MasterINTERFACE 39 Series - Relay interface modules
Common features
•
•
•
•
•
•
Space saving 6.2 mm wide
Connections for 16-way jumper link
Integral coil indication and protection circuit
Secure retention and easy ejection by plastic
clip
Dual screw head (blade+cross) terminals
35 mm rail mounting (EN 60715)
MasterBASIC
•
For general use in any type of system
•
EMR: 6 to 24 V AC/DC and 230 V AC supply
SSR: 6 to 24 V DC and 230 V AC supply
•
EMR
Electromechanical Relays
•
•
SSR
Solid State Relays
1 CO 6 A 250 V AC
High switching capability
•
•
39.11
1 solid state output (options 0.1 A 48 V DC,
2 A 24 V DC, 2 A 240 V AC)
Silent, high speed switching, long electrical life
39.10
Page 5
Page 4
MasterPLUS
•
Accepts the output fuse module, for the easy
and space efficient protection of output circuits
•
EMR: 6 to 125 V AC/DC, 125 and 220 V DC,
230 V AC supply
SSR: 24 - 125 V AC/DC, 6 to 220 V DC and
230 V AC supply
•
•
39.31 - 39.31.3
39.30 - 39.30.3
Special 125 and 230 V AC leakage current
suppression types (39.31.3 EMR and 39.30.3 SSR)
Page 6
MasterINPUT
•
Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices
•
EMR: 6 to 24 V and 125 V AC/DC, 230 V AC
supply
SSR: 6 - 12 V DC, 24 - 125 V AC/DC, 230 V AC
supply
•
39.41
Page 7
39.40
Page 8
MasterOUTPUT
•
Jumper link option for the quick and easy
distribution of supply voltage to output side
and its connection to electromagnetic valves
and similar output devices
•
EMR:6 to 24 V and 125 V AC/DC, 230 V AC
supply
SSR: 6 to 24 V DC, 125 V AC/DC, 230 V AC
supply
•
39.21
Page 9
39.20
Page 10
MasterTIMER
•
Timer adjustment via top mounted rotary
knob accessible after assembly
Control signal terminal
DIP-switch for selection of 4 time scales and 8
functions
Output with fuse module option
•
EMR and SSR: 12 to 24 V AC/DC supply
•
•
•
39.81
Page 11
39.80
Page 12
Page 13
Typical Applications
MasterBASIC
39.11 - 39.10
MasterPLUS
39.31 - 39.30 - 39.31.3 - 39.30.3
• For general interface use in any type of
system and application.
• Can be used for input interface applications
between auxiliary contacts, sensors etc. and
controllers, PLCs’ or motors. Or for output
interface between PLC’s controllers and
relays, solenoids etc.
• This special version provides extra protection
for the output circuit thanks to the replaceable
fuse module.
• For general interface use in any type of
system and application.
• Can be used for input interface applications
between auxiliary contacts, sensors etc. and
controllers, PLCs’ or motors. Or for output
interface between PLC’s controllers and
relays, solenoids etc.
Output devices
Output devices
Fuse module
093.63
PLC - Output
PLC - Output
PLC - Input
PLC - Input
Fuse module
093.63
Input devices
2
Input devices
Typical Applications
MasterINPUT
39.41 - 39.40
MasterOUTPUT
39.21 - 39.20
MasterTIMER
39.81 - 39.80
• These models allow the full termination of
• These models allow the full termination of
• Slim and Multifunction Timed Interface
input device to the interface without the need
output device to the interface without the
modules.
for additional terminals - saving component
need for additional terminals - saving
cost, time and panel space.
component cost, time and panel space.
• Quick and easy distribution of supply voltage • Quick and easy distribution of supply voltage
through the jumper link on the Bus-Bar (BB)
through the jumper link on the Bus-Bar (BB)
connection.
connection.
• Ideal for interface applications between the
• Ideal for interface applications between the
auxiliary contacts, sensors, limit switches and
PLC’s or Controllers and output devices such
Controllers or PLC’s.
as electomagnetic valves or motors etc..
