP
FAZ-C2/2
FAZ-C2/3
FAZ-C3/1-SP
FAZ-C3/2
FAZ-C3/3
4
FAZ-C4/1-SP
FAZ-C4/2
FAZ-C4/3
5
FAZ-C5/1-SP
FAZ-C5/2
FAZ-C5/3
8
10
13
FAZ-C6/1-SP
FAZ-C7/1-SP
FAZ-C8/1-SP
FAZ-C10/1-SP
FAZ-C13/1-SP
FAZ-C6/2
FAZ-C7/2
FAZ-C8/2
FAZ-C10/2
FAZ-C13/2
FAZ-C8/3
FAZ-C10/3
15
1
16
FAZ-C16/1-SP
FAZ-C16/2
FAZ-C16/3
20
FAZ-C20/1-SP
FAZ-C20/2
FAZ-C20/3
25
1
30
1
32
40
1
50
63
1
FAZ-C25/1-SP
FAZ-C30/1-SP
FAZ-C32/1-SP
FAZ-C40/1-SP
FAZ-C50/1-SP
FAZ-C63/1-SP
FAZ-C15/2
FAZ-C25/2
FAZ-C30/2
FAZ-C32/2
FAZ-C40/2
FAZ-C50/2
FAZ-C63/2
Single-Pole + Neutral
FAZ-C7/3
FAZ-C13/3
C Curve (5–10X In Current Rating)—
Designed Inductive Loads, continued 1
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Catalog
Amperes Number
Catalog
Number
Catalog
Number
0.5
FAZ-C0.5/4
FAZ-C0.5/1N
FAZ-C0.5/3N
1
FAZ-C1/4
FAZ-C1/1N
FAZ-C1/3N
1.6
FAZ-C1.6/4
FAZ-C1.6/1N
FAZ-C1.6/3N
2
FAZ-C2/4
FAZ-C2/1N
FAZ-C2/3N
3
FAZ-C3/4
FAZ-C3/1N
FAZ-C3/3N
4
FAZ-C4/4
FAZ-C4/1N
FAZ-C4/3N
5
FAZ-C5/4
FAZ-C5/1N
FAZ-C5/3N
6
FAZ-C6/4
FAZ-C6/1N
FAZ-C6/3N
7
FAZ-C7/4
FAZ-C7/1N
FAZ-C7/3N
8
FAZ-C8/4
FAZ-C8/1N
FAZ-C8/3N
10
FAZ-C10/4
FAZ-C10/1N
FAZ-C10/3N
13
FAZ-C13/4
FAZ-C13/1N
FAZ-C13/3N
15
FAZ-C15/4
FAZ-C15/1N
FAZ-C15/3N
16
FAZ-C16/4
FAZ-C16/1N
FAZ-C16/3N
20
FAZ-C20/4
FAZ-C20/1N
FAZ-C20/3N
25
FAZ-C25/4
FAZ-C25/1N
FAZ-C25/3N
32
FAZ-C32/4
FAZ-C32/1N
FAZ-C32/3N
40
FAZ-C40/4
FAZ-C40/1N
FAZ-C40/3N
50
FAZ-C50/4
FAZ-C50/1N
FAZ-C50/3N
63
FAZ-C63/4
FAZ-C63/1N
FAZ-C63/3N
Four-Pole
FAZ-C6/3
1
FAZ-C15/1-SP
Four-Pole
FAZ-C1.6/3
3
7
Three-Pole
FAZ-C1.6/1-SP
2
6
1
1
C
0.01
1
1
Type C: 10 x I : t < 0.1 s
N
1
1
1
Type C: 5 x I : t > 0.1 s
N
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
t [sec]
1
Miniature Circuit Breakers and Supplementary Protectors
Three-Pole + Neutral
FAZ-C15/3
FAZ-C25/3
FAZ-C30/3
FAZ-C32/3
FAZ-C40/3
FAZ-C50/3
FAZ-C63/3
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
1
1
V4-T1-70
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.3
Miniature Circuit Breakers and Supplementary Protectors
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 10–20X rating of device (In). The
high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
1
1.45
7200
Specified non-tripping
current
INT = 1.13 x IN for t > 1 h
3600
1200
Specified tripping current
IT = 1.45 x IN for t < 1 h
600
300
2.55 I :
N
1
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Type D: 10 x I : t > 0.1 s
N
1
Type D: 20 x I : t < 0.1 s
N
120
1
1
60
30
1
10
t [sec]
FAZ D curve (10–20X In current rating)
●
Designed for highly inductive loads
●
Response time of instantaneous trip: 10–20X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451
1.13
UL 1077 DIN Rail Supplementary Protectors
5
1
2
1
1
1
0.5
0.2
3
0.1
2
0.05
1
D
1
0.02
0.01
0.005
1
0.002
0.001
1
0.0005
1
2
3
4
5
6 7 8 9 10
15
20
30
40
50
1
I / IN
Single-Pole
D Curve (10–20X In Current Rating)—
Designed for Inductive Loads 1
Single-Pole 2
Catalog
Amperes Number
Two-Pole
Three-Pole
Two-Pole
Three-Pole
Catalog
Number
Catalog
Number
0.5
FAZ-D0.5/1-SP FAZ-D0.5/2
FAZ-D0.5/3
1
FAZ-D1/1-SP
FAZ-D1/2
FAZ-D1/3
2
FAZ-D2/1-SP
FAZ-D2/2
FAZ-D2/3
3
FAZ-D3/1-SP
FAZ-D3/2
FAZ-D3/3
4
FAZ-D4/1-SP
FAZ-D4/2
FAZ-D4/3
5
FAZ-D5/1-SP
FAZ-D5/2
FAZ-D5/3
6
FAZ-D6/1-SP
FAZ-D6/2
FAZ-D6/3
7
FAZ-D7/1-SP
FAZ-D7/2
FAZ-D7/3
8
FAZ-D8/1-SP
FAZ-D8/2
FAZ-D8/3
10
FAZ-D10/1-SP
FAZ-D10/2
FAZ-D10/3
13
FAZ-D13/1-SP
FAZ-D13/2
FAZ-D13/3
15
FAZ-D15/1-SP
FAZ-D15/2
FAZ-D15/3
16
FAZ-D16/1-SP
FAZ-D16/2
FAZ-D16/3
20
FAZ-D20/1-SP
FAZ-D20/2
FAZ-D20/3
25
FAZ-D25/1-SP
FAZ-D25/2
FAZ-D25/3
30
FAZ-D30/1-SP
FAZ-D30/2
FAZ-D30/3
32
FAZ-D32/1-SP
FAZ-D32/2
FAZ-D32/3
40
FAZ-D40/1-SP
FAZ-D40/2
FAZ-D40/3
50 3
FAZ-D50/1-SP
FAZ-D50/2
FAZ-D50/3
63 3
FAZ-D63/1-SP
FAZ-D63/2
FAZ-D63/3
Four-Pole
D Curve (10–20X In Current Rating)—
Designed for Inductive Loads, continued 1
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Catalog
Amperes Number
Catalog
Number
Catalog
Number
0.5
FAZ-D0.5/4
FAZ-D0.5/1N
FAZ-D0.5/3N
1
FAZ-D1/4
FAZ-D1/1N
FAZ-D1/3N
2
FAZ-D2/4
FAZ-D2/1N
FAZ-D2/3N
3
FAZ-D3/4
FAZ-D3/1N
FAZ-D3/3N
4
FAZ-D4/4
FAZ-D4/1N
FAZ-D4/3N
5
FAZ-D5/4
FAZ-D5/1N
FAZ-D5/3N
6
FAZ-D6/4
FAZ-D6/1N
FAZ-D6/3N
7
FAZ-D7/4
FAZ-D7/1N
FAZ-D7/3N
8
FAZ-D8/4
FAZ-D8/1N
FAZ-D8/3N
10
FAZ-D10/4
FAZ-D10/1N
FAZ-D10/3N
13
FAZ-D13/4
FAZ-D13/1N
FAZ-D13/3N
15
FAZ-D15/4
FAZ-D15/1N
FAZ-D15/3N
16
FAZ-D16/4
FAZ-D16/1N
FAZ-D16/3N
20
FAZ-D20/4
FAZ-D20/1N
FAZ-D20/3N
25
FAZ-D25/4
FAZ-D25/1N
FAZ-D25/3N
30
FAZ-D30/4
FAZ-D30/1N
FAZ-D30/3N
32
FAZ-D32/4
FAZ-D32/1N
FAZ-D32/3N
40
FAZ-D40/4
FAZ-D40/1N
FAZ-D40/3N
50 c
FAZ-D50/4
FAZ-D50/1N
FAZ-D50/3N
63 c
FAZ-D63/4
FAZ-D63/1N
FAZ-D63/3N
Four-Pole
Single-Pole + Neutral
Three-Pole + Neutral
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
3 IEC 60947-2 only.
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-71
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
1
1
1
1
1
UL 1077 DIN Rail Supplementary Protectors
1.13
1.45
FAZ K curve (8–12X In current rating)
●
Designed for motors, transformers and upstream electronics
●
Response time of instantaneous trip: 8–12X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451
7200
3600
120
60
30
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 8–12X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.
