22.34.0.XXX.xxx0
UN (12 - 24 - 48 - 60 - 120 - 230)V AC (50/60 Hz) / DC
Umin - Umax: (0.8...1.1)UN
P 2 VA (50 Hz) / 2.2 W
1
ENGLISH
2
22.34 MODULAR CONTACTOR 25 A
Contact gap ≥ 3 mm for NO contacts only. NC contacts ≥ 1.5 mm.
Compliant with EN 61095: 2009.
AC/DC silent coil (with varistor protection).
1 CONNECTION DIAGRAM
22.34...x3x0
22.34...x7x0
2 OUTLINE DRAWINGS
22.34...x6x0
25 A 440 V AC (EN 61095)
22.34
AC1 / AC-7a (250 V AC)
6250 VA
AC3 / AC-7b
10 A
AC15 (230 V AC)
1800 VA
M
3
3 FRONT VIEW
A = Selector (22.34.0.xxx.xx40)
The three-position manual selector has the following functions:
3
~ (400 - 440 V AC)
4 kW
10 A (22.34...4xx0)
AC - 7c
(230 V AC)
ON position
The contacts are latched in the operated state (NO contacts - closed
and NC contacts - open), the mechanical indicator is visible in its
window, the LED is not illuminated.
800 W
2000 W (22.34...4xx0)
AUTO position
The state of contacts, mechanical indicator and LED follow the coil
supply voltage.
A
(230 V AC) 300 W
800 W (22.34...4xx0)
CFL - LED
100 W
200 W (22.34...4xx0)
B
OFF position
Even if terminals A1 - A2 are supplied with rated voltage, the coil is
not energized, and so the contacts remain in the non-operated state,
the mechanical indicator is not visible and the LED is not illuminated.
C
(–20…+50)°C
B = LED
IP20
C = Mechanical indicator
4
• Open Type Device - Pollution degree 2 Installation Environment
• Maximum Surrounding Air Temperature 50°C
• Minimum distance among modular contactors 9 mm
• Field Wiring Terminals:
Use 60/75°C copper conductor only and wire ranges
No. 10-12-18-24 AWG, Solid only
Terminal tightening torque 7.0 lb.in. (0.8 Nm)
• Suitable for use on a circuit capable of delivering not more than
5000 ARMS Symmetrical, 240 V AC, when protected by Listed
Cartridge Fuses, rated K5 Class (No Current Limiting, Non-Time
Delay, max 600 V AC, 30 A, 50 kA A.I.C.) or RK5 Class (Current
Limiting, Time Delay, max 600 Vac, 15 A, 50 kA A.I.C.) or equivalent.
• For use in a circuit protected by Type1 or Type2 Surge Protective
Devices with “Max Voltage Protection” rating of 3.7 kVpk and
“Minimum Nominal Discharge Current” of 5 kA (at 6 kV).
Utility Model - IB2234001 - 09/17 - FINDER S.p.A. - 10040 ALMESE (TO) - ITALY
22.34 + (022.33 / 022.35)
4 ACCESSORIES
Auxiliary contact module available, “Quick assembly” with the main
contactor 022.33/022.35.
022.33
022.35
022.33
2 NO (DPST-NO)
022.35
1 NO (SPST-NO) + 1NC (SPST-NC)
AC1
AC15(230 V AC)
6A
700 VA
OTHER DATA
It is suggested an air gap of 9 mm between adjacent relays for
installations and working conditions close to the limit (that is,
ambient temperature > 40 °C, coil operated for a prolonged
period of time, all contacts loaded with current > 20 A).