Output devices
Output devices
Fuse module
093.63
PLC - Output
PLC - Input
Input devices
PLC - Output
PLC - Input
Input devices
3
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterBASIC - EMR
39.11
Features
1 Pole interface module, 6.2 mm wide, ideal for
PLC and electronic systems
•
Common connection possible with optional
jumper links (terminals A1, A2 and 11)
•
•
•
6 A electromechanical relay
6 to 24 V AC/DC and 230 V AC supply
35 mm rail (EN 60715) mounting
39.11
Screw terminal
For outline drawing see page 20
Contact specification
1 CO (SPDT)
Contact configuration
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage
Rated load AC1
V AC
VA
Rated load AC15 (230 V AC)
Single phase motor rating (230 V AC)
250/400
1,500
VA
300
kW
0.185
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
6/10
AgNi
Standard contact material
Supply specification
Nominal voltage (UN)
V AC/DC
V AC (50/60 Hz)
Rated power
VA (50 Hz)/W
6 - 12 - 24
220...240
See page 16
Operating range
(0.8...1.1)UN
Holding voltage
0.6 UN
0.1 UN
Must drop-out voltage
(0.8...1.2)UN
Technical data
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
ms
Insulation between coil and contacts (1.2/50 μs) kV
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
4
V AC
°C
5/6
6 (8 mm)
1,000
–40…+70
IP 20
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterBASIC - SSR
39.10
Features
1 Pole interface module, 6.2 mm wide, ideal for
PLC and electronic systems
•
Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
•
•
•
0.1 or 2 A solid state relay
6 to 24 V DC and 230 V AC supply
35 mm rail (EN 60715) mounting
39.10
Screw terminal
For outline drawing see page 20
39.10.x.xxx.9024 39.10.x.xxx.7048 39.10.x.xxx.8240
Output specification (SSR)
1 NO (SPST-NO)
Contact configuration
A
2/20 DC
0.1/0.5 DC
2/40 AC
Rated voltage/Maximum blocking voltage
V
24/33 DC
48/60 DC
240/275 AC
Switching voltage range
V (1.5…24) DC
Rated current/Maximum peak current (10 ms)
(1.5…48) DC (12…240) AC
Minimum switching current
mA
1
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
0.12
1
1.6
V
Max. “ON-state” voltage drop
0.05
22
Supply specification
Nominal voltage (UN)
V AC (50/60 Hz)
220...240
V DC
6 - 12 - 24
Rated power
See page 17
VA (50 Hz)/W
(0.8…1.1) UN
Operating range
0.1 UN
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.11
12/12
2,500
–20…+55
IP20
Approvals relay (according to type)
5
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterPLUS - EMR
39.31
39.31.3
Features
1 Pole interface modules, 6.2 mm wide, ideal for
PLC and electronic systems
•
•
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 22
Common connection possible with optional
jumper links (terminals A1, A2 and 11)
•
•
•
6 A electromechanical relay
6 to 125 V AC/DC, 125 and 220 V DC,
230 V AC supply
35 mm rail (EN 60715) mounting
•
•
6 A electromechanical relay
Leakage current suppression version, 125
and 230 V AC supply
39.31 / 39.31.3
Screw terminal
Fuse module
093.63
For outline drawing see page 20
Contact specification
Contact configuration
1 CO (SPDT)
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage
V AC
1 CO (SPDT)
6/10
6/10
250/400
250/400
Rated load AC1
VA
1,500
1,500
Rated load AC15 (230 V AC)
VA
300
300
Single phase motor rating (230 V AC)
kW
0.185
0.185
A
6/0.2/0.12
6/0.2/0.12
mW (V/mA)
500 (12/10)
500 (12/10)
AgNi
AgNi
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Supply specification
Nominal voltage (UN)
V AC/DC
V AC (50/60 Hz)
V DC
6 - 12 - 24 - 60 - 110…125
—
220...240
110…125 - 220…240
110…125 - 220
—
See page 16
See page 16
Operating range
(0.8…1.1) UN
(0.8…1.1) UN
Holding voltage
0.6 UN
0.6 UN
Must drop-out voltage
0.1 UN
0.3 UN
Rated power
VA (50 Hz)/W
Technical data
Mechanical life AC/DC
cycles
10 · 106
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
60 · 103
5/6
5/6
6 (8 mm)
6 (8 mm)
1,000
1,000
–40…+70 (+55 for 220 V DC)
–40…+70
IP20
IP20
Operate/release time
ms
Insulation between coil and contacts (1.2/50 μs) kV
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
6
V AC
°C
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterPLUS - SSR
39.30
39.30.3
Features
1 Pole interface modules, 6.2 mm wide, ideal for
PLC and electronic systems
•
•
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 22
Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
•
•
•
0.1 or 2 A solid state relay
24 - 125 V AC/DC, 6 to 220 V DC and 230
V AC supply
35 mm rail (EN 60715) mounting
•
•
0.1 or 2 A solid state relay
Leakage current suppression version, 125
and 230 V AC supply
39.30 / 39.30.3
Screw terminal
Fuse module
093.63
For outline drawing see page 20
Output specification (SSR)
39.30.x.xxx.9024 39.30.x.xxx.7048 39.30.x.xxx.8240 39.30.3.xxx.9024 39.30.3.xxx.7048 39.30.3.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/Maximum peak current (10 ms)