1
Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h
1200
600
300
10
5
t (sec)
1
Miniature Circuit Breakers and Supplementary Protectors
2
1
0.5
K
0.2
0.1
0.05
1
1
0.02
0.01
0.005
1
0.002
0.001
0.0005
1
1
1
Single-Pole
K Curve (8–12X In Current Rating)—
Designed for Inductive Loads 12
Single-Pole 3
1
Two-Pole
Three-Pole
Catalog
Amperes Number
Catalog
Number
Catalog
Number
0.5
FAZ-K0.5/1
FAZ-K0.5/2
FAZ-K0.5/3
1
FAZ-K1/1
FAZ-K1/2
FAZ-K1/3
1.6
FAZ-K1.6/1
FAZ-K1.6/2
FAZ-K1.6/3
2
FAZ-K2/1
FAZ-K2/2
FAZ-K2/3
3
FAZ-K3/1
FAZ-K3/2
FAZ-K3/3
4
FAZ-K4/1
FAZ-K4/2
FAZ-K4/3
1
6
FAZ-K6/1
FAZ-K6/2
FAZ-K6/3
8
FAZ-K8/1
FAZ-K8/2
FAZ-K8/3
1
10
FAZ-K10/1
FAZ-K10/2
FAZ-K10/3
13
FAZ-K13/1
FAZ-K13/2
FAZ-K13/3
16
FAZ-K16/1
FAZ-K16/2
FAZ-K16/3
20
FAZ-K20/1
FAZ-K20/2
FAZ-K20/3
25
FAZ-K25/1
FAZ-K25/2
FAZ-K25/3
32
FAZ-K32/1
FAZ-K32/2
FAZ-K32/3
40
FAZ-K40/1
FAZ-K40/2
FAZ-K40/3
50
FAZ-K50/1
FAZ-K50/2
FAZ-K50/3
63
FAZ-K63/1
FAZ-K63/2
FAZ-K63/3
1
1
1
Two-Pole
1
1
1
3
4 5 6 7 8 9 10 15 20
30 40 50
U-rated Current
1
1
2
Three-Pole
1
1
1
Four-Pole
K Curve (8–12X In Current Rating)—
Designed for Inductive Loads, continued 12
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Catalog
Amperes Number
Catalog
Number
Catalog
Number
0.5
FAZ-K0.5/4
FAZ-K0.5/1N
FAZ-K0.5/3N
1
FAZ-K1/4
FAZ-K1/1N
FAZ-K1/3N
1.6
FAZ-K1.6/4
FAZ-K1.6/1N
FAZ-K1.6/3N
2
FAZ-K2/4
FAZ-K2/1N
FAZ-K2/3N
3
FAZ-K3/4
FAZ-K3/1N
FAZ-K3/3N
4
FAZ-K4/4
FAZ-K4/1N
FAZ-K4/3N
6
FAZ-K6/4
FAZ-K6/1N
FAZ-K6/3N
8
FAZ-K8/4
FAZ-K8/1N
FAZ-K8/3N
10
FAZ-K10/4
FAZ-K10/1N
FAZ-K10/3N
13
FAZ-K13/4
FAZ-K13/1N
FAZ-K13/3N
16
FAZ-K16/4
FAZ-K16/1N
FAZ-K16/3N
20
FAZ-K20/4
FAZ-K20/1N
FAZ-K20/3N
25
FAZ-K25/4
FAZ-K25/1N
FAZ-K25/3N
32
FAZ-K32/4
FAZ-K32/1N
FAZ-K32/3N
40
FAZ-K40/4
FAZ-K40/1N
FAZ-K40/3N
50
FAZ-K50/4
FAZ-K50/1N
FAZ-K50/3N
63
FAZ-K63/4
FAZ-K63/1N
FAZ-K63/3N
Four-Pole 3
Single-Pole + Neutral
Three-Pole + Neutral
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in additional delivery time.
3 Two-piece box order, quantities of 2.
1
1
1
1
V4-T1-72
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
7200
3600
Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h
1200
600
300
120
60
30
1
1
1
1
10
5
t (sec)
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 13–17X rating of device (In). The
high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
1
1.05
1.30
FAZ S curve (13–17X In current rating)
●
Designed for control circuits with high inrush
●
Response time of instantaneous trip: 13–17X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
●
UL file number 177451
1.3
1
2
1
0.5
1
S
0.2
0.1
0.05
1
1
0.02
0.01
0.005
1
0.002
0.001
0.0005
1
2
3
4 5 6 7 8 9 10 15 20
1
30 40 50
1
U-rated Current
Single-Pole
Two-Pole
S Curve (13–17X In Current Rating)—
Designed for Inductive Loads 12
Single-Pole 3
Two-Pole
Amperes
Catalog
Number
Catalog
Number
1
FAZ-S1/1
FAZ-S1/2
2
FAZ-S2/1
FAZ-S2/2
3
FAZ-S3/1
FAZ-S3/2
4
FAZ-S4/1
FAZ-S4/2
6
FAZ-S6/1
FAZ-S6/2
10
FAZ-S10/1
FAZ-S10/2
16
FAZ-S16/1
FAZ-S16/2
20
FAZ-S20/1
FAZ-S20/2
25
FAZ-S25/1
FAZ-S25/2
32
FAZ-S32/1
FAZ-S32/2
40
FAZ-S40/1
FAZ-S40/2
1
1
1
1
1
1
1
1
1
Notes
1 In North America, these switches are UL recognized and CSA
Certified as supplementary protection devices. Per the intent of
NEC (National Electrical Code), Article 240, and CEC (Canadian
Electrical Code), Part 1 C22.1, supplementary breakers cannot be
used as a substitute for the branch circuit protective device.
They can be used to provide overcurrent protection within an
appliance or other electrical equipment where branch circuit
overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in
additional delivery time.
3 Two-piece box order, quantities of 2.
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-73
1.3
1
1
1
1
UL 1077 DIN Rail Supplementary Protectors
FAZ Z curve (2–3X In current rating)
●
Designed for protection of electronic devices
●
Response time of instantaneous trip: 2–3X In current rating
●
UL recognized and CSA Certified as supplementary protectors
●
For international and domestic use (conform to IEC 60947-2)
1.05
1.30
1
Miniature Circuit Breakers and Supplementary Protectors
7200
3600
1200
600
300
Suitable for applications where low levels of inrush current
are expected. Instantaneous trip is 2–3X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.
