58 SERIES
Relay interface modules 7 - 10 A
58
SERIES
58.P3
3 & 4 CO relay interface modules,
31 mm wide with Push-in terminals
58.P4
Ideal interface for PLC and electronic systems
Type 58.P3
-- 3 CO 10 A
-- Push-in terminals
Type 58.P4
-- 4 CO 7 A
-- Push-in terminals
B
• AC coils or DC coils
• Supply status indication and EMC coil
• 3 CO 10 A
• Push-in terminals
suppression module as standard
• Identification label
• Cadmium Free contacts
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• 4 CO 7 A
• Push-in terminals
58.P3 / 58.P4
Push-in terminals
For outline drawing see page 7
Example: AC
Example: DC
3 CO (3PDT)
4 CO (4PDT)
10/20
7/15
250/400
250/250
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
Rated load AC1
VA
2500
1750
Rated load AC15 (230 V AC)
VA
500
350
Single phase motor rating (230 V AC)
kW
0.37
0.125
Breaking capacity DC1: 30/110/220 V
A
10/0.25/0.12
7/0.25/0.12
300 (5/5)
300 (5/5)
AgNi
AgNi
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 125
12 - 24 - 48 - 125
Minimum switching load
mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
V DC
Rated power AC/DC
Operating range
VA (50 Hz)/W
AC
DC
1.5/1
1.5/1
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
AC/DC
0.8 UN / 0.5 UN
0.8 UN / 0.5 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life AC/DC
cycles
20 · 106 / 50 · 106
20 · 106 / 50 · 106
Electrical life at rated load AC1
cycles
200 · 103
150 · 103
ms
10/5 (AC) - 10/15 (DC)
11/3 (AC) - 11/15 (DC)
kV
3.6
3.6
1000
1000
–40…+70
–40…+70
IP 20
IP 20
Technical data
X-2016, www.findernet.com
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
V AC
°C
Approvals relay (according to type)
1
58
SERIES
58 SERIES
Relay interface modules 7 - 10 A
58.32
2, 3 & 4 CO relay interface modules,
27 mm wide with Screw terminals
58.33
58.34
Ideal interface for PLC and electronic systems
Type 58.32
-- 2 CO 10 A
-- Screw terminals
Type 58.34
-- 4 CO 7 A
-- Screw terminals
• 2 CO 10 A
• Screw terminals
• AC coils or DC coils
• Supply status indication and EMC coil
• 3 CO 10 A
• Screw terminals
• 4 CO 7 A
• Screw terminals
suppression module as standard
• Identification label
• Cadmium Free contacts
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
58.32 / 58.33 / 58.34
Screw terminals
For outline drawing see page 7
Example: AC
Example: DC
Example: AC
2 CO (DPDT)
3 CO (3PDT)
4 CO (4PDT)
10/20
10/20
7/15
250/400
250/400
250/250
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
Rated load AC1
VA
2500
2500
1750
Rated load AC15 (230 V AC)
VA
500
500
350
Single phase motor rating (230 V AC)
kW
0.37
0.37
0.125
Breaking capacity DC1: 30/110/220 V
A
10/0.25/0.12
10/0.25/0.12
7/0.25/0.12
300 (5/5)
300 (5/5)
300 (5/5)
AgNi
AgNi
AgNi
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 125
12 - 24 - 48 - 125
12 - 24 - 48 - 125
Minimum switching load
mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
V DC
Rated power AC/DC
Operating range
VA (50 Hz)/W
AC
DC
1.5/1
1.5/1
1.5/1