A
2/20 DC
Rated voltage/Maximum blocking voltage
V
24/33 DC
Switching voltage range
V (1.5…24) DC
2/40 AC
2/20 DC
48/60 DC
240/275 AC
24/33 DC
(1.5…48)DC (12…240) AC (1.5…24) DC
Minimum switching current
mA
1
0.05
Max. “OFF-state” leakage current
mA
0.001
0.12
Max. “ON-state” voltage drop
V
1 NO (SPST-NO)
0.1/0.5 DC
0.1/0.5 DC
2/40 AC
48/60 DC
240/275 AC
(1.5…48)DC (12…240) AC
22
1
0.05
22
0.001
1.5
0.001
0.001
1.5
1
1.6
0.12
1
1.6
Supply specification
Nominal voltage (UN)
V AC/DC
V AC (50/60 Hz)
V DC
Rated power
24 - 110…125
—
220...240
110…125 - 220…240
6 - 12 - 24 - 60 - 110…125 - 220
VA (50 Hz)/W
Operating range
Must drop-out voltage
—
See page 17
See page 17
(0.8…1.1) UN
(0.8…1.1) UN
0.1 UN
0.3 UN
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.11
12/12
0.2/0.6
0.04/0.11
2,500
2,500
–20…+55
–20…+55
IP20
IP20
12/12
Approvals relay (according to type)
7
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterINPUT - EMR
39.41
Features
1 Pole interface module, 6.2 mm wide, ideal
for PLC and electronic systems
•
•
Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices (Bus-bar
connection BB)
Gold plated output contact as standard, for
better compatibility with low energy PLC
inputs
•
•
•
6 A electromechanical relay
6 - 12 - 24 - 125 V AC/DC and 230 V AC
supply
35 mm rail (EN 60715) mounting
39.41
Screw terminal
For outline drawing see page 20
1
Contact specification
1 CO (SPDT)
Contact configuration
A
Rated current/Maximum peak current
V AC
Rated voltage/Maximum switching voltage
VA
Rated load AC1
Rated load AC15 (230 V AC)
Single phase motor rating (230 V AC)
1,500
VA
300
0.185
mW (V/mA)
Minimum switching load
250/400
kW
A
Breaking capacity DC1: 30/110/220 V
6/10
6/0.2/0.12
50 (5/2)
AgNi + Au
Standard contact material
Supply specification
V AC/DC
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power
VA (50 Hz)/W
6 - 12 - 24 - 110…125
220...240
See page 16
Operating range
(0.8…1.1) UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
Insulation between coil and contacts (1.2/50 μs)
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
8
ms
5/6
kV
6 (8 mm)
V AC
°C
1,000
–40…+70
IP20
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterINPUT - SSR
39.40
Features
1 Pole interface modules, 6.2 mm wide, ideal
for PLC and electronic systems
•
Jumper link option for the quick and easy
distribution of supply voltage to proximity
switches and similar input devices (Bus-bar
connection BB)
•
•
•
0.1 or 2 A solid state relay
6 - 12 V DC, 24 - 125 V AC/DC and 230 V AC
supply
35 mm rail (EN 60715) mounting
39.40
Screw terminal
For outline drawing see page 20
Output specification (SSR)
39.40.x.xxx.9024 39.40.x.xxx.7048 39.40.x.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/Maximum peak current (10 ms)
A
2/20 DC
0.1/0.5 DC
2/40 AC
Rated voltage/Maximum blocking voltage
V
24/33 DC
48/60 DC
240/275 AC
Switching voltage range
V
(1.5…24) DC
(1.5…48) DC
(12…240) AC
Minimum switching current
mA
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
0.12
1
1.6
Max. “ON-state” voltage drop
V
Supply specification
Nominal voltage (UN)
V AC/DC
24 - 110...125
V AC (50/60 Hz)
220...240
V DC
Rated power
6 - 12
VA (50 Hz)/W
See page 17
Operating range
(0.8…1.1) UN
Must drop-out voltage
0.1 UN
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.11
12/12
2,500
–20…+55
IP20
Approvals relay (according to type)
9
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterOUTPUT - EMR
39.21
Features
1 Pole interface modules, 6.2 mm wide, ideal for
PLC and electronic systems
•
Jumper link option for the quick and easy
distribution of supply voltage to output side
(Bus-bar connection BB) and its connection to
electromagnetic valves and similar output
devices
•
•
•
6 A electromechanical relay
6 - 12 - 24 - 125 V AC/DC and 230 V AC
supply
35 mm rail (EN 60715) mounting
39.21
Screw terminal
For outline drawing see page 20
1
Contact specification
1 NO (SPST-NO)
Contact configuration
A
Rated current/Maximum peak current
V AC
Rated voltage/Maximum switching voltage
VA
Rated load AC1
Rated load AC15 (230 V AC)
Single phase motor rating (230 V AC)
250/400
1,500
VA
300
kW
0.185
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
6/10
AgNi
Standard contact material
Supply specification
V AC/DC
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power
VA (50 Hz)/W
6 - 12 - 24 - 110…125
220...240
See page 16
Operating range
(0.8…1.1) UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Mechanical life AC/DC
cycles
10 · 106
Electrical life at rated load AC1
cycles
60 · 103
Operate/release time
Insulation between coil and contacts (1.2/50 μs)
Dielectric strength between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
10
ms
5/6
kV
6 (8 mm)
V AC
°C
1,000
–40…+70
IP20