120
60
30
10
5
t (sec)
1
1
2
1
0.5
1
0.02
0.01
0.005
1
0.002
0.001
0.0005
1
1
1
2
3
4 5 6 7 8 9 10 15 20
30 40 50
U-rated Current
Single-Pole
1
1
1
1
1
Z
0.2
0.1
0.05
1
1
Specified
non-tripping current
Int = 1.05 u In
for t > 1 h
Specified
tripping current
It = 1.30 u In
for t < 1 h
Two-Pole
1
1
Z Curve (2–3X In Current Rating)—
Designed for Inductive Loads 12
Single-Pole 3
Two-Pole
Amperes
Catalog
Number
Catalog
Number
0.5
FAZ-Z0.5/1
FAZ-Z0.5/2
1
FAZ-Z1/1
FAZ-Z1/2
1.6
FAZ-Z1.6/1
FAZ-Z1.6/2
2
FAZ-Z2/1
FAZ-Z2/2
3
FAZ-Z3/1
FAZ-Z3/2
4
FAZ-Z4/1
FAZ-Z4/2
6
FAZ-Z6/1
FAZ-Z6/2
8
10
1
13
16
1
20
FAZ-Z8/1
FAZ-Z10/1
FAZ-Z13/1
FAZ-Z16/1
FAZ-Z20/1
FAZ-Z10/2
FAZ-Z13/2
FAZ-Z16/2
FAZ-Z20/2
1
32
FAZ-Z32/1
FAZ-Z32/2
1
40
FAZ-Z40/1
FAZ-Z40/2
1
63
1
FAZ-Z50/1
FAZ-Z63/1
Four-Pole
FAZ-Z8/2
25
50
FAZ-Z25/1
Three-Pole
FAZ-Z25/2
FAZ-Z50/2
FAZ-Z63/2
Z Curve (2–3X In Current Rating)—
Designed for Inductive Loads, continued 12
Three-Pole
Four-Pole
Amperes
Catalog
Number
Catalog
Number
0.5
FAZ-Z0.5/3
FAZ-Z0.5/4
1
FAZ-Z1/3
FAZ-Z1/4
1.6
FAZ-Z1.6/3
FAZ-Z1.6/4
2
FAZ-Z2/3
FAZ-Z2/4
3
FAZ-Z3/3
FAZ-Z3/4
4
FAZ-Z4/3
FAZ-Z4/4
6
FAZ-Z6/3
FAZ-Z6/4
8
FAZ-Z8/3
FAZ-Z8/4
10
FAZ-Z10/3
FAZ-Z10/4
13
FAZ-Z13/3
FAZ-Z13/4
16
FAZ-Z16/3
FAZ-Z16/4
20
FAZ-Z20/3
FAZ-Z20/4
25
FAZ-Z25/3
FAZ-Z25/4
32
FAZ-Z32/3
FAZ-Z32/4
40
FAZ-Z40/3
FAZ-Z40/4
50
FAZ-Z50/3
FAZ-Z50/4
63
FAZ-Z63/3
FAZ-Z63/4
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in additional delivery time.
3 Two-piece box order, quantities of 2.
1
1
1
1
V4-T1-74
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Accessories
1
FAZ Auxiliary Contacts and Voltage Trips
Circuit Diagram
Description
Rated Operational
Voltage
Catalog
Number
FAZ-XHIN11
1
1
Standard Auxiliary Contacts
14
12
■
■
■
■
1NO/1NC
Installs on left side of FAZ or shunt trip
Max. one per FAZ (1077) device
Switches when FAZ is tripped
electrically or manually
230 Vac
■
■
■
■
1 changeover contact
Installs on left side of FAZ or shunt trip
Max. one per FAZ (1077) device
Switches when FAZ is tripped
electrically or manually
230 Vac
1
1
1
FAZ-XHINW1
1
1
1
11
1
Auxiliary/Trip Indicating Contact
■
■
■
■
Small selector screw changes mode
Two Form C (changeover) contacts
Installs on left side of FAZ or shunt trip
Auxiliary contacts switch when FAZ is
tripped electrically or manually
■ Trip indicating contact switches only
when FAZ is tripped electrically
Two-pole auxiliary mode
230 Vac
FAZ-XAM002
1
1
1
1
1
1
Trip indicating mode
Undervoltage Trip
■ Prevents FAZ from operating unless
D1
voltage is present
■ Installs on left side of FAZ
■ Includes test button
U
D2
115 Vac
FAZ-XUA(115VAC)
230 Vac
FAZ-XUA(230VAC)
400 Vac
FAZ-XUA(400VAC)
1
1
1
1
1
Shunt Trip
■ Allows remote trip of FAZ
■ Installs on left side of FAZ
C1
C2
12–110 Vac
12–60 Vdc
FAZ-XAA-C-12-110VAC
110–415 Vac
110–230 Vdc
FAZ-XAA-C-110415VAC
1
1
1
1
1
Allowable Combinations of Accessories
AUX
AUX
TRIP
FAZ
or
AUX
1
FAZ
AUX
TRIP
1
FAZ
1
or
Circuit
Breaker
Shunt
Trip
Circuit
Breaker
UnderV
Trip
Circuit
Breaker
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1
V4-T1-75
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
1
Busbar System
1
Description
Without Auxiliary Contacts
1
For connecting FAZ supplementary protectors without auxiliary
contacts. May be fed from line or load side.
Rated Operational Current
Number of Poles
per Device
Number of
Terminals
Catalog
Number 1
80A
1
57
BB-UL-18/1P-1M/57
2
56
BB-UL-18/2P-2M/56
3
57
BB-UL-18/3P-3M/57
1
57
BB-UL-25/1P-1M/57
2
56
BB-UL-25/2P-2M/56
3
57
BB-UL-25/3P-3M/57
1
37
BB-UL-18/1P-1,5M/37
2
46
BB-UL-18/2P+AS-2,5M/46
3
48
BB-UL-18/3P+AS-3,5M/48
1
37
BB-UL-25/1P-1,5M/37
2
46
BB-UL-25/2P+AS-2,5M/46
3
48
BB-UL-25/3P+AS-3,5M/48
1
1
1
1
FAZ
FAZ
FAZ
100A
1
1
1
1
1
Auxiliary/Trip Indicating Contacts
1
For connecting FAZ supplementary protectors with auxiliary
contacts. May be fed from line or load side.
80A
1
1
1
1
FAZ
FAZ
100A
1
1
1
1
1
1
Note
1 Bus may be center fed for high current capacity.
1
1
1
1
1
1
1
V4-T1-76
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Incoming Terminal
Pin Type Incoming Supply Terminals
Description
Catalog
Number
■ Accommodates conductors
BB-UL-TEP/35
Incoming Terminal
Description
■
■
■
■
■
from 6–35 mm2/#10–2 AWG
■ 4–5.5 Nm/35–50 lb-in
■ Two- and three-pole
Fork Connector
Incoming Terminal
Pin Type Incoming Supply Terminals—
Single-Phase Only
Description
Catalog
Number
■ Accommodates conductors
BB-UL-TEPA/35
Bus Incoming Supply Terminals
50 mm2
#14–1 AWG
75 Deg wire
115 A/Y, 480V UL
160 A/Y 690V IEC
1
Catalog
Number
1
BB-UL-TE/50
1
1
1
Busbar End Cap
Description
Poles
Catalog
Number
■ Install after cutting busbar
■ Protects end of busbar
2 and 3
BB-EV-EC/3
1
BB-UL-EC/1
from 6–35 mm2/#10–2 AWG
■ 4–5.5 Nm/35–50 lb-in
Busbar Terminal Cover
For covering
unused terminals
1
1
1
1
Protective Accessories
Description
1
Catalog
Number
1
BB-IP/5
1
1
1
1
Lockoff Device
UL lockoff device
1
FAZPLOFF
1
1
1
1
Padlock Hasp
■ Prevents reactivation of the device
1
Z-IS/SPE-1TE
during maintenance
■ Holds one padlock
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-77
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
1
Technical Data and Specifications
1
Trip Curves Chart
Eaton FAZ supplementary
protectors are available with
six different tripping
characteristics, including
Type B, C, D, K, S and Z.
Definitions for each trip curve
are contained on the ordering
pages and can be used to
determine the optimal
characteristic for your
application. For example,
low-level short-circuit faults in
control wiring, such as PLCs,
are best protected by devices
with Type B trip characteristics
(3–5X continuous rating of the
device (In).
1
1
1
1
1
1
1
1.30
1.05
1.13
1.45
1
Tripping Characteristics
Even though not required by
NEC or CEC for supplementary
protectors, Eaton’s FAZ
devices are current limiting,
which means that they
interrupt fault currents
within one half cycle. Current
limiting devices offer superior
protection by reducing
peak let-through current
and energy.