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
AC/DC
0.8 UN / 0.5 UN
0.8 UN / 0.5 UN
0.8 UN / 0.5 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life AC/DC
cycles
20 · 106 / 50 · 106
20 · 106 / 50 · 106
20 · 106 / 50 · 106
Electrical life at rated load AC1
cycles
200 · 103
200 · 103
150 · 103
ms
10/5 (AC) - 10/15 (DC)
10/5 (AC) - 10/15 (DC)
11/3 (AC) - 11/15 (DC)
kV
3.6
3.6
3.6
1000
1000
1000
–40…+70
–40…+70
–40…+70
IP 20
IP 20
IP 20
Technical data
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
2
V AC
°C
X-2016, www.findernet.com
B
Type 58.33
-- 3 CO 10 A
-- Screw terminals
58 SERIES
Relay interface modules 6 - 9 - 10 A
58
SERIES
58.32 - x0xx
2, 3 & 4 CO relay interface modules,
27 mm wide with Screw terminals
58.33 - x0xx
58.34 - x0xx
ATEX compliant (EX nA nC)
Type 58.32 - x0xx
-- 2 CO 10 A
-- Screw terminals
Type 58.33 - x0xx
-- 3 CO 9 A
-- Screw terminals
B
Type 58.34 - x0xx
-- 4 CO 6 A
-- Screw terminals
• 2 CO 10 A
• Screw terminals
• ATEX compliant
• AC coils or DC coils
• Supply status indication and EMC coil
suppression module as standard
• 3 CO 9 A
• Screw terminals
• ATEX compliant
• 4 CO 6 A
• Screw terminals
• ATEX compliant
• Mechanical indicator - optional on 2 & 4 CO
types
• Identification label
• Cadmium Free contacts
• UL Listed
• Complies with:
--EN 60079-0:2012 and EN 60079-15:2010
--94/9/CE and 2014/34/UE
• 35 mm rail (EN 60715) mounting
58.32 / 58.33 / 58.34 - x0xx
Screw terminals
For outline drawing see page 7
Example: DC
Example: AC
Example: DC
2 CO (DPDT)
3 CO (3PDT)
4 CO (4PDT)
10/20
9/20
6/15
250/400
250/400
250/250
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
Rated load AC1
VA
2500
2250
1500
Rated load AC15 (230 V AC)
VA
500
500
350
Single phase motor rating (230 V AC)
kW
0.37
0.37
0.125
Breaking capacity DC1: 30/110/220 V
A
10/0.25/0.12
9/0.25/0.12
6/0.25/0.12
300 (5/5)
300 (5/5)
300 (5/5)
AgNi
AgNi
AgNi
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 110 - 120 - 230
12 - 24 - 48 - 125
12 - 24 - 48 - 125
12 - 24 - 48 - 125
Minimum switching load
mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
V DC
Rated power AC/DC
Operating range
VA (50 Hz)/W
AC
DC
1.5/1
1.5/1
1.5/1
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
AC/DC
0.8 UN / 0.5 UN
0.8 UN / 0.5 UN
0.8 UN / 0.5 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life AC/DC
cycles
20 · 106 / 50 · 106
20 · 106 / 50 · 106
20 · 106 / 50 · 106
Electrical life at rated load AC1
cycles
150 · 103
150 · 103
150 · 103
ms
11/3 (AC) - 11/15 (DC)
11/3 (AC) - 11/15 (DC)
11/3 (AC) - 11/15 (DC)
kV
3.6
3.6
3.6
1000
1000
1000
–40…+70
–40…+70
–40…+70
IP 20
IP 20
IP 20
Technical data
X-2016, www.findernet.com
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
V AC
°C
Approvals relay (according to type)
3
58
SERIES
58 SERIES
Relay interface modules 6 - 7 - 9 - 10 A
Ordering information
Example: 58 series, 35 mm rail (EN 60715) mounting, Push-in terminals interface module, 4 CO, 24 V DC coil, green LED + diode.