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterOUTPUT - SSR
39.20
Features
1 Pole interface modules, 6.2 mm wide, ideal for
PLC and electronic systems
•
Jumper link option for the quick and easy
distribution of supply voltage to output side
(Bus-bar connection BB) and its connection to
electromagnetic valves and similar output
devices
•
•
•
0.1 or 2 A solid state relay
6 to 24 V DC, 125 V AC/DC and 230 V AC
supply
35 mm rail (EN 60715) mounting
39.20
Screw terminal
For outline drawing see page 20
Output specification (SSR)
39.20.x.xxx.9024 39.20.x.xxx.7048 39.20.x.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/Maximum peak current (10 ms)
A
2/20 DC
0.1/0.5 DC
2/40 AC
Rated voltage/Maximum blocking voltage
V
24/33 DC
48/60 DC
240/275 AC
Switching voltage range
V (1.5…24) DC
(1.5…48) DC (12…240) AC
Minimum switching current
mA
1
0.05
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
0.12
1
1.6
Max. “ON-state” voltage drop
V
22
Supply specification
Nominal voltage (UN)
V AC/DC
110...125
V AC (50/60 Hz)
220...240
V DC
6 - 12 - 24
Rated power
VA (50 Hz)/W
See page 17
Operating range
(0.8…1.1) UN
Must drop-out voltage
0.1 UN
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
ms
V AC
°C
0.2/0.6
0.04/0.11
12/12
2,500
–20…+55
IP20
Approvals relay (according to type)
11
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterTIMER - EMR
39.81
Features
Slim timed interface module, 6.2 mm wide, ideal
for space-saving timing solutions in panels
•
•
•
•
•
Timer adjustment via top mounted rotary
knob, accessible after assembly
Control signal terminal
DIP-switch for selection of 4 time scales and 8
functions
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 22
Common connection possible with optional
jumper links (terminals A1, A2 and 15)
6 A electromechanical relay
12 - 24 V AC/DC supply
• 35 mm rail (EN 60715) mounting
•
•
39.81
Screw terminal
Fuse module
093.63
For outline drawing see page 20
Contact specification
1 CO (SPDT)
Contact configuration
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage
Rated load AC1
VA
Rated load AC15 (230 V AC)
Single phase motor rating (230 V AC)
250/400
1,500
VA
300
kW
0.185
A
6/0.2/0.12
mW (V/mA)
500 (12/10)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
V AC
6/10
AgNi
Standard contact material
Supply specification
Nominal voltage (UN)
V AC/DC
Rated power AC/DC
VA (50 Hz)/W
12 - 24
See page 16
Operating range
(0.8…1.1) UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
(0.1...3)s, (3...60)s, (1...20)min, (0.3...6)h
Specified time range
Repeatability
%
±1
Recovery time
ms
≤ 50
Minimum control impulse
ms
50
%
5
Setting accuracy – full range
Electrical life at rated load AC1
Ambient temperature range
Protection category
Approvals relay (according to type)
12
cycles
°C
60 · 103
–20...+50
IP20
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
39 Series - Relay interface modules 0.1 - 2 - 6 A
MasterTIMER - SSR
39.80
Features
Slim timed interface module, 6.2 mm wide, ideal
for space-saving timing solutions in panels
•
•
•
•
•
Timer adjustment via top mounted rotary
knob; accessible after assembly
Start terminal
DIP-switch for selection of 4 time scales and 8
functions
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 22
Common connection possible with optional
jumper links (terminals A1, A2 and 15+)
0.1 or 2 A solid state relay
12 - 24 V AC/DC supply
• 35 mm rail (EN 60715) mounting
•
•
39.80
Screw terminal
Fuse module
093.63
AI: On-delay
DI: Interval
GI: Pulse (0.5 s) delayed
SW: Symmetrical flasher
(starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
EE: Interval with control signal off
For outline drawing see page 20
Output specification (SSR)
39.80.x.xxx.9024 39.80.x.xxx.7048 39.80.x.xxx.8240
Contact configuration
1 NO (SPST-NO)
Rated current/Maximum peak current (10 ms)
A
2/20 DC
0.1/0.5 DC
2/40 AC
Rated voltage/Maximum blocking voltage
V
24/33 DC
48/60 DC
240/275 AC
Switching voltage range
V
(1.5…24) DC
(1.5…48) DC
(12…240) AC
Minimum switching current
mA
1
0.05
22
Max. “OFF-state” leakage current
mA
0.001
0.001
1.5
0.12
1
1.6
Max. “ON-state” voltage drop
V
Supply specification
Nominal voltage (UN)
Rated power
V AC/DC
VA (50 Hz)/W
12 - 24
See page 17
Operating range
(0.8…1.1) UN
Holding voltage
0.6 UN
Must drop-out voltage
0.1 UN
Technical data
Specified time range
(0.1...3)s, (3...60)s, (1...20)min, (0.3...6)h
Repeatability
%
±1
Recovery time
ms
≤ 50
Minimum control impulse
ms
50
Setting accuracy – full range
%
5
Ambient temperature range
°C
–20...+50
Protection category
IP20
Approvals relay (according to type)
13
39 Series - Relay interface modules - Ordering information
Ordering information
Example: MasterPLUS 39 series screw terminal interface module, electromechanical relay output, 1 CO (SPDT), 24 V AC/DC coil.