7200
3600
Time-current characteristic acc. to UL 1077
Conventional
2.55 I :
N
non-tripping current
t = 1–60 s (IN < 32A)
t = 1–120 s (IN < 32A)
Int = 1.13 IN: t > 1 h
1200
600
300
Conventional tripping
current
It = 1.45 IN: t < 1 h
120
60
30
1
Type B: 5 I : t < 0.1 s
N
Type C: 5 I : t > 0.1 s
N
Type C: 10 I : t < 0.1 s
N
Type D: 10 I : t > 0.1 s
N
Type D: 20 I : t < 0.1 s
N
2
1
0.5
D
0.2
0.1
0.05
1
Type B: 3 I : t > 0.1 s
N
10
5
t (sec)
1.3
Z
B
C
K
S
0.02
0.01
0.005
1
0.002
0.001
0.0005
1
1
1
2
3
4 5 6 7 8 9 10 15 20
I/In
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-78
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
30 40 50
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
1.3
FAZ Miniature Circuit Breakers Technical Data
Description
B Curve
C Curve
1
D Curve
1
Electrical
Approvals
UR (UL 1077), CSA (CSA 22.2 No. 235), CE
1
Standards
IEC/EN 60947-2
Short-circuit trip response
3–5 In
5–10 In
10–20 In
1
1–63A
0.5–63A
0.5–40A
1
277 Vac
48 Vdc
277 Vac
48 Vdc
277 Vac
48 Vdc
1
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
1
Thermal tripping characteristics
Single-pole
Multi-pole
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
5 kA
5 kA
10 kA @ 48 Vdc
10 kA @ 96 Vdc
Current range
1–63A
0.5–63A
0.5–63A
Maximum voltage ratings—IEC 68898-1
Single-pole
Two-, three-pole
1
230 Vac
230/400 Vac
230 Vac
230/400 Vac
230 Vac
230/400 Vac
1
240 Vac
48 Vdc
240/415 Vac
96 Vdc
240 Vac
48 Vdc
240/415 Vac
96 Vdc
240 Vac
48 Vdc
240/415 Vac
96 Vdc
Thermal tripping characteristics
Single-pole
Multi-pole
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
Interrupt ratings (at max. voltage)
IEC 60947-2
IEC 60898
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA (10 kA for 50 and 63A)
10 kA (50 and 63A not available)
7.5 kA
125A
4000 Vac
440 Vac
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-pole, four-pole and
three-pole + neutral
Two poles in series
1
1
1
1
Miniature Circuit Breaker—IEC
Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
Two poles in series
1
1
1
1
1
1
1
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
1
1
1
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
Mounting
Degree of protection
Terminals top and bottom
Supply connection
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
Terminal capacity [mm2]
Torque
Imperial torque
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
Thickness of busbar material
Mounting position
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-79
1.3
1
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ Miniature Circuit Breakers Technical Data, continued
Description
K Curve
S Curve
Z Curve
1
Electrical
1
Approvals
UR (UL 1077), CSA (CSA 22.2 No. 235), CE
Standards
IEC/EN 60947-2, E177451, 204453
Short-circuit trip response
8–12 In
13–17 In
2–3 In
0.5–63A
0.5–40A
1–63A
277 Vac
48 Vdc
277 Vac
48 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
Thermal tripping characteristics
Single-pole
Multi-pole
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
Short-circuit ratings (at max. voltage)
Single-pole
Single-pole + neutral
Two-, three-, four-pole
Two poles in series
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
—
0.5–63A
0.5–40A
1–63A
240 Vac
240 Vac
240 Vac
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-, four-pole and
three-pole + neutral
Two poles in series
Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 60947-2
Single-pole, single-pole + neutral
Two-, three-, four-pole,
three-pole + neutral
240/415 Vac
240/415 Vac
240/415 Vac
Thermal tripping characteristics
Single-pole
Multi-pole
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
Interrupt ratings (at max. voltage)
IEC 60947-2
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
15 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
7.5 kA
125A
4000 Vac
440 Vac
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
Standard front dimension
Device height
Terminal protection
Mounting width per pole
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
Mounting
Degree of protection
Terminals top and bottom
Supply connection
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
Terminal capacity [mm2]
Torque
Imperial torque
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
Mechanical
Thickness of busbar material
Mounting position
1
1
1
V4-T1-80
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Let-Through Energy I2t
Let-Through Energy ID
Characteristic B and C
Characteristic B and C
∫i2dt 105
[A2s] 8
63 A
50 A
40 A
32 A
25 A
20 A
16 A
13 A
10 A
6
4
1
1
lD 104
9
[A] 8
63 A
50 A
40 A
32 A
25 A
16 A20 A
13 A
10 A
7
6
5
4
6A
4A
3A
2
1.5
6A
4A
104
3A
3
2A
1
1.5
4
1
103
2
1
1A
1.5
1
0.5 A
1 A
103
0.5 A
1
1
2A
6
1
1
2
8
1
5
6
1
4
1
8
1
3
2
0.5
1
1.5
2
3
4
5 6 7 8 910
15
0.5
1
1.5
2
3
4
5 6 7 8 910
15
1
Icc rms [kA]
Icc rms [kA]
Characteristic D
1
Characteristic D
5
∫i2dt 10
[A2s] 8
40 A
32 A
25 A
20 A
16 A
13 A
6
4
1
lD 104
9
[A] 8
40 A
32 A
25 A
20 A
16 A
13 A
10 A
6A
7
6
1
1
10 A
5
6A
4
1
3
1
2
1.5
2
1
1.5
1
104
8
6
4
1
103
1
2
1.5
1
103
5
6
1
4
1
8
0.5
1
1.5
2
3
4
5 6 7 8 910
15
Icc rms [kA]
2
1
0.5
1
1.5
2
3
4
5 6 7 8 910
15
1
Icc rms [kA]
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-81
1.3
1
1
1
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Let-Through Energy I2t
Characteristic K
lD
[A]
Characteristic S
lD
[A]
104
8
1
104
8
6
63 A
50 A
40 A
32 A 25 A
20 A
13 A 16 A
6
1
4
1
3
10 A
6A
4A
3A
4
2
2A
3
1
40 A
32 A
25 A
20 A
16 A
10 A
6A
4A
3A
2A
1.6 A
1
1.5
1A
1
2
1A
3
10
1
1.5
1
103
5
1
0.5 A
1
1
5
0.5
1
1
1
1
1
lD
[A]
3
4
5
6
7 8 9 10
0.5
104
8
6
1
3
1
2
Characteristic Z
4
1
1.5
Icc rms [kA]
1
1
1
63 A
50 A
40 A
32 A 25 A
20 A
16 A
10 A
8A
6A
2
4A
3A
1.5
2A
103
1
1
1
5
1.6 A
1A
1
0.5 A
1
0.5
1
1
1.5
2
3
4
5
6
7 8 9 10
Icc rms [kA]
V4-T1-82
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1
1.5
2
3
4
5
6
7 8 9 10
Icc rms [kA]
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature
1
Ambient Temperature T
In (A)
–40°C
–30°C
–20°C
–10°C
0°C
10°C
20°C
30°C
35°C
40°C
45°C
50°C
55°C
60°C
65°C
70°C
75°C
0.16
0.20
0.20
0.19
0.19
0.18
0.17
0.17
0.16
0.16
0.15
0.15
0.15
0.14
0.14
0.14
0.14
0.13
0.25
0.32
0.31
0.30
0.29
0.28
0.27
0.26
0.25
0.25
0.24
0.24
0.23
0.23
0.22
0.22
0.21
0.21
0.50
0.64
0.62
0.60
0.58
0.56
0.54
0.52
0.50
0.49
0.48
0.47
0.46
0.45
0.44
0.43
0.42
0.41
0.75
0.96
0.93
0.90
0.87
0.84
0.81
0.78
0.75
0.74
0.73
0.71
0.69
0.68
0.66
0.65
0.64
0.62
1.00
1.30
1.20
1.20
1.20
1.10
1.10
1.00
1.00
0.99
0.97
0.95
0.93
0.90
0.89
0.87
0.85
0.83
1.50
1.90
1.90
1.80
1.70
1.70
1.60
1.60
1.50
1.50
1.50
1.40
1.40
1.40
1.30
1.30
1.30
1.20
1.60
2.00
2.00
1.90
1.90
1.80
1.70
1.70
1.60
1.60
1.50
1.50
1.50
1.40
1.40
1.40
1.40
1.30
2.00
2.60
2.50
2.40
2.30
2.20
2.20
2.10
2.00
2.00
1.90
1.90
1.90
1.80
1.80
1.70
1.70
1.70
2.50
3.20
