60 Series - General purpose relays 6 - 10 A
Features
60.12
60.13
Plug-in mount
10 A General purpose relay
•2
& 3 pole changeover contacts
Cadmium Free contacts
(preferred version)
• AC coils & DC coils
• UL Listed (certain relay/socket
combinations)
• Contact material options
• Lockable test button with mechanical flag
indicator (preferred version)
• 90 series sockets, coil EMC suppression
and timer accessories
•
•
•
2 pole - 10 A power contacts
8 pin plug-in
124
225
143
246
111
218
A12
•
•
3 pole - 10 A power contacts
11 pin plug-in
225 216
247
124
328
143
111
349
3111
60
A27
A12
36.4
A210
32.5
36.4
12.6
12.6
54.2
54.2
32.5
Contact specification
Contact configuration
2 CO (DPDT)
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage V AC
3 CO (3PDT)
10/20
10/20
250/400
250/400
Rated load AC1
VA
2,500
2,500
Rated load AC15 (230 V AC)
VA
500
500
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.37
0.37
10/0.4/0.15
10/0.4/0.15
500 (10/5)
500 (10/5)
AgNi
AgNi
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
V DC
Rated power AC/DC
VA (50 Hz)/W
Operating range
AC
DC
6 - 12 - 24 - 48 - 60 - 110 -125 - 220
2.2/1.3
2.2/1.3
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
AC/DC
0.8 UN/0.5 UN
0.8 UN/0.5 UN
Must drop-out voltage
AC/DC
0.2 UN/0.1 UN
0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC
cycles
20 · 106/50 · 106
20 · 106/50 · 106
Electrical life at rated load AC1
cycles
200 · 103
200 · 103
ms
9/9
9/9
Insulation between coil and contacts (1.2/50 µs) kV
3.6
3.6
1,000
1,000
–40…+70
–40…+70
RT I
RT I
Operate/release time
Dielectric strength between open contacts
Ambient temperature range
Environmental protection
V AC
°C
Approvals (according to type)
83
60 Series - General purpose relays 6 - 10 A
Features
60.12 - 0200
60.13 - 0200
Plug-in mount - 6 A
Bifurcated contacts for low level switching
•2
& 3 pole changeover contacts
Free contacts
(Gold plated Silver Nickel)
• AC coils & DC coils
• Lockable test button with mechanical flag
indicator (preferred version)
• 90 series sockets, coil EMC suppression
and timer accessories
• Cadmium
•
•
2 pole - 6 A bifurcated contacts
8 pin plug-in
124
225
143
246
111
60
•
•
3 pole - 6 A bifurcated contacts
11 pin plug-in
225 216
247
124
328
143
111
349
3111
218
A12
A27
A12
36.4
A210
32.5
36.4
12.6
12.6
54.2
54.2
32.5
Contact specification
Contact configuration
2 CO (DPDT)
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage V AC
3 CO (3PDT)
6/10
6/10
250/400
250/400
Rated load AC1
VA
1,500
1,500
Rated load AC15 (230 V AC)
VA
250
250
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.185
0.185
6/0.3/0.12
6/0.3/0.12
50 (5/5)
50 (5/5)
AgNi + Au bifurcated contacts
AgNi + Au bifurcated contacts
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
6 - 12 - 24 - 48 - 60 - 110 -125 - 220
V DC
Rated power AC/DC
VA (50 Hz)/W
Operating range
AC
2.2/1.3
2.2/1.3
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
AC/DC
0.8 UN/0.5 UN
0.8 UN/0.5 UN
Must drop-out voltage
AC/DC
0.2 UN/0.1 UN
0.2 UN/0.1 UN
DC
Technical data
Mechanical life AC/DC
cycles
20 · 106/50 · 106
20 · 106/50 · 106
Electrical life at rated load AC1
cycles
250 · 103
250 · 103
ms
9/9
9/9
Insulation between coil and contacts (1.2/50 µs) kV
3.6
3.6
1,000
1,000
–40…+70
–40…+70
RT I
RT I
Operate/release time
Dielectric strength between open contacts
Ambient temperature range
Environmental protection
Approvals (according to type)
84
V AC
°C
60 Series - General purpose relays 6 - 10 A
Features
60.62
60.63
Flange mount