3 9 . 3
A
B
C
D
1 . 0 . 0 2 4 . 0
0
6
0
Series
D: Special Version, EMR
0 = Standard
Type
1 = MasterBASIC, screw terminal
3 = MasterPLUS, screw terminal,
fuse-protectable output
4 = MasterINPUT, screw terminal
2 = MasterOUTPUT, screw terminal
8 = MasterTIMER multifunction,
screw terminal,
fuse-protectable output
C: Options, EMR
6 = Standard
B: Contact circuit, EMR
0 = CO (except 39.21, 1 NO)
A: Contact material, EMR
0 = AgNi Standard
4 = AgSnO2
5 = AgNi + Au (5 μm)
No. of poles
1 = 1 CO (only EMR, except 39.21, 1 NO)
0 = 1 NO (only SSR)
ABCD: Output version, SSR
7048 = 0.1 A - 48 V DC
8240 =
2 A - 230 V AC
9024 =
2 A - 24 V DC
Coil version, EMR / Input version, SSR
0 = AC (50/60 Hz)/DC
3 = Leakage current suppression AC (50/60 Hz)
7 = DC sensitive
8 = AC (50/60 Hz)
Coil voltage, EMR / Input voltage, SSR
See page 16
EMR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
39.11
Coil version
0.006 - 0.012
0.024 - 8.230
A
B
C
D
0-4-5
0
6
0
0-4-5
0
6
0
0-4-5
0
6
0
0-4-5
0
6
0
0
0
6
0
0.006 - 0.012
0.024 - 0.060
39.31
0.125 - 8.230
7.125 - 7.220
3.125 - 3.230
0.006 - 0.012
39.41
0.024 - 0.125
8.230
0.006 - 0.012
39.21
0.024 - 0.125
8.230
39.81
0.012 - 0.024
SSR - Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
39.10
39.30
Input version
7.006 - 7.012
7.024 - 8.230
7.006 - 7.012
7.024 - 7.060
7.125 - 7.220
0.024 - 0.125
Output version, ABCD
7048 - 8240 - 9024
7048 - 8240 - 9024
8.230
3.125 - 3.230
0.006 - 0.012
39.40
0.024 - 0.125
7048 - 8240 - 9024
8.230
0.006 - 0.012
39.20
0.024 - 0.125
7048 - 8240 - 9024
8.230
39.80
14
0.012 - 0.024
7048 - 8240 - 9024
39 Series - Relay interface modules - Technical data
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system
Rated insulation voltage
Pollution degree
Insulation between coil and contact set
Type of Insulation
Overvoltage category
Rated impulse voltage
Dielectric strength
Insulation between open contacts (EMR)
Type of disconnection
Dielectric strength
V AC 230/400
V AC 250
3
Reinforced
III
kV (1.2/50) μs 6
V AC 4,000
Micro-disconnection
V AC/kV (1.2/50) μs 1,000/1.5
Conducted disturbance immunity
Fast transients (burst 5/50 ns, 5 kHz) according to EN 61000-4-4
at supply terminals
Voltage pulses (surge 1.2/50 μs) according to EN 61000-4-5 at
supply terminals (differential mode)
Other data
Bounce time (EMR) : NO/NC
Vibration resistance (EMR,10..55 Hz): NO/NC
without contact current
Power lost to the environment
with rated current
Terminals
Wire strip length
Screw torque
400
2
UN ≤ 60 V
UN = 125 V
UN = 230 V
kV 4
4
4
kV 0.8
2
4
ms 1/6
g 10/15
W 0.2 (24 V) – 0.4 (230 V)
W 0.6 (24 V) – 0.9 (230 V)
mm 10
Nm 0.5
Solid and stranded cable
mm2 1 x 2.5/2 x 1.5
AWG 1 x 14/2 x 16
mm2 1 x 0.2
AWG 1 x 24
Max. wire size
Min. wire size
Contact specification (EMR)
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
H 39 - Maximum DC1 breaking capacity
DC breaking current (A)
Cycles
F 39 - Electrical life (AC) v contact current
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 60·103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
15
39 Series - Relay interface modules - Technical data
Coil specifications - Electromechnical Relay
Coil data sensitive DC, type 39.31
Nominal
Voltage
Coil code
UN
V
125
Operating range
Must drop-out Rated input
Rated power
current at UN
voltage
Umin
Umax
Ur
IN
at UN
V
V
V
mA
W
(110...125)
7.125
88
138
12.5
4.6
0.6
220
7.220
176
242
22
3.0
0.6
Coil data AC/DC, type 39.11/21/31/41
Nominal
Voltage
Coil code
UN
V
6
0.006
Operating range
Must drop-out Rated input
Rated power
current at UN
voltage
Umin
Umax
Ur
IN
at UN
V
V
V
mA
VA/W
4.8
6.6
0.6
35
0.2/0.2
12
0.012
9.6
13.2
1.5
15
0.2/0.2
24
0.024
19.2
26.4
2.4
11
0.25/0.25
60(1)
0.060
48
66
6.0
125(2)
(110…125)
5.7
0.35/0.35
(1)
(2)
0.125
88
138
12.5
5.6
0.7/0.7
60 V AC/DC for type 39.31 only
125 V AC/DC for types 39.21/31/41 only
Coil data AC, type 39.11/21/31/41
Nominal
Voltage
Coil code
UN
V
230
(230...240)
8.230
Operating range
Must drop-out
voltage
Rated input
Rated power
current at UN
Umin
Umax
Ur
IN
at UN
V
V
V
mA
VA/W
184
264
23
4.3
1/0.4
Coil data leakage current suppression versions, type 39.31.3
Nominal
Voltage
Coil code
UN
V
125
(110...125)
230
(230...240)
Operating range
Must drop-out Rated input
Rated power
current at UN
voltage
Umin
Umax
Ur
IN
at UN
V
V
V
mA
VA/W
3.125
88
138
44
8.4
1.1/1
3.230
184
264
72
5.9
1.4/0.5
The 39 Series interface modules (supply version 3) have builtin leakage current suppression to address industry concerns
of the contacts not dropping-out when there is residual current
in the circuit; at (110...125)V AC and (230...240)V AC.
This problem can occur, for example, when connecting the
interface modules to PLC‚s with triac outputs or when
connecting via relatively long cables.
