46
SЕRIES
Miniature Industrial
relay 8 - 16 A
Automation for
blinds, grilles
and shutters
Elevators and lifts
Shipyards
Road / tunnel
lighting
Hoists and
cranes
Bottling plant
Control panels
Panels for electrical
distribution
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
46 SERIES
Miniature industrial relays 8 to16 A
46
SERIES
46.52
1 & 2 CO industrial style power relays
For socket mount or direct connection via
Faston connectors
46.61
A
Type 46.52
-- 2 CO 8 A
Type 46.61
-- 1 CO 16 A
• AC coils & DC coils
• Available with: lockable test button,
mechanical indicator & LED indicator
• 8 mm, 6 kV (1.2/50 μs) isolation, coil-contacts
• Cadmium free contacts
• 97 series 35 mm rail (EN 60715) Screw,
• 2 CO 8 A
• Plug-in/Solder terminals
• 1 CO 16 A
• Plug-in/Faston 187
Screwless or Push-in terminals, and PCB mount
sockets
• Coil Indication and EMC suppression modules
99 series and Timer module 86.30 options
• Optional alternative mounting adaptors
• European Patent
For UL ratings see:
“General technical information” page V
For outline drawing see page 6
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
1 CO (SPDT)
8/15
16/25*
250/440
250/440
VA
2000
4000
Rated load AC15 (230 V AC)VA
350
750
Single phase motor rating (230 V AC)kW
0.37
0.55
Breaking capacity DC1: 30/110/220 VA
6/0.5/0.15
12/0.5/0.15
Minimum switching load
300 (5/5)
300 (5/5)
AgNi
AgNi
Rated load AC1
V AC
2 CO (DPDT)
mW (V/mA)
Standard contact material
* With the AgSnO2 material
the maximum peak current is
80 A - 5 ms on normally open
contact.
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
12 - 24 - 48 - 110 - 120 - 230 - 240
V DC
Rated power
Operating range
VA/W
AC
12 - 24 - 48 - 110 - 125
1.2/0.5
1.2/0.5
(0.8…1.1)UN
(0.8…1.1)UN
DC
(0.73…1.1)UN
(0.73…1.1)UN
Holding voltage
AC/DC
0.8 UN / 0.4 UN
0.8 UN / 0.4 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life AC/DC
cycles
10 · 106
10 · 106
Electrical life at rated load AC1
cycles
100 · 10
100 · 103
ms
10/3
15/5
kV
6 (8 mm)
6 (8 mm)
Technical data
X-2018, www.findernet.com
Operate/release time
Insulation between coil
and contacts (1.2/50 μs)
Dielectric strength
between open contacts
Ambient temperature range
Environmental protection
V AC
°C
3
1000
1000
–40…+70
–40…+70
RT II
RT II
Approvals (according to type)
3
46
SERIES
46 SERIES
Miniature industrial relays 8 to16 A
Ordering information
Example: 46 series Miniature industrial relay, 1 CO, 24 V DC coil, lockable test button and mechanical indicator.
A
4 6 . 6
A
B
C
D
1 . 9 . 0 2 4 . 0
0
4
0
Series
A: Contact material
0 = AgNi
4 = AgSnO2 (46.61 only)
5 = AgNi + Au
Type
5 = Spade/blade solder terminal
(2.5 x 0.5)mm
6 = Spade/blade terminal
Faston 187 (4.8 x 0.5)mm
D: Special versions
0 = S tandard
C: Options
2 = M
echanical indicator
4 = L ockable test button +
mechanical indicator
54 = L ockable test button + LED (AC) +
mechanical indicator
74 = L ockable test button + double LED
(DC non-polarized) + mechanical
indicator
B: Contact circuit
0 = CO (nPDT)
No. of poles
1 = 1 pole, 16 A
2 = 2 poles, 8 A
Coil version
9 = DC
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
Coil version
A
B
C
D
46.52
AC - DC
0-5
0
2-4
0
AC
0-5
0
54
/
DC
0-5
0
74
/
AC - DC
0-4-5
0
2-4
0
AC
0-4-5
0
54
/
DC
0-4-5
0
74
/
46.61
Special versions for Rail Applications on request
Descriptions: Options
EAN
N
T E
P A
Lockable test button and mechanical flag indicator (0040, 0054, 0074)
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly below the test button) remains intact. In this
case, when the test button is pushed, the contacts operate. When the test button is
released the contacts return to their former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case,
(in addition to the above function), when the test button is pushed and rotated, the
contacts are latched in the operating state, and remain so until the test button is rotated
back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
EAN
1
4
3
T
X-2018, www.findernet.com
OP
EUR
2
EUR
C: Option 74
LED (DC, non-polarized)
OP
C: Option 54
LED (AC)
46 SERIES
Miniature industrial relays 8 to16 A
46
SERIES
Technical data
Insulation according to EN 61810-1
1 pole
Nominal voltage of supply system
V AC 230/400
Rated insulation voltage
V AC 250
Pollution degree
A
2 pole
230/400
3
400
250
400
2
3
2
Insulation between coil and contact set
Type of Insulation
Reinforced (8 mm)
Reinforced (8 mm)
Overvoltage category
III
III
kV (1.2/50 μs) 6
6
Rated impulse voltage
Dielectric strength
V AC 4000