10 A General purpose relay
• Flange
mount (Faston 187,
4.8x0.8 mm termination)
• 2 & 3 pole changeover contacts
• AC coils & DC coils
• Cadmium Free contacts
(preferred version)
• Contacts material options
•
•
2 pole - 10 A power contacts
Flange mount/Faston 187
•
•
3 pole - 10 A power contacts
Flange mount/Faston 187
1 42 5 3 6
1 4 3 6
7
A
A1
9
7
B
A2
A
A1
32.2
8
9
32.2
36.5
60
B
A2
36.5
3.6
7
43
52
7
43
52
3.6
7.1 18 7.1
11
9 5.9 6.2 4.4
7.1 18 7.1
11
9 5.9 6.2 4.4
Contact specification
Contact configuration
2 CO (DPDT)
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage V AC
3 CO (3PDT)
10/20
10/20
250/400
250/400
Rated load AC1
VA
2,500
2,500
Rated load AC15 (230 V AC)
VA
500
500
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.37
0.37
10/0.4/0.15
10/0.4/0.15
500 (10/5)
500 (10/5)
AgNi
AgNi
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
6 - 12 - 24 - 48 - 60 - 110 -125 - 220
V DC
Rated power AC/DC
VA (50 Hz)/W
Operating range
AC
2.2/1.3
2.2/1.3
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
Holding voltage
AC/DC
0.8 UN/0.5 UN
0.8 UN/0.5 UN
Must drop-out voltage
AC/DC
0.2 UN/0.1 UN
0.2 UN/0.1 UN
DC
Technical data
Mechanical life AC/DC
cycles
20 · 106/50 · 106
20 · 106/50 · 106
Electrical life at rated load AC1
cycles
200 · 103
200 · 103
ms
9/9
9/9
Insulation between coil and contacts (1.2/50 µs) kV
3.6
3.6
Operate/release time
Dielectric strength between open contacts
Ambient temperature range
Environmental protection
V AC
°C
1,000
1,000
–40…+70
–40…+70
RT I
RT I
Approvals (according to type)
85
60 Series - General purpose relays 6 - 10 A
Ordering information
Example: 60 series plug-in relay, 3 CO (3PDT), 12 V DC coil, test button and mechanical indicator.
6 0 . 1
A
B
C
D
3 . 9 . 0 1 2 . 0
0
4
0
A: Contact material
0 = Standard
2 = AgCdO
5 = AgNi + Au (5 µm)
Series
Type
1 = 8/11 pin plug-in
6 = Faston 187 (4.8x0.8 mm)
with flange mount
B: Contact circuit
0 = CO (nPDT)
2 = Bifurcated contacts
60.12/13 - 6 A only
No. of poles
2 = 2 pole
3 = 3 pole
60
Coil version
4 = Current sensing
8 = AC (50/60 Hz)
9 = DC
Coil voltage
see coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best avaliability are shown in bold.
Type
Coil version
60.12/13 AC
AC
AC
AC
DC
DC
DC
DC
current sensing
60.62/63 AC-DC
A
0-2
0-2
5
5
0-2
0-2
5
5
0
0-2-5
B
0
0
000
0
000
0
2
2
2
2
C
0-2-3-4-5
54
0-2-3-4-5
54
0-2-4-6-7
74
0-2-4-6-7
74
4
0
D: Special versions
0 = Standard
C: Options
0 = None
2 = Mechanical indicator
3 = LED (AC)
4 = Lockable test button +
mechanical indicator
5 = Lockable test button + LED (AC)
54 = Lockable test button + LED (AC) +
mechanical indicator
6 = LED + diode (DC, polarity positive
to pin 2)
7 = Lockable test button + LED + diode
(DC, polarity positive to pin 2)
74 = Lockable test button + LED + diode
(DC, polarity positive to pin 2) +
mechanical indicator
D
0
/
0
/
0
/
0
/
0
0
Descriptions: Options and Special versions
2
A1
C: Option 3, 5, 54
LED (AC)
7/10
A2
2
A1
7/10
A2
C: Option 6, 7, 74
LED + diode (DC, polarity
positive to pin 2)
Lockable test button and mechanical flag indicator (0040)
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly above the test button) remains intact. In this case, when the
test button is pushed, the contacts operate. When the test button is released the contacts return to their
former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition to
the above function), when the test button is pushed and rotated, the contacts are latched in the