Coil data AC/DC timer, type 39.81
Nominal
Voltage
Coil code
UN
V
16
Operating range
(AC/DC)
Umin
Umax
Must drop-out
voltage
Rated input current at UN
Ur
DC
AC
mA
Rated power at UN
DC
AC
V
V
V
mA
W
VA/W
12
0.012
9.6
13.2
1.2
15
23
0.2
0.3/0.2
24
0.024
19.2
26.4
2.4
11
19
0.25
0.4/0.3
39 Series - Relay interface modules - Technical data
Input specifications - Solid State Relay
Input data sensitive DC, type 39.10/20/30/40
Nominal
Voltage
Input code
UN
V
7.006
6
12
24
60
(1)
(2)
125
(2)
(110...125)
220
(2)
Operating range
Must drop-out Rated input
current at UN
voltage
Umin
Umax
Ur
IN
V
V
V
mA
4.8
6.6
0.6
7.5
Rated
power
at UN
W
0.2
7.012
9.6
13.2
1.2
20.7
0.25
7.024
19.2
26.4
2.4
10.5
0.25
7.060
48
66
6.0
6.4
0.4
7.125
88
138
12.5
4.6
0.6
7.220
176
242
22
3.0
0.6
(1)
(2)
24 V DC for type 39.10/20/30 only
60 V DC, 125 V DC and 220 V DC for type 39.30 only
(3)
24 V AC/DC for type 39.30/40 only
Input data AC/DC, type 39.20/30/40
Nominal
Voltage
Input code
UN
V
24
(3)
125
(110...125)
Operating range
Must drop-out Rated input
current at UN
voltage
Rated
power
Umin
Umax
Ur
IN
at UN
V
V
V
mA
VA/W
0.024
19.2
0.125
88
26.4
138
2.4
17.5
0.4/0.3
12.5
5.5
0.7/0.7
Input data AC, type 39.10/20/30/40
Nominal
Voltage
Input code
UN
V
230
(230...240)
8.230
Operating range
Must drop-out Rated input
current at UN
voltage
Rated
power
Umin
Umax
Ur
IN
at UN
V
V
V
mA
VA/W
184
264
23
4.2
1/0.4
Input data leakage current suppression versions, type 39.30.3
Nominal
Voltage
Input code
UN
V
125
(110...125)
230
(230...240)
Operating range
Must drop-out Rated input
current at UN
voltage
Rated
power
Umin
Umax
Ur
IN
at UN
V
V
V
mA
VA/W
3.125
88
138
44
8.4
1.1/1
3.230
184
264
72
5.9
1.4/0.5
The 39 Series interface modules (supply version 3) have builtin leakage current suppression to address industry concerns
of the contacts not dropping-out when there is residual current
in the circuit; at (110...125)V AC and (230...240)V AC.
This problem can occur, for example, when connecting the
interface modules to PLC‚s with triac outputs or when connecting via relatively long cables.
Input data AC/DC timer, type 39.80
Nominal
Voltage
Input code
UN
V
Operating range
(AC/DC)
Umin
Umax
Must drop-out
voltage
Rated input current at UN
Ur
DC
AC
mA
Rated power at UN
DC
AC
V
V
mA
W
VA/W
12
0.012
9.6
13.2
1.2
15
23
0.2
0.3/0.2
24
0.024
19.2
26.4
2.4
11
19
0.25
0.4/0.3
V
17
39 Series - Timed interface modules
Timer specifications
EMC specifications
Type of test
Electrostatic discharge
Radio-frequency electromagnetic field
Fast transients (burst) (5-50 ns, 5 and 100 kHz)
Surges (1.2/50 μs) on supply and control
signal terminals
Radio-frequency common mode (0.15 ÷ 80
MHz)
contact discharge
air discharge
(80 ÷ 1,000 MHz)
(1,400 ÷ 2,700 MHz)
on Supply terminals
on control signal terminals
common mode
differential mode
on Supply terminals
on control signal terminals
Radiated and conducted emission
Other data
Bounce time (EMR) : NO/NC
Vibration resistance (EMR,10..55 Hz): NO/NC
without contact current
Power lost to the environment
with rated current
Terminals
Wire strip length
Screw torque
Reference standard
EN 61000-4-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-3
EN 61000-4-4
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
EN 61000-4-6
EN 55022
4 kV
8 kV
10 V/m
10 V/m
4 kV
4 kV
2 kV
0.8 kV
10 V
3V
class B
ms 1/6
g 10/15
W 0.3
W 0.8
mm 10
Nm 0.5
Solid and stranded cable
mm2 1 x 2.5/2 x 1.5
AWG 1 x 14/2 x 16
mm2 1 x 0.2
AWG 1 x 24
Max. wire size
Min. wire size
Times scales
Functions
18
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
(0.1...3)s
(3...60)s
(1...20)min
(0.3...6)h
LED
Supply voltage
NO contact/output
OFF
Open
ON
Open
ON
Open (timing to close in progress)
ON
Closed
39 Series - Timed interface modules
Wiring diagram
U = Supply voltage
= Output contact
1 2 3 4 5
(AI) On-delay
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs when power is
removed.
1 2 3 4 5
(DI) Interval
Apply power to timer. Output contacts transfer
immediately. After the preset time has elapsed, contacts
reset.