5 8 . P
B
C
D
4 . 9 . 0 2 4 . 0
0
5
0
Series
A: Contact material
0 = AgNi Standard
5 = AgNi + Au
Type
3 = Screw terminals
35 mm rail (EN 60715) mount
P = Push-in terminals
35 mm rail (EN 60715) mount
D: Special versions
0 = Standard
C: Options
5 = Standard DC: green LED + diode
(polarity +A1)
6 = Standard AC: green LED + Varistor
B: Contact circuit
0 = CO (nPDT)
No. of poles
2 = 2 pole, 10 A
3 = 3 pole, 10 A
4 = 4 pole, 7 A
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Coil version
8 = AC (50/60 Hz)
9 = DC
Coil voltage
See coil specifications
Type
Coil version A
B
C
D
58.P3/P4/32/33/34
AC
58.P3/P4/32/33/34
DC
0-5
0
6
0
0-5
0
5
0
Ordering information ATEX versions
Example: 58 series, 35 mm rail (EN 60715), screw terminal interface module, 4 CO, 120 V AC, green LED, mechanical indicator, ATEX version
5 8 . 3
Series
Type
3 = Screw terminals
35 mm rail (EN 60715) mount
No. of poles
2 = 2 pole, 10 A
3 = 3 pole, 9 A
4 = 4 pole, 6 A
A
B
C
D
4 . 8 . 1 2 0 . 0
0
4
9
A: Contact material
0 = AgNi Standard
2 = AgCdO
5 = AgNi + Au
B: Contact circuit
0 = CO (nPDT)
D: Special versions
8 = ATEX compliant (Ex nA nC)
without mechanical indicator
9 = ATEX compliant (Ex nA nC)
with mechanical indicator
(2 & 4 CO only)
C: Options
4 = Module 99 LED (AC/DC)
5 = Module 99
LED + Diode (DC)
Coil version
8 = AC (50/60 Hz)
9 = DC
Coil voltage
See coil specifications
X-2016, www.findernet.com
B
A
4
58 SERIES
Relay interface modules 6 - 7 - 9 - 10 A
58
SERIES
Technical data
Insulation
Insulation according to EN 61810-1
insulation rated voltage
V 400 (2-3 pole)
250 (4 pole)
rated impulse withstand voltage kV 3.6 (2-3 pole)
2.5 (4 pole)
pollution degree
2
2
overvoltage category
III
II
Insulation between coil and contacts (1.2/50 μs)
B
kV 3.6
Dielectric strength between open contacts
V AC 1000
Dielectric strength between adjacent contacts
V AC 2000 (58.32,58.33, 58.P3)
1550 (58.34, 58.P4)
Conducted disturbance immunity
Burst (5…50)ns, 5 kHz, on A1 - A2
EN 61000-4-4
level 4 (4 kV)
Surge (1.2/50 μs) on A1 - A2 (differential mode)
EN 61000-4-5
level 4 (4 kV)
Other data
Bounce time: NO/NC
ms 1/3
Vibration resistance (10…55)Hz: NO/NC
g 6/6
Power lost to the environment
without contact current
W 1
with rated current
W 3 (58.32, 58.34, 58.P4)
58.32/33/34 (screw terminals)
Wire strip length
Screw torque
Max. wire size
4 (58.P3, 58.33)
58.P3/P4 (Push-in terminals)
mm 8
8
Nm 0.5
—
stranded cable
solid cable
stranded cable
mm2 1 x 6 / 2 x 2.5
solid cable
1 x 4 / 2 x 2.5
2 x (0.5…1.5)
2 x (0.5…1.5)
AWG 1 x 10 / 2 x 14
1 x 12 / 2 x 14
2 x (21…14)
2 x (21…14)
Other data ATEX versions
Max current @ 70 °C
Single piece mount
> 1 piece mount
Type 58.32
A 10
7
Type 58.33
A 9
6
Type 58.34
A 6
5
Terminal
Wire strip length
Screw torque
Wire size
mm 8
Nm 0.5
solid cable
stranded cable
mm2 1 x 2.5
2 x 1.5
AWG 1 x 12
2 x 16
Markings - ATEX versions - ATEX, II 3G Ex nA nC IIC Gc
MARKING
X-2016, www.findernet.com
GAS
Specific marking of explosion protection
II
Component for surface plant (different from mines)
3
Category 3: normal level of protection
G