operating state, and remain so until the test button is rotated back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
86
60 Series - General purpose relays 6 - 10 A
Technical data
Insulation
Insulation according to EN 61810-1 ed. 2
insulation rated voltage
V 250
rated impulse withstand voltage
400
kV 4 (2 pole)
pollution degree
overvoltage category
Insulation between coil and contacts (1.2/50 µs)
3.6 (3 pole)
4 (2 pole)
3
2
III
III
3.6 (3 pole)
kV 3.6
Dielectric strength between open contacts
V AC 1,000
Dielectric strength between adjacent contacts
V AC 2,000
Conducted disturbance immunity
Burst (5...50)ns, 5 kHz, on A1 - A2
EN 61000-4-4
level 4 (4 kV)
Surge (1.2/50 µs) on A1 - A2 (differential mode)
EN 61000-4-5
level 4 (4 kV)
Other data
Bounce time: NO/NC
ms 2/4
Vibration resistance (5…55)Hz, max. ± 1 mm: NO/NC
g/g 22/22
Shock resistance
g 20
2 pole
Power lost to the environment
3 pole
without contact current
W 1.3
1.3
with rated current
W 2.7
3.4
60
Contact specification
F 60 - Electrical life (AC) v contact current
H 60 - Maximum DC1 breaking capacity
7
20
DC breaking current (A)
Cycles
10
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
6
10
5
10
10
6
4
2
1
3 contacts in series
2
1
0.2
0.1
0
4
8
12
20
16
(A)
60
100
140
180
220
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100·103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
AC coil data
DC coil data
Nominal
voltage
UN
V
6
12
24
48
60
110
125
220
Coil
code
9.006
9.012
9.024
9.048
9.060
9.110
9.125
9.220
Operating range
Umin
V
4.8
9.6
19.2
38.4
48
88
100
176
Umax
V
6.6
13.2
26.4
52.8
66
121
137.5
242
Resistance Rated coil
consumption
R
I at UN
Ω
mA
28
214
110
109
445
53.9
1,770
27.1
2,760
21.7
9,420
11.7
12,000
10.4
37,300
5.8
Nominal
voltage
UN
V
6
12
24
48
60
110
120
230
240
400
Coil
code
8.006
8.012
8.024
8.048
8.060
8.110
8.120
8.230
8.240
8.400
Operating range
Umin
V
4.8
9.6
19.2
38.4
48
88
96
184
192
320
Umax
V
6.6
13.2
26.4
52.8
66
121
132
253
264
440
Resistance Rated coil
consumption
R
I at UN (50Hz)
Ω
mA
4.6
367
19
183
74
90
290
47
450
37
1,600
20
1,940
18.6
7,250
10.5
8,500
9.2
19,800
6
87
60 Series - General purpose relays 6 - 10 A
Coil specifications
R 60 - DC coil operating range v ambient temperature
R 60 - AC coil operating range v ambient temperature
U 2.0
UN
U 2.0
UN
1.5
1.5
1
1.0
1
1.0
2
0.5
-20
-10
0
10
20
30
40
50
2
60
70
80
(°C)
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
0.5
-20
-10
0
10
20
30
40
50
60
70
80
(°C)
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
60
Current sensing version
Current sensing DC coil data
L
C
L1
L2
S1
K1
N
Typical application with current sensing relays.
An open circuit filiment of lamp L1 is detected by the current sensing
relay coil (K1) which causes the back-up safety lamp L2 to be energised,
and indication of failure at the control panel via lamp S1.
Example: navigation light.
L1 = Light
L2 = Safety light
S1 = Control light
K1 = Relay
Coil code
4202
4182
4162
4142
4122
4102
4092
4062
4032
4012
Imin (A)
1.7
1.5
1.4
1.2
1.0
0.85
0.8
0.5
0.25
0.085
IN (A)
2.0
1.8
1.6
1.4
1.2
1.0
0.9
0.6
0.3
0.1
Imax (A)
2.4
2.2
1.9
1.7
1.4
1.2
1.1
0.7
0.4
0.15
R (Ω)
0.15
0.19
0.24
0.31
0.42
0.61
0.75
1.70
6.70
61
IN (A)
2.5
1.8
1.6
1.2
1.0
0.5
0.4
0.3
0.2
0.1
Imax (A)
3.0
2.2
1.9
1.4
1.2
0.6
0.5
0.4
0.25
0.15
R (Ω)
0.05
0.10
0.12
0.22
0.32
1.28
2.00
3.57
8.0
32.1
Current sensing AC coil data
Coil code
4251
4181
4161
4121
4101
4051
4041
4031
4021
4011
Imin (A)
2.1
1.5
1.4
1.0
0.85
0.42
0.34
0.25
0.17
0.085
Other types of current sensing relays are available on request.