1 2 3 4 5
(GI) Pulse (0.5s) delayed
Apply power to timer. Output contacts transfer after
preset time has elapsed. Reset occurs after a fixed time
of 0.5s.
Without control signal
1 2 3 4 5
With control signal
(SW) Symmetrical flasher (starting pulse on)
Apply power to timer. Output contacts transfer
immediately and cycle between ON and OFF for as
long as power is applied. The ratio is 1:1 (time on =
time off).
1 2 3 4 5
(BE) Off-delay with control signal
Power is permenently applied to the timer. The output
contacts transfer immediately on closure of the
Signal Switch (S). Opening the Signal Switch
initiates the preset delay, after which time the output
contacts reset.
1 2 3 4 5
(CE) On- and off-delay with control signal
Power is permenently applied to the timer. Closing the
Signal Switch (S) initiates the preset delay, after which
time the output contacts transfer. Opening the Signal
switch initiates the same preset delay, after which time
the output contacts reset.
*
*With DC supply,
positive polarity has to
be conneted to B1,
terminal (according to
EN 60204-1).
S = Signal switch
1 2 3 4 5
1 2 3 4 5
(DE) Interval with control signal on
Power is permenently applied to the timer. On momentary
or maintained closure of Signal Switch (S), the output
contacts transfer, and remain so for the duration of the
preset delay, after which they reset.
(EE) Interval with control signal off
Power is permenently applied to the timer. On opening
of the Signal Switch (S) the output contacts transfer, and
remain so for the duration of the preset delay, after
which they reset.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 24 V AC
B1 - A2 = 12 V DC
19
39 Series - Relay interface modules 0.1 - 2 - 6 A
Outline drawings
39.20
39.21
Screw terminal
I
REG
ERED
U
MM
CO
D
E S I
NI
TY
E S I
39.40
39.41
Screw terminal
E S I
39.80
39.81
Screw terminal
ERED
ITY
G
UN
MM
CO
D
E S I
N
REG
I
ST
ERED
UN
MM
CO
D
E S I
ITY
N
ST
I
ITY
REG
N
MU
G
M
CO
D
ERED
N
REG
I
ST
G
39.30 / 39.30.3
39.31 / 39.31.3
Screw terminal
20
ST
TY
G
CO
D
NI
N
ERED
U
MM
N
REG
I
ST
G
39.10
39.11
Screw terminal
39 Series - Relay interface modules 0.1 - 2 - 6 A
Electromechanical Relay (1 Pole 6 A) & Socket Combinations
Interface Module Code
MasterBASIC
39.11.0.006.0060
39.11.0.012.0060
39.11.0.024.0060
39.11.8.230.0060
MasterPLUS
39.31.0.006.0060
39.31.0.012.0060
39.31.0.024.0060
39.31.0.060.0060
39.31.0.125.0060
39.31.8.230.0060
39.31.7.125.0060
39.31.7.220.0060
39.31.3.125.0060
39.31.3.230.0060
MasterINPUT
39.41.0.006.5060
39.41.0.012.5060
39.41.0.024.5060
39.41.0.125.5060
39.41.8.230.5060
MasterOUTPUT
39.21.0.006.0060
39.21.0.012.0060
39.21.0.024.0060
39.21.0.125.0060
39.21.8.230.0060
MasterTIMER
39.81.0.012.0060
39.81.0.024.0060
Coil voltage
Relay
Socket
6 V AC/DC
12 V AC/DC
24 V AC/DC
(230...240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
6 V AC/DC
12 V AC/DC
24 V AC/DC
60 V AC/DC
(110...125)V AC/DC
(230...240)V AC
(110...125)V DC
220 V DC
(110...125)V AC
(230...240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
34.51.7.060.0010
93.63.7.024
93.63.7.024
93.63.7.024
93.63.7.060
93.63.0.125
93.63.8.230
93.63.7.125
93.63.7.220
93.63.3.125
93.63.3.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125) V AC/DC
(230...240)V AC
34.51.7.005.5010
34.51.7.012.5010
34.51.7.024.5010
34.51.7.060.5010
34.51.7.060.5010
93.64.0.024
93.64.0.024
93.64.0.024
93.64.0.125
93.64.8.230
6 V AC/DC
12 V AC/DC
24 V AC/DC
(110…125) V AC/DC
(230...240)V AC
34.51.7.005.0010
34.51.7.012.0010
34.51.7.024.0010
34.51.7.060.0010
34.51.7.060.0010
93.62.7.024
93.62.7.024
93.62.7.024
93.62.0.125
93.62.8.230
12 V AC/DC
24 V AC/DC
34.51.7.012.0010
34.51.7.024.0010
93.68.0.024
93.68.0.024
93.61.7.024
93.61.7.024
93.61.7.024
93.61.8.230
Solid State Relay (1 Pole 0.1 or 2 A) & Socket Combinations
Example: .xxxx
.9024
.7048
.8240
Interface Module Code
MasterBASIC
39.10.7.006.xxxx
39.10.7.012.xxxx
39.10.7.024.xxxx
39.10.8.230.xxxx
MasterPLUS
39.30.7.006.xxxx
39.30.7.012.xxxx
39.30.7.024.xxxx
39.30.7.060.xxxx
39.30.7.125.xxxx
39.30.7.220.xxxx
39.30.0.024.xxxx
39.30.0.125.xxxx
39.30.8.230.xxxx
39.30.3.125.xxxx
39.30.3.230.xxxx
MasterINPUT
39.40.7.006.xxxx
39.40.7.012.xxxx
39.40.0.024.xxxx
39.40.0.125.xxxx
39.40.8.230.xxxx
MasterOUTPUT