Explosive atmosphere due to presence of combustible gas vapour or mist
Ex nA
Non-sparking equipment
Ex nC
Sealed device (type of protection for category 3G)
IIC
Gas group
Gc
Equipment Protection Level
–40 °C ≤ Ta ≤ +70 °C
Ambient temperature
EPT 15 ATEX 0195 U
EPT: laboratory which issues the CE type certificate
15: year of issue of certificate
0195: number of CE type certificate
U: ATEX component
5
58 SERIES
Relay interface modules 7 - 10 A
58
SERIES
Contact specification
F 58 - Electrical life (AC) v contact current
2 & 3 pole relays
B
F 58 - Electrical life (AC) v contact current
4 pole relay
Cycles
Cycles
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
H 58 - Maximum DC1 breaking capacity
• When switching a resistive load (DC1) having voltage and current values
2 & 3 pole current limit
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC breaking current (A)
4 pole current limit
1
2
3
4
contacts in series
DC voltage (V)
Coil specifications
DC coil data
Nominal
voltage
AC coil data
Coil code
Operating range
Resistance
Rated coil
absorption
Nominal
voltage
Coil code
Operating range
Resistance
Rated coil
absorption
UN
Umin
Umax
R
I at UN
UN
Umin
Umax
R
I at UN (50 Hz)
V
V
V
Ω
mA
V
V
V
Ω
mA
12
9.012
9.6
13.2
140
86
12
8.012
9.6
13.2
50
97
24
9.024
19.2
26.4
600
40
24
8.024
19.2
26.4
190
53
2400
20
48
8.048
38.4
770
25
110
8.110
88
48
9.048
125
9.125
38.4
52.8
100
138
17300
R 58 - DC coil operating range v ambient temperature
7.2
52.8
121
4000
12.5
120
8.120
96
132
4700
12
230
8.230
184
253
17000
6
R 58 - AC coil operating range v ambient temperature
1
1
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
6
2
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
X-2016, www.findernet.com
2
58 SERIES
Relay interface modules 7 - 10 A
Combinations
ertain relay/socket
C
combinations
58
SERIES
Code
Type of socket
Type of relay
Module
Retaining clip
58.P3
94.P3
55.33
99.02
094.91.3
58.P4
94.P4
55.34
99.02
094.91.3
58.32
94.02
55.32
99.02
094.91.3
58.33
94.03
55.33
99.02
094.91.3
58.34
94.04
55.34
99.02
094.91.3
B
Outline drawing
58.33
Screw terminals
58.P3
Push-in terminal
58.P4
Push-in terminal
58.34
Screw terminals
X-2016, www.findernet.com
58.32
Screw terminals
7
58 SERIES
Relay interface modules 7 - 10 A
58
SERIES
Accessories
094.52.1
10 A - 250 V
2-way jumper link for type 58.P3 and 58.P4
Rated values
097.52
10 A - 250 V
Marker tag holder for type 58.P3, 58.P4, 58.32, 58.33 and 58.34
097.00
6-way jumper link for type 58.32, 58.33, 58.34
094.06 (blue)
094.52.1
097.52
O
P A
PEAN
N
T E
T
EUR
EUR
097.00
O
PEAN
Rated values
094.06.0 (black)
10 A - 250 V
O
P A
6-way jumper link for type 58.P3 and 58.P4
PEAN
N
T E
T
EUR
EUR
094.06
O
PEAN
094.56 (blue)
Rated values
10 A - 250 V
094.56
Sheet of marker tags, plastic, 48 tags, 6 x 12 mm
060.48
060.48
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
5 8 . P
4 . 9 . 0 2 4 . 0
0
5
0
S P
A
A Standard packaging
B Blister packaging
SP Plastic retaining clip
SM Metallic retaining clip
(58.32/33/34 - x0xx only)
8
X-2016, www.findernet.com
B
2-way jumper link for type 58.P3 and 58.P4
Rated values