Accessories
Sheet of marker tags for relay types 60.12 and 60.13, plastic, 72 tags, 6x12 mm
060.72
88
060.72
60 Series
General Purpose Relays 10 A
ORDERING INFORMATION
Example: a 60 series P.C.B.relay, 3 CO (3PDT) with coil rated 12 V DC.
6 0
Series
4
3
No. of poles
2 = 2 CO (DPDT)
3 = 3 CO (3PDT)
0 1 2
9
Coil version
3 = DC diode in parallel to
coil (positive to pin 2)
8 = AC (50/60 Hz)
9 = DC
Type
4 = P.C.B.
0
0
Contact material
and contact circuit
00 = Standard
20 = AgCdO
50 = AgNi + 5µm Au
0
0
Options
00 = Standard
Coil voltage
006 =
6V
012 = 12 V
024 = 24 V
048 = 48 V
060 = 60 V
110 = 110 V
120 = 120 V AC only
230 = 230 V AC only
240 = 240 V AC only
OPTIONS
2
7
10
Coil version = 3
62
2
7
10
Option = 0030
7
10
2
Option = 0060 - 0070
7
10
2
Option = 0080 - 0090
60 Series
General Purpose Relays 10 A
TECHNICAL DATA
DIELECTRIC STRENGTH
between coil and contacts 2,000 V
tested at leakage current
between open contacts
≤ 10 mA for 1 min at 50 Hz
between adjacent contacts 1,000 V
2,000 V
SURGE TEST (1.2/50 µs)
2,500 V
between frame and live parts 2,000 V
BETWEEN COIL AND CONTACTS
ISOLATION RESISTANCE
≥ 20 · 103 MΩ
ISOLATION GROUP
C 250
MAXIMUM SWITCHING
FREQUENCY
- at rated load
60.43
GOST
BEAB
RINA
- without load
(–40 ... +70)°C
MECHANICAL LIFE
20 · 106 cycles version AC
50 · 106 cycles version DC
C
OPERATE AND RELEASE TIME
60.42
1
9
36
7.1
10.8 9 6 5.9 4.3
60.43
4
3
1
6
10
4
2
11
5 3
6
8
7
9
7
9
10
60.42
11
60.43
copper side view
3
4
6
6
7
9
9
10
11
10.8
1.5
4.3
5.9
1
60.42
58
7.1
7.1
36
1.5
36
32.2
32.2
18
7.1
≤ 15 ms (including contact bounce)
TYPE OF RELAY
43
7.1
≤ 15 ms (including contact bounce)
- drop-out time (UN to 0)
DIELECTRIC TEST
6
7.1
- pick-up time (0 to UN)
TYPE OF DUTY
32.2
18
IP 40
OF ENCLOSURES
P.C.B. RELAYS 10 A
TYPE 60.42 2 CO (DPDT)
TYPE 60.43 3 CO (3PDT)
- Tin plated copper pins (1.2 x 0.5 mm)
- Standard contact material: AgNi
- Options: see coding table page 62
- Ordering information: see page 62
7.1
1,800 cycles/h
AMBIENT TEMPERATURE
PROTECTION CATEGORY
32.2
36,000 cycles/h
9
9
7.1
4.3
5.9
1
2
3
4
5
6
6
7
8
9
9
10
11
60.43
10.8
continuous
2
all-or-nothing
60 Series
General Purpose Relays 10 A
CONTACT SPECIFICATIONS
RATED CURRENT
10 A
MAXIMUM PEAK CURRENT
20 A
NOMINAL RATE IN AC1
2,500 VA
NOMINAL RATE IN AC15
500 VA
RATED VOLTAGE
250 V AC
MAXIMUM SWITCHING VOLTAGE
400 V AC
BREAKING CAPACITY IN DC1
see diagram H 60
SINGLE PHASE HP MOTOR RATING
0.37 kW/0.6 HP
CONTACT RESISTANCE: - initial
≤ 50 mΩ
MINIMUM SWITCHING LOAD
500 mW (10 V/5 mA)
STANDARD CONTACT MATERIAL
AgNi
F 60
H 60
7
10
20
MAX SWITCHING CURRENT (A)
CYCLES
A
106
105
0.5
1
1.5
2
2.5
3
C
6
4
2
1
0.6
0.4
0.2
0.1
0
B
10
20
60
100
140
180
220
VOLTAGE DC (V)
LOAD (kVA)
Contact life vs AC1 load at 1800 cycles/h.