39.20.7.006.xxxx
39.20.7.012.xxxx
39.20.7.024.xxxx
39.20.0.125.xxxx
39.20.8.230.xxxx
MasterTIMER
39.80.0.012.xxxx
39.80.0.024.xxxx
Input voltage
Relay
Socket
6 V DC
12 V DC
24 V DC
(230...240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
6 V DC
12 V DC
24 V DC
60 V DC
(110...125)V DC
220 V DC
24 V AC/DC
(110...125)V AC/DC
(230...240)V AC
(110...125)V AC
(230...240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.63.7.024
93.63.7.024
93.63.7.024
93.63.7.060
93.63.7.125
93.63.7.220
93.63.0.024
93.63.0.125
93.63.8.230
93.63.3.125
93.63.3.230
6 V DC
12 V DC
24 V AC/DC
(110…125) V AC/DC
(230...240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.64.0.024
93.64.0.024
93.64.0.024
93.64.0.125
93.64.8.230
6 V DC
12 V DC
24 V DC
(110…125) V AC/DC
(230...240)V AC
34.81.7.005.xxxx
34.81.7.012.xxxx
34.81.7.024.xxxx
34.81.7.060.xxxx
34.81.7.060.xxxx
93.62.7.024
93.62.7.024
93.62.7.024
93.62.0.125
93.62.8.230
12 V AC/DC
24 V AC/DC
34.81.7.012.xxxx
34.81.7.024.xxxx
93.68.0.024
93.68.0.024
93.61.7.024
93.61.7.024
93.61.7.024
93.61.8.230
21
ERED
ITY
39 Series - Relay interface modules 0.1 - 2 - 6 A
G
UN
MM
CO
D
E S I
N
REG
I
ST
Accessories
Output fuse module for 39.31/30/81/80 types
- For 5 x 20 mm fuses up to 6 A, 250 V
- Easy visibility of the fuse condition through the window
- Quick connection to socket
093.63
093.63
Multi-state fuse module
0. As delivered, the socket comes without a fuse module. However, the absent fuse is internally replaced with an electrical
link - which allows the interface relay to be used without a fuse module.
In this state, the peg/indicator is visually hidden and the connection is protected by a special cap.
1. With fuse module inserted after removing the cap, the fuse is positioned electrically in series with the common output
terminal of the interface module (11 for EMR versions, 13+ for SSR versions, 15 for EMR timer, 15+ for SSR timer).
This state is indicated by the peg/indicator.
2. If the fuse module is extracted (for example; because the fuse element has blown) the output circuit will be locked open,
as this will generally be the “safe option”.
This state is indicated by the peg/indicator.
3. In order to reinstate the output circuit it is necessary to either re-insert the fuse module (complete with functional fuse),
or alternatively, return the peg/indicator to position 0 by gently applying pressure in the direction of the arrow.
22
ERED
ITY
39 Series - Relay interface modules 0.1 - 2 - 6 A
G
UN
MM
CO
D
E S I
N
REG
I
ST
Accessories
093.16
16-way jumper link
093.16 (blue)
Rated values
36 A - 250 V
093.16.0 (black)
093.16.1 (red)
Possibility of multiple connection, side by side
093.16.0
093.16.1
Dual-purpose plastic separator (1.8 mm or 6.2 mm separation)
093.60
1. By breaking off the protruding ribs (by hand), the separator becomes only 1.8 mm thick; useful for the visual separation
of different groups of interfaces, or necessary for the protective separation of different voltages of neighbouring
interfaces, or for the protection of cut ends of jumper links.
093.60
2. Leaving the ribs in place provides 6.2mm separation. Simply cutting (with scissors) the relevant segment(s) permits the
interconnection across the separator of 2 different groups of interface relays, using the standard jumper link.
Sheet of marker tags, plastic, 72 tags, 6x12 mm
060.72
060.72
23
39 Series - Relay interface modules 0.1 - 2 - 6 A
Accessories
MasterADAPTER
093.68.14.1
The MasterADAPTER permits the easy connection of A1/A2 terminals of up to MasterINTERFACE modules to PLC outputs
via a 14-Pole ribbon cable, plus simple 2-wire power supply connection.
Technical data
Rated current (per signal path)
Minimum required supply power
093.68.14.1
Nominal voltage (UN)
A
1
W
3
V DC
24
Operating range
(0.8...1.1) UN
Control logic
Positive switching (to A1)
Power supply status indication
Green LED
Ambient temperature range
°C
–40…+70
Terminals for 24 V control logic
Type of connector
14 pole, according to IEC 60603-13
Terminals for 24 V power supply
Wire strip length
mm
9.5
Screw torque
Nm
0.5
Max. wire size
solid wire
stranded wire
1 x 4/2 x 1.5
AWG
1 x 12/2 x 16
mm2
AWG
Connected MasterADAPTER
Wiring diagram
24
mm2
1 x 2.5/2 x 1.5
1 x 14/2 x 16