3.10
3.00
2.90
2.80
2.70
2.60
2.50
2.50
2.40
2.40
2.30
2.30
2.20
2.20
2.10
2.10
3.00
3.80
3.70
3.60
3.50
3.40
3.30
3.10
3.00
3.00
2.90
2.80
2.80
2.70
2.70
2.60
2.50
2.50
3.50
4.50
4.40
4.20
4.10
3.90
3.80
3.70
3.50
3.40
3.40
3.30
3.20
3.20
3.10
3.00
3.00
2.90
4.00
5.10
5.00
4.80
4.70
4.50
4.30
4.20
4.00
3.90
3.90
3.80
3.70
3.60
3.50
3.50
3.40
3.30
5.00
6.40
6.20
6.00
5.80
5.60
5.40
5.20
5.00
4.90
4.80
4.70
4.60
4.50
4.40
4.30
4.20
4.10
6.00
7.70
7.50
7.20
7.00
6.70
6.50
6.30
6.00
5.90
5.80
5.70
5.60
5.40
5.30
5.20
5.10
5.00
7.00
9.00
8.70
8.40
8.20
7.80
7.60
7.40
7.00
6.90
6.80
6.70
6.50
6.30
6.20
6.10
6.00
5.80
8.00
10.20
9.90
9.60
9.30
9.00
8.70
8.40
8.00
7.90
7.70
7.60
7.40
7.20
7.10
6.90
6.80
6.60
10.00
13.00
12.00
12.00
12.00
11.00
11.00
10.00
10.00
9.90
9.70
9.50
9.30
9.00
8.90
8.70
8.50
8.30
12.00
15.00
15.00
14.00
14.00
13.00
13.00
13.00
12.00
12.00
12.00
11.00
11.00
11.00
11.00
10.00
10.00
10.00
13.00
17.00
16.00
16.00
15.00
15.00
14.00
14.00
13.00
13.00
13.00
12.00
12.00
12.00
12.00
11.00
11.00
11.00
15.00
19.00
19.00
18.00
17.00
17.00
16.00
16.00
15.00
15.00
15.00
14.00
14.00
14.00
13.00
13.00
13.00
12.00
16.00
20.00
20.00
19.00
19.00
18.00
17.00
17.00
16.00
16.00
15.00
15.00
15.00
14.00
14.00
14.00
14.00
13.00
20.00
26.00
25.00
24.00
23.00
22.00
22.00
21.00
20.00
20.00
19.00
19.00
19.00
18.00
18.00
17.00
17.00
17.00
25.00
32.00
31.00
30.00
29.00
28.00
27.00
26.00
25.00
25.00
24.00
24.00
23.00
23.00
22.00
22.00
21.00
21.00
32.00
41.00
40.00
38.00
37.00
36.00
35.00
33.00
32.00
32.00
31.00
30.00
30.00
29.00
28.00
28.00
27.00
26.00
35.00
45.00
43.00
41.00
41.00
38.00
38.00
36.00
35.00
35.00
34.00
33.00
32.00
32.00
32.00
30.00
29.00
29.00
40.00
51.00
50.00
48.00
47.00
45.00
43.00
42.00
40.00
39.00
39.00
38.00
37.00
36.00
35.00
35.00
34.00
33.00
50.00
64.00
62.00
60.00
58.00
56.00
54.00
52.00
50.00
49.00
48.00
47.00
46.00
45.00
44.00
43.00
42.00
41.00
63.00
81.00
78.00
76.00
73.00
71.00
68.00
66.00
63.00
62.00
61.00
60.00
58.00
57.00
56.00
55.00
53.00
52.00
IMA(f)IMA (50 Hz) [%]
60
100
200
300
400
91
100
101
106
115
134
141
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Load Carrying Capacity of Adjoining Miniature Circuit Breakers
1
1.00
Rated Diversity Factor
1
1
Mains Frequency f [Hz]
50
1
1
Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA
of the instantaneous release
16 2/3
1
1
1
0.90
1
1
0.80
1
0.70
1
2
3
4
5
6
7
1
8
Number of Circuit Breakers
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-83
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
1
Accessories Technical Data
1
Description
FAZ-XHIN
FAZ-XAM002
FAZ-XAA-C
FAZ-XUA
Contact function
1A + 1B
2 C/O
—
—
—
—
Rated operational voltage Un
250 Vac
—
1
115 Vac
230 Vac
400 Vac
Voltage range
—
—
1
12–110 Vac
12–60 Vdc
Voltage range
—
110–415 Vac
110–230 Vdc
—
1
1
1
1
1
1
1
1
1
Electrical
Closing threshold [x Un]
—
—
0.8
Tripping threshold [x Un]
—
—
0.5
Rated frequency ƒ
50/60 Hz
50/60 Hz
50/60 Hz
General use (UL/CSA)
AC—230/240 Vac
DC—110/120 Vdc
2/2A
0.5/0.5A
—
—
—
—
Pilot duty
A600/Q600
—
—
Conventional free air thermal current Ith
4A
—
—
Rated operational current
AC-13 Ie
AC-15 Ie
DC-13 Ie
3A (250 Vac)
2A (250 Vac)
0.5A (110 Vdc)
—
—
—
—
—
—
—
Rated insulation voltage Ui
250 Vac
—
Minimum operating voltage per contract Umin
5 Vdc
—
—
Rated impulse withstand voltage (1.2/50μ) Uimp
2.5 kV
—
—
1
Rated conditional short-circuit current with 6A backup fuse ISC
1 kA
—
—
Max. admissible backup fuse
4A gL
—
—
1
Mechanical
1
Standard front dimension
45 mm
45 mm
45 mm
Device height
80 mm
80 mm
80 mm
1
1
Mounting width
8.8 mm
17.6 mm
17.8 mm
Mounting
On MCB
IEC/EN 60715 top-hat rail
IEC/EN 60715 top-hat rail
IP40
IP40
IP40
1
Degree of protection enclosed
1
Terminal protection
Protection against
electric shock to IEC 536
Protection against
electric shock to IEC 536
Protection against
electric shock to IEC 536
1
Terminals
Lift terminals
Twin-purpose terminals
Twin-purpose terminals
Terminal capacity
Solid
Flexible
0.5–2.5 mm2
0.5–2.5 mm2
1–2.5 mm2
1–2.5 mm2
2 x (1–2.5) mm2
2 x (1–2.5) mm2
Tightening torque of terminal screws
0.8–1.0 Nm (7–9 lb-in)
2.4 Nm (21 lb-in)
0.8 Nm (7 lb-in)
1
1
1
1
1
1
1
1
1
V4-T1-84
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
1.3
Dimensions
Approximate Dimensions in Inches (mm)
1
Miniature Circuit Breakers
1
1
FAZ
0.74
(9.4)
1
1
1.77
(45.0)
3.15
(80.0)
1
1
1.40
(35.4)
0.70
(17.8)
2.09
(53.1)
0.22
(5.5)
2.79
(70.8)
1
1.73
(44.0)
1
2.36
(60.0)
1
1
Auxiliary Contacts
FAZ-XHI11 and FAZ-XH1NW1
FAZ-XAM002
1
1
3.15
(80.0)
3.15
(80.0)
1.77
(45.0)
1
1.77
(45.0)
1
1
0.35
(8.8)
0.22
(5.5)
1.73
(44.0)
0.35
(8.8)
2.36
(60.0)
0.22
(5.5)
Shunt Releases
Undervoltage Releases
FAZ-XAA
FAZ-XUA
1.73
(44.0)
1
1
2.36
(60.0)
1
1
1
3.15
(80.0)
1.77
(45.0)
3.15
(80.0)
1
1.77
(45.0)
1
1
0.70
(17.8)
1.03
(26.2)
0.22
(5.5)
1.20
(30.5)
1.73
(44.0)
0.39
(10.0)
2.36
(60.0)
0.70
(17.8)
0.22
(5.5)
1.73
(44.0)
1
1
2.36
(60.0)
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-85
1.3
1
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Approximate Dimensions in Inches (mm)
1
Busbar and Accessory Weights and Dimensions
1
Unit Weight (kg)
Length
Width
Height
Catalog
Number
0.29
39.72 (1009.0)
0.59 (15.0)
0.59 (15.0)
BB-UL-18/1P-1M/57
0.64
39.02 (991.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-18/2P-2M/56
1
0.83
39.72 (1009.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-18/3P-3M/57
1
0.26
38.78 (985.0)
0.59 (15.0)
0.59 (15.0)
BB-UL-18/1P-1.5M/37
0.63
39.72 (1009.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-18/2P+AS-2.5M/46
1
0.79
38.66 (982.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-18/3P+AS-3.5M/48
0.36
39.72 (1009.0)
0.59 (15.0)
0.59 (15.0)
BB-UL-25/1P-1M/57
1
0.79
39.02 (991.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-25/2P-2M/56
1
1.04
39.72 (1009.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-25/3P-3M/57
1
0.31
38.78 (985.0)
0.59 (15.0)
0.59 (15.0)
BB-UL-25/1P-1.5M/37
1
0.73
39.72 (1009.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-25/2P+AS-2.5M/46
0.97
38.66 (982.0)
0.87 (22.0)
1.46 (37.0)
BB-UL-25/3P+AS-3.5M/48
1
0.03
2.36 (60.0)
0.67 (17.0)
1.14 (29.0)
BB-UL-TEP/35
0.03
1.42 (36.0)
0.67 (17.0)
1.14 (29.0)
BB-UL-TEPA/35
1
0.03
1.57 (40.0)
0.71 (18.0)
1.18 (30.0)
BB-UL-TE/50
1
0.003
3.35 (85.0)
0.47 (12.0)
0.94 (24.0)
BB-IP/5
0.001
0.55 (14.0)
0.20 (5.0)
0.39 (10.0)
BB-EV-EC/3
0.001
0.94 (24.0)
0.87 (22.0)
0.39 (10.0)
BB-UL-EC/1
1
1
L
1
W
1
1
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-86
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
L1
L2
H
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
1.4
Contents
UL 1053 DIN Rail RCCB
Description
UL 1053 DIN Rail RCCB 480/277 Vac
Product Selection . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .
UL 1053 DIN Rail RCCB 208Y/120 Vac. . . . . . . . . . . . .
Page
V4-T1-88
V4-T1-89
V4-T1-90
V4-T1-91
V4-T1-93
1
1
1
1
1
1
1
1
1
1
1
UL 1053 DIN Rail RCCB 480/277 Vac
Product Overview
Features
Optimum product quality,
tested reliability and safety
stand for best protection of
installations and plant.
Eaton’s UL 1053 Residual
Current Circuit Breaker
(RCCB) is designed for use in
residual current applications.
●
Application Description
●
●
●
●
●
●
Motor control circuits
HVAC internal/external
equipment
PLCs
HMIs
Equipment protection
European housing
●
●
●
●
●
●
●
1
Standards and Certifications
Wide range of compact
RCCB types serving as
fault-current and additional
protection according to
UL 1053 and IEC/EN 61008
standards, suitable for
worldwide use
Type A or Type G/A (with
delay) protection available
Comprehensive range of
accessories
Real contact position
indicator
Fault current tripping
indicator
Transparent designation
plate
Trip-free design—RCCB
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
●
●
●
●
●
UL 1053
IEC/EN 61008
CSA
ÖVE
CE Marked
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-87
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
1
Product Selection
1
UL 1053 RCCB 480Y/277V Type A
1
Two-Pole
Conditionally Surge Current–Proof 250A, Sensitive to Residual Pulsating DC, Type A
Two-Pole
Amperes
GF Sensitivity
(mA)
Catalog
Number 1
Designation
1
25
30
167113
FRCmM-25/2/003-A-NA
300
167116
FRCmM-25/2/03-A-NA
1
40
30
167114
FRCmM-40/2/003-A-NA
300
167117
FRCmM-40/2/03-A-NA
30
167115
FRCmM-63/2/003-A-NA
300
167118
FRCmM-63/2/03-A-NA
1
1
63
1
1
Four-Pole
Conditionally Surge Current–Proof 250A, Sensitive to Residual Pulsating DC, Type A
Four-Pole
1
1
Amperes
GF Sensitivity
(mA)
Catalog
Number 1
Designation
25
30
167125
FRCmM-25/4/003-A-NA
300
167104
FRCmM-25/4/03-A-NA
30
167102
FRCmM-40/4/003-A-NA
300
167105
FRCmM-40/4/03-A-NA
30
167103
FRCmM-63/4/003-A-NA
300
167106
FRCmM-63/4/03-A-NA
1
40
1
63
1
1
1
1
UL 1053 RCCB 480Y/277V Type G/A
Type G/A has a 10 ms delay.
Two-Pole
Surge Current–Proof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (ÖVE E 8601)
Two-Pole
1
Amperes
GF Sensitivity
(mA)
Catalog
Number 1
Designation
1
25
30
167119
FRCmM-25/2/003-G/A-NA
300
167122
FRCmM-25/2/03-G/A-NA
1
40
30
167120
FRCmM-40/2/003-G/A-NA
1
300
167123
FRCmM-40/2/03-G/A-NA
63
30
167121
FRCmM-63/2/003-G/A-NA
300
167124
FRCmM-63/2/03-G/A-NA
1
1
Four-Pole
Surge Current–Proof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (ÖVE E 8601)
Four-Pole
1
Amperes
GF Sensitivity
(mA)
Catalog
Number 1
Designation
1
25
30
167107
FRCmM-25/4/003-G/A-NA
300
167110
FRCmM-25/4/03-G/A-NA
1
40
30
167108
FRCmM-40/4/003-G/A-NA
1
300
167111
FRCmM-40/4/03-G/A-NA
63
30
167109
FRCmM-63/4/003-G/A-NA
300
167112
FRCmM-63/4/03-G/A-NA
1
Note
1 Has no thermal element; must be paired with FAZ-NA or FAZ per application.
1
1
V4-T1-88
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
Accessories
1
UL 1053 DIN Rail RCCB 480/277 Vac
Contact
Description
Catalog Number
Two-pole contact or auxiliary
contact / trip indicating contact
Z-NHK 1
Padlock Hasp
Description
Catalog Number
Padlock hasp
Z-IS/SPE-1TE
1
1
1
1
1
Lockoff Device
UL lockoff device
1
FAZPLOFF
1
1
1
1
Note
1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-89
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
1
Technical Data and Specifications
1
●
1
●
1
●
●
●
1
●
1
●
●
1
1
●
●
1
1
1
●
●
●
1
1
●
1
1
●
1
●
1
1
1
1
Residual current devices
Has no thermal protection; must be paired with FAZ-NA
or FAZ per application
Captive screw terminals
Universal tripping signal switch, also suitable for Z-A; can be
mounted subsequently
Auxiliary switch Z-HK can be mounted subsequently
Red-green contact position indicator
White-blue tripping indicator
Delayed types recommended for use with standard
fluorescent tubes with or without electronical ballast
(30mA-RCD: 30 units per phase conductor,
100mA-RCD: 90 units per phase conductor)
The device functions irrespective of the position of installation
Tripping is line voltage-independent. Consequently, the RCD is
suitable for “fault current/residual current protection” and
“additional protection” within the meaning of the applicable
installation rules
Reverse-feed permitted
The four-pole device can also be used for two-pole
connection. For this purpose, use terminals 5-6 and N-N
The test key “T” must be pressed every month. The system
operator must be informed of this obligation and responsibility
in a way that can be proven (self-adhesive RCD-label enclosed)
Pressing the test key “T” serves the only purpose of function
testing the residual current device (RCD). This test does not
make earthing resistance measurement (RE) or proper
checking of the earth conductor condition redundant, which
must be performed separately
Type -A: Protects against special forms of residual pulsating
DC that have not been smoothed
Type -G/A: Additionally protects against special forms of
residual pulsating DC that have not been smoothed
UL 1053 DIN Rail RCCB Technical Data, continued
Description
Specification
Electrical According to UL 1053
Design according to
UL 1053
Current test marks as printed onto the device
Tripping Type G
8 ms delay
Rated voltage Un
480Y/277V, 60 Hz
Pickup current
22, 200 mA
Sensitivity
AC and pulsating DC
Overvoltage tested
530V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit capacity Inc
5 kA according to CSA
Maximum backup fuse
Overload protection
Short-circuit protection
In = 25–40A
25A gG/gL
63A gG/gL
In = 63A
40A gG/gL
63A gG/gL
Rated breaking capacity Im or
Rated fault breaking capacity I m
In = 25–40A
In = 63A
Voltage range of test button
Endurance
500A
630A
Two-pole
184–305V~
Four-pole
184–528V~
Electrical
>4000 operating cycles
Mechanical
>20,000 operating cycles
Mechanical
Frame size
45.0 mm
Device height
80.0 mm
Device width
35 mm (2TE), 70 mm (4TE)
Device width
Quick fastening with two
lock-in positions on DIN
rail IEC/EN 60715
Degree of protection, built-in
IP40
UL 1053 DIN Rail RCCB Technical Data
Degree of protection in moisture-proof
enclosure
IP54
Description
Upper and lower terminals
Lift terminals
Terminal protection
Finger and hand touch
safe BGV A3, ÖVE-EN 6
Specification
Electrical According to IEC/EN 61008
Design according to
IEC/EN 61008
Terminal capacity
ÖVE E 8601
1.5–35 mm2 single-wire
2 x 16 mm2 multi-wire
Current test marks as printed onto the device
1
Tripping Type G
10 ms delay
Busbar material thickness
0.8–2 mm
Rated voltage Un
230/400V, 50 Hz
Tripping temperature
–25°C to +60°C
1
Rated tripping current I n
Sensitivity
30, 300 mA
Resistance to climatic conditions
According to IEC 61008
AC and pulsating DC
Humidity
5–95%
1
1
1
1
1
Rated insulation voltage Ui
440V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit capacity Inc
10 kA
Maximum backup fuse
Overload protection
Short-circuit protection
In = 25–40A
25A gG/gL
63A gG/gL
In = 63A
40A gG/gL
63A gG/gL
Rated breaking capacity Im bzw.