Breaking capacity for DC1 load at 1800 cycles/h.
A = load applied to 1 contact
B = load applied to 2 contacts in series
C = load applied to 3 contacts in series
K 60
k REDUCTION FACTOR
1
0.8
k
0.6
0.4
1
0.8
0.6
0.4
0.2
COS ϕ
Load reduction factor vs cos ϕ.
59
60 Series
General Purpose Relays 10 A
COIL SPECIFICATIONS
VERSIONS:
AC - alternating current 50/60 Hz
DC - direct current
AM - current sensing
DI - DC coil with a diode in parallel
AC
RATED POWER
2.2 VA
1.3 W
OPERATING RANGE
(0.8 to 1.1) UN
(0.8 to 1.1) UN
HOLDING VOLTAGE
≤ 0.8 UN
≤ 0.5 UN
MUST DROP-OUT VOLTAGE
≥ 0.2 UN
≥ 0.1 UN
NOMINAL MAGNETOMOTIVE FORCE
THERMAL INSULATION CLASS OF WIRE
THERMAL RESISTANCE
CONDUCTED DISTURBANCE IMMUNITY
180 A
250 A
F (+155°C)
F (+155°C)
43°C/W
43°C/W
BURST (acc. to EN 61000 - 4 - 4)
level 4 (4 kV)
SURGE (acc. to EN 61000 - 4 - 5)
level 4 (4 kV)
AC VERSION DATA
R values relate to +20°C. Tolerance of R and I values: ± 10%.
Rated
voltage
UN
V
6
12
24
48
60
110
120
230
240
60
DC
Operating range
Umin
V
4.8
9.6
19.2
38.4
48
88
96
184
192
U
max
V
6.6
13.2
26.4
52.8
66
121
132
253
264
Resistance
R
Ω
4.6
19
80
320
500
1,800
1,940
7,250
8,500
Nominal coil
absorption
UN 50 Hz I
mA
367
183
91.7
45.8
36.7
20
18.6
9.6
9.2
DC VERSION DATA
R values relate to +20°C. Tolerance of R and I values: ± 10%.
Operating range
Rated
voltage
UN
Umin
V
6
12
24
48
60
110
V
4.8
9.6
19.2
38.4
48
88
U
max
V
6.6
13.2
26.4
52.8
66
121
Resistance
R
Nominal coil
absorption
I
Ω
28
110
445
1,770
2,760
9,420
mA
214
109
53.9
27.1
21.7
11.7
60 Series
General Purpose Relays 10 A
COIL SPECIFICATIONS
R 60
Umin
70
1
TEMPERATURE RISE “∆t” (°C)
UN
S 60/1
0.9
0.8
0.7
0.6
60
1.1 UN
50
UN
40
30
0.8 UN
20
10
0.5
0
- 40
-20
0
20
40
60
10
80
20
30
50
60
HEATING TIME (min)
AMBIENT TEMPERATURE (°C)
Temperature rise "∆t " vs applied voltage. DC coils.
DC coil min pick-up voltage vs ambient temperature.
Umin = pick-up voltage
UN = rated voltage
S 60/3
S 60/2
70
70
60
50
1.1 UN
40
UN
30
0.8 UN
20
10
TEMPERATURE RISE “∆t” (°C)
TEMPERATURE RISE “∆t” (°C)
40
60
50
1.1 UN
40
UN
30
0.8 UN
20
10
0
10
20
30
40
50
60
HEATING TIME (min)
Temperature rise "∆t " vs applied voltage. AC 50 Hz coils.
0
10
20
30
40
50
60
HEATING TIME (min)
Temperature rise "∆t " vs applied voltage. AC 60 Hz coils.
61