UN (12- 24- 48-60- 120 -230)V AC (50/60 Hz) / DC
Umin- Umax (0.8-1.1)UN
P 2 VA / 2.2 W
ENGLISH
2
1
22.32.0.xxx.xxx0
22.32 MODULAR CONTACTORS 25 A
Contact gap ≥ 3 mm for NO contacts only; NC contacts ≥ 1.5 mm.
Compliant with EN 61095: 2009.
AC/DC silent coil (with varistor protection).
1 CONNECTION DIAGRAM
2 OUTLINE DRAWINGS
22.32...x3x0
22.32...x5x0
3 FRONT VIEW
22.32...x4x0
A = Selector (22.32.0.xxx.xx40)
The three-position manual selector has the following functions:
25 A 440 V AC (EN 61095)
22.32
AC1/ AC-7a (250 V)
6250 VA
AC3/ AC-7b
10 A
AC5a (250 V)
15 A
AC15 (230 V AC)
1800 VA
M
(230
V AC)
1 kW
DC1 (30/110/ 220)V (25 /5 /1)A
AC-7c (10 A - 22.32...4xx0)
800 W (2000 W - 22.32...4xx0)
300 W (800 W - 22.32...4xx0)
CFL–LED
100 W (200 W - 22.32...4xx0)
4
22.32 + (022.33/022.35)
AUTO position
The state of contacts, mechanical indicator and LED follow the coil
supply voltage.
OFF position
Even if terminals A1 - A2 are supplied with rated voltage, the coil
is not energized, and so the contacts remain in the non-operated
state, the mechanical indicator is not visible and the LED is not
illuminated.
(–20...+50)°C
B = LED
IP20
• Open Type Device - Pollution degree 2 Installation Environment
• Maximum Surrounding Air Temperature 50°C
• Minimum distance among modular contactors 9 mm
• Field Wiring Terminals:
Use 60/75°C copper conductor only and wire ranges
No. 10-12-18-24 AWG, Solid only
Terminal tightening torque 7.0 lb.in. (0.8 Nm)
• Suitable for use on a circuit capable of delivering not more than
5000 ARMS Symmetrical, 240 V ac, when protected by Listed
Cartridge Fuses, rated K5 Class (No Current Limiting, Non-Time
Delay, max 600 Vac, 30 A, 50 kA A.I.C.) or RK5 Class (Current
Limiting, Time Delay, max 600 Vac, 15 A, 50 kA A.I.C.) or equivalent
• For use in a circuit protected by Type1 or Type2 Surge Protective
Devices with “Max Voltage Protection” rating of 3.7 kVpk and
“Minimum Nominal Discharge Current” of 5 kA (at 6 kV)
Utility Model - IB2232001 - 09/17 - FINDER S.p.A. - 10040 ALMESE (TO) - ITALY
ON position
The contacts are latched in the operated state (NO contacts closed and NC contacts - open), the mechanical indicator is visible
in its window, the LED is not illuminated.
3
022.33
022.35
C = Mechanical indicator
4 ACCESSORIES
- Auxiliary contact module available, “Quick assembly” with the main
contactor 022.33/022.35
- It is not possible to assembly the auxiliary module on 22.32.0.xxx.x4x0
(2 NC versions)
A
C
B
022.33
2 NO (DPST- NO)
022.35
1 NO (SPST- NO) + 1 NC (SPST- NC)
Ith
AC15
(230 V AC)
6A
700 VA
OTHER DATA
It is suggested an air gap of 9 mm between adjacent relays for installations
and working conditions close to the limit (that is, ambient temperature
> 40°C, coil operated for a prolonged period of time, all contacts loaded
with current > 20 A).