Rated fault breaking capacity I m
In = 25–40A
500A
In = 63A
630A
1
Voltage range of test button
1
Endurance
1
Overvoltage category
V4-T1-90
Two-pole
184–250V~
Four-pole
184–440V~
Electrical
>4000 operating cycles
Mechanical
>20,000 operating cycles
III
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
Connection Diagram
Impact of Ambient Temperature on the Maximum
Permanent Current Allowed (A)
1 N
1 3 5 N
T
16A
25A
40A
1
63A
Tripping
Temperature
TwoPole
FourPole
TwoPole
FourPole
TwoPole
FourPole
TwoPole
FourPole
40°C
16
16
25
25
40
40
63
63
T
2 N
Two-Pole
45°C
14
14
21
22
37
37
59
59
2 4 6 N
50°C
11
11
18
19
33
34
55
55
Four-Pole
55°C
9
9
14
16
30
31
50
50
60°C
1
—
—
—
26
27
45
45
Notes
1 Do not use.
Please make sure that these values are not exceeded and that any upstream overload protection
switches off in time.
Correct Connection
1
1
1
1
1
1
1
1
1
1
1
1
3+N
(230/400V) IEC
(277/480V) UL
Three-phase load without N
(184–254 Vac Phase-Phase) IEC
(184–277 Vac Phase-Phase) UL
Three-phase load without N
(400 Vac Phase-Phase) IEC
(480 Vac Phase-Phase) UL
1+N
(230V) IEC
(277V) UL
1
1
1
Dimensions
1
Approximate Dimensions in Inches (mm)
UL 1053 DIN Rail RCCB
0.22
(5.5)
1.20
(30.5)
1
0.18
(4.5)
1
1
1
3.15
(80.0)
1.77
(45.0)
1
1
2.76
(70.0)
Four-Pole
1
0.41
(10.5)
1.73
(44.0)
1
2.36
(60.0)
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-91
1.4
1
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
Accessories Technical Data
Description
Z-NHK
1
Electrical
1
Rated voltage
230V
Frequency
50/60 Hz
1
Contact function
2CO
Rated current
2A
Rated thermal current Ith
2A
3A/250 Vac
1
Utilization category AC13
Rated operational current Ie
Utilization category AC15
Rated operational current Ie
2A/250 Vac
1
Utilization category DC12
Rated operational current Ie
0.5A/110 Vdc
1
Rated insulation voltage UI
250 Vac
Minimum operational voltage per contact Umin
5 Vdc
1
Minimum operational current Imin
10 mA DC
Rated peak withstand voltage Uimp (1.2/50μ)
2.5 kV
1
1
Conditional short-circuit current Ik with backup fuse 6A
1 kA
Maximum backup fuse, overload and short circuit
6A gL
1
Mechanical
Tripping indicator “electrical tripping”
Blue/white
1
Frame size
45 mm
1
Device height
80 mm
Device width
8.8 mm (0.5MU)
Mounting
Onto switching device
Degree of protection, built-in
IP40
Terminal protection
Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
Terminals
Lift terminals
1
Terminal capacity
20–14 AWG
1
Terminal screws
M3 (Posidrive Z0)
Fastening torque of terminal screws
7 lb-in maximum
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-92
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
1.4
Contents
UL 1053 DIN Rail RCCB
Description
UL 1053 DIN Rail RCCB 480/277 Vac . . . . . . . . . .
UL 1053 DIN Rail RCCB 208Y/120 Vac
Product Selection . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
V4-T1-87
V4-T1-94
V4-T1-95
V4-T1-96
V4-T1-97
1
1
1
1
1
1
1
1
1
1
1
UL 1053 DIN Rail RCCB 208Y/120 Vac
Product Overview
Features
Optimum product quality,
tested reliability and safety
stand for best protection of
installations and plant.
Eaton’s UL 1053 Residual
Current Circuit Breaker
(RCCB) is designed for use in
residual current applications.
●
Application Description
●
●
●
●
●
Motor control circuits
HVAC internal/external
equipment
PLCs
HMIs
Equipment protection
●
●
●
●
●
●
●
1
Standards and Certifications
Wide range of compact
RCD type serving as faultcurrent and additional
protection according to
UL 1053 and IEC/EN 61008
standards, suitable for
worldwide use in the 110V
range of applications
Type A or Type G/A (with
delay) protection available
Comprehensive range of
accessories
Real contact position
indicator
Fault current tripping
indicator
Transparent designation
plate
Trip-free design—RCCB
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
●
●
UL 1053
IEC/EN 61008
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-93
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
1
Product Selection
1
UL 1053 RCCB 208Y/120 Vac Type A
1
Four-Pole
Conditionally Surge Current–Proof 250A, Sensitive to Residual Pulsating DC, Type A
Four-Pole
1
Amperes
1
25
GF Sensitivity
(mA)
Catalog
Number 1
Designation
FRCmM-25/4/003-A-NA-110
30
167699
300
167702
FRCmM-25/4/03-A-NA-110
167700
FRCmM-40/4/003-A-NA-110
1
40
30
1
300
167703
FRCmM-40/4/03-A-NA-110
63
30
167701
FRCmM-63/4/003-A-NA-110
300
167704
FRCmM-63/4/03-A-NA-110
1
1
1
1
UL 1053 RCCB 208Y/120 Vac Type G/A
Type G/A has a 10 ms delay.
Two-Pole
Surge Current–Proof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (ÖVE E 8601)
Two-Pole
1
Amperes
1
25
1
40
1
63
1
1
1
Four-Pole
GF Sensitivity
(mA)
Catalog
Number 1
Designation
30
167693
FRCmM-25/2/003-G/A-NA-110
300
167696
FRCmM-25/2/03-G/A-NA-110
30
167694
FRCmM-40/2/003-G/A-NA-110
300
167697
FRCmM-40/2/03-G/A-NA-110
30
167695
FRCmM-63/2/003-G/A-NA-110
300
167698
FRCmM-63/2/03-G/A-NA-110
Surge Current–Proof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (ÖVE E 8601)
Four-Pole
1
Amperes
25
GF Sensitivity
(mA)
Catalog
Number 1
Designation
FRCmM-25/4/003-G/A-NA-110
30
167705
300
167708
FRCmM-25/4/03-G/A-NA-110
1
40
30
167706
FRCmM-40/4/003-G/A-NA-110
300
167709
FRCmM-40/4/03-G/A-NA-110
1
63
30
167707
FRCmM-63/4/003-G/A-NA-110
300
167710
FRCmM-63/4/03-G/A-NA-110
1
1
Note
1 Has no thermal element; must be paired with FAZ-NA or FAZ per application.
1
1
1
1
1
1
1
V4-T1-94
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
Accessories
1
UL 1053 DIN Rail RCCB 208Y/120 Vac
Contact
Description
Catalog Number
Two-pole contact or auxiliary
contact / trip indicating contact
Z-NHK 1
Padlock Hasp
Description
Catalog Number
Padlock hasp
Z-IS/SPE-1TE
1
1
1
1
1
Lockoff Device
UL lockoff device
1
FAZPLOFF
1
1
1
1
Note
1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-95
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
1
Technical Data and Specifications
1
●
1
●
1
●
●
●
1
●
1
●
●
1
1
●
●
1
1
1
●
●
●
1
1
●
1
1
●
1
●
1
1
1
1
Residual current devices
Has no thermal protection; must be paired with FAZ-NA
or FAZ per application
Captive screw terminals
Universal tripping signal switch, also suitable for Z-A; can be
mounted subsequently
Auxiliary switch Z-HK can be mounted subsequently
Red-green contact position indicator
White-blue tripping indicator
Delayed types recommended for use with standard
fluorescent tubes with or without electronical ballast
(30mA-RCD: 30 units per phase conductor,
100mA-RCD: 90 units per phase conductor)
The device functions irrespective of the position of installation
Tripping is line voltage-independent. Consequently, the RCD is
suitable for “fault current/residual current protection” and
“additional protection” within the meaning of the applicable
installation rules
Reverse-feed permitted
The four-pole device can also be used for two-pole
connection. For this purpose, use terminals 5-6 and N-N
The test key “T” must be pressed every month. The system
operator must be informed of this obligation and responsibility
in a way that can be proven (self-adhesive RCD-label enclosed)
Pressing the test key “T” serves the only purpose of function
testing the residual current device (RCD). This test does not
make earthing resistance measurement (RE) or proper
checking of the earth conductor condition redundant, which
must be performed separately
Type -A: Protects against special forms of residual pulsating
DC that have not been smoothed
Type -G/A: Additionally protects against special forms of
residual pulsating DC that have not been smoothed
UL 1053 DIN Rail RCCB Technical Data
Description
Specification
UL 1053 DIN Rail RCCB Technical Data, continued
Description
Electrical According to UL1053
Design according to
IEC/EN 61008
UL 1053
Current test marks as printed onto the device
Tripping Type G
8 ms delay
Rated voltage Un
208Y/120V, 60 Hz
Pickup current
22, 200 mA
Sensitivity
AC and pulsating DC
Overvoltage tested
530V
Rated impulse withstand voltage Uimp
4 kV
Rated short-circuit capacity Inc
5 kA according to CSA
Maximum backup fuse
Overload protection
Short-circuit protection
In = 25–40A
25A gG/gL
63A gG/gL
In = 63A
40A gG/gL
63A gG/gL
Rated breaking capacity Im or
Rated fault breaking capacity I m
In = 25–40A
In = 63A
Voltage range of test button
Endurance
500A
630A
Two-pole
100–121V~
Four-pole
100–210V~
Electrical
>4000 operating cycles
Mechanical
>20,000 operating cycles
Mechanical
Frame size
45.0 mm
Device height
80.0 mm
Device width
35 mm (2TE), 70 mm (4TE)
Device width
Quick fastening with two
lock-in positions on DIN
rail IEC/EN 60715
Degree of protection, built-in
IP40
Degree of protection in moisture-proof
enclosure
IP54
Upper and lower terminals
Lift terminals
Terminal protection
Finger and hand touch
safe BGV A3, ÖVE-EN 6
Terminal capacity
1.5–35 mm2 single-wire
Electrical According to IEC/EN 61008
Design according to
Specification
2 x 16 mm2 multi-wire
ÖVE E 8601
Current test marks as printed onto the device
Busbar material thickness
0.8–2 mm
1
Tripping Type G
10 ms delay
Tripping temperature
–25°C to +60°C
Rated voltage Un
230/400V, 50 Hz
Resistance to climatic conditions
According to IEC 61008
1
Rated tripping current I n
Sensitivity
30, 300 mA
Humidity
5–95%
1
Rated insulation voltage Ui
440V
Rated impulse withstand voltage Uimp
4 kV
1
Rated short-circuit capacity Inc
10 kA
Maximum backup fuse
Overload protection
1
1
1
AC and pulsating DC
Short-circuit protection
In = 25–40A
25A gG/gL
63A gG/gL
In = 63A
40A gG/gL
63A gG/gL
Rated breaking capacity Im bzw.
Rated fault breaking capacity I m
In = 25–40A
500A
In = 63A
630A
1
Voltage range of test button
1
Endurance
1
Overvoltage category
V4-T1-96
Two-pole
100–132V~
Four-pole
100–230V~
Electrical
>4000 operating cycles
Mechanical
>20,000 operating cycles
III
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
1.4
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
Connection Diagram
Impact of Ambient Temperature on the Maximum
Permanent Current Allowed (A)
1 N
1 3 5 N
T
16A
25A
40A
1
63A
Tripping
Temperature
TwoPole
FourPole
TwoPole
FourPole
TwoPole
FourPole
TwoPole
FourPole
40°C
16
16
25
25
40
40
63
63
T
2 N
Two-Pole
45°C
14
14
21
22
37
37
59
59
2 4 6 N
50°C
11
11
18
19
33
34
55
55
Four-Pole
55°C
9
9
14
16
30
31
50
50
60°C
1
—
—
—
26
27
45
45
Notes
1 Do not use.
Please make sure that these values are not exceeded and that any upstream overload protection
switches off in time.
Correct Connection
1
1
1
1
1
1
1
1
1
1
1
1
3+N
(230/400V) IEC
(277/480V) UL
Three-phase load without N
(184–254 Vac Phase-Phase) IEC
(184–277 Vac Phase-Phase) UL
Three-phase load without N
(400 Vac Phase-Phase) IEC
(480 Vac Phase-Phase) UL
1+N
(230V) IEC
(277V) UL
1
1
1
Dimensions
1
Approximate Dimensions in Inches (mm)
UL 1053 DIN Rail RCCB
0.22
(5.5)
1.20
(30.5)
1
0.18
(4.5)
1
1
1
3.15
(80.0)
1
1.77
(45.0)
1
2.76
(70.0)
Four-Pole
1
0.41
(10.5)
1.73
(44.0)
1
2.36
(60.0)
1
1
1
1
1
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com
V4-T1-97
1.4
1
Miniature Circuit Breakers and Supplementary Protectors
UL 1053 DIN Rail RCCB
Accessories Technical Data
Description
Z-NHK
Z-IHK-NA
1NO + 1NC
1
Electrical
1
Contact function
2CO
Rated voltage
230V
250V
Frequency
50/60 Hz
50/60 Hz
1
Rated current
2A
6A
Rated thermal current Ith
2A
6A
Utilization category AC13
Rated operational current Ie
3A/250 Vac
3A/250 Vac
Utilization category AC15
Rated operational current Ie
2A/250 Vac
2A/250 Vac
Utilization category DC12
Rated operational current Ie
0.5A/110 Vdc
0.5A/110 Vdc
0.25A/220 Vdc
Rated insulation voltage UI
250 Vac
250 Vac
1
Minimum operational voltage per contact Umin
5 Vdc
5 Vdc
Minimum operational current Imin
10 mA DC
10 mA AC/DC
1
Rated peak withstand voltage Uimp (1.2/50μ)
2.5 kV
4 kV
Conditional short-circuit current Ik with backup fuse 6A
1 kA
1 kA
1
Maximum backup fuse, overload and short circuit
6A gL
—
1
Tripping indicator “electrical tripping”
Blue/white
—
Frame size
45 mm
45 mm
1
1
1
1
Mechanical
1
Device height
80 mm
80 mm
Device width
8.8 mm (0.5MU)
8.8 mm (0.5MU)
1
Mounting
Onto switching device
—
Degree of protection, built-in
IP40
IP40
Terminal protection
Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
1
1
1
Terminals
Lift terminals
Lift terminals
Terminal capacity
20–14 AWG
0.5–2.5 mm2
Terminal screws
M3 (Posidrive Z0)
M3 (Posidrive Z0)
Fastening torque of terminal screws
7 lb-in maximum
1.2 Nm
1
1
1
1
1
1
1
1
1
1
1
1
1
V4-T1-98
Volume 4—Circuit Protection CA08100005E—November 2016 www.eaton.com