4000
Insulation between adjacent contacts
Type of insulation
—
Basic
Overvoltage category
—
III
kV (1.2/50 μs) —
4
Rated impulse voltage
Dielectric strength
V AC —
2000
Insulation between open contacts
Type of disconnection
Micro-disconnection
Dielectric strength
V AC/kV (1.2/50 μs) 1000/1.5
Micro-disconnection
1000/1.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5)
kV(1.2/50 µs) 2
Other data
46.61
Bounce time: NO/NC
ms 2/6
46.52
1/4
Vibration resistance (10…150)Hz: NO/NC
g 20/12
20/15
Shock resistance
g 20
20
without contact current
W 0.6
0.6
with rated current
W 1.6
2
Power lost to the environment
Recommended distance between relays mounted on PCB
mm ≥ 5
Contact specification
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
DC breaking current (A)
X-2018, www.findernet.com
H 46 - Maximum DC1 breaking capacity
46.61 limit current
46.52 limit current
F 46 - E
lectrical life (AC) v contact current
Type 46.61
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
Cycles
Cycles
F 46 - Electrical life (AC) v contact current
Type 46.52
• When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC voltage (V)
5
46 SERIES
Miniature industrial relays 8 to16 A
46
SERIES
Coil specifications
DC coil data
A
Nominal
voltage
AC coil data
Coil code
Operating range
Resistance
Rated coil
consumption
Nominal
voltage
Coil code
Operating range
Resistance
Rated coil
consumption
UN
Umin
Umax
R
I at UN
UN
Umin
Umax
R
I at UN
V
V
V
Ω
mA
V
V
V
Ω
mA
12
9.012
8.8
13.2
300
40
12
8.012
9.6
13.2
80
90
24
9.024
17.5
26.4
1200
20
24
8.024
19.2
26.4
320
45
48
9.048
35
52.8
4800
10
48
8.048
38.4
52.8
1350
21
110
9.110
80
121
23500
4.7
110
8.110
88
121
6900
9.4
125
9.125
91.2
138
32000
3.9
120
8.120
96
132
9000
8.4
R 46 - DC coil operating range v ambient temperature
230
8.230
184
253
28000
5
240
8.240
192
264
31500
4.1
R 46 - AC coil operating range v ambient temperature
1
1
2
2
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
Outline drawings
Type 46.52
Type 46.61
12.4
0.5
4.75
X-2018, www.findernet.com
4.75
6.5
20
32.8
29
6
97 SERIES
Sockets and accessories for 46 series relays
46
SERIES
Accessories
Flange mount adaptor for relays types 46.52 and 46.61
046.05
36.6
3.6
A
2
46
38
046.05
14.4
18.1
046.05
046.05 with relay
046.05 with relay
35 mm rail adaptor for relays types 46.52 and 46.61
046.07
42.4
39.8
14.4
35.4
46.9
34.8
046.07
046.07
046.07 with relay
046.07 with relay
Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types 46.52 and 46.61 (48 tags),
6 x 12 mm
060.48
X-2018, www.findernet.com
060.48
7
46
SERIES
97 SERIES
Sockets and accessories for 46 series relays
Push-in terminal socket panel or 35 mm rail (EN 60715) mount 97.P1
For relay type
46.61
97.P2
46.52
Accessories
A
97.P2
Approvals
(according to type):
097.01
060.48
Plastic retaining and release clip
(supplied with socket - packaging code SPA)
097.01
Metal retaining clip
097.71
Identification tag
095.00.4
8-way jumper link
097.58
2-way jumper link
097.52
2-way jumper link
097.42
Marker tag holder
097.00
Modules (see table below)
99.02
Timer modules (see table below)
86.30
Sheet of marker tags for marker tag holder 097.00, 48 tags,
6 x 12 mm, for CEMBRE thermal transfer printers
060.48
Technical data
Rated values
10 A-250 V AC
8 A-250 V AC
Dielectric strength
6 kV (1.2/50 μs) between coil and contacts
Protection category
IP 20
Ambient temperature
°C –40…+70
Wire strip length
mm 8
Min. wire size for 97.P1 and 97.P2 socket
solid wire
stranded wire
0.5
mm2 0.5
AWG 21
21
Max. wire size for 97.P1 and 97.P2 socket
solid wire
stranded wire
2 x 1.5 / 1 x 2.5
mm2 2 x 1.5 / 1 x 2.5
AWG 2 x 16 / 1 x 14
2 x 16 / 1 x 14
97.P1
97.P2
8-way jumper link for 97.P1 and 97.P2 sockets
Rated values
097.58
10 A - 250 V
2-way jumper link for 97.P1 and 97.P2 sockets
Rated values
097.52
10 A - 250 V
097.58
X-2018, www.findernet.com
097.52
8
97 SERIES
Sockets and accessories for 46 series relays
2-way jumper link for 97.P1 and 97.P2 sockets
Rated values
46
SERIES
097.42
10 A - 250 V
A
097.42
Marker tag holder for 97.P1 and 97.P2 sockets
097.00
86 series timer modules
(12…24)V AC/DC; Bi-function: AI, DI; (0.05 s…100 h)
(110…125)V AC; Bi-function: AI, DI; (0.05 s…100 h)
(230…240)V AC; Bi-function: AI, DI; (0.05 s…100 h)
86.30.0.024.0000
86.30.8.120.0000
86.30.8.240.0000
097.00
86.30
99.02
Approvals
(according to type):
99.02 coil indication and EMC suppression modules for 97.P1 and 97.P2 sockets
Diode (+A1, standard polarity)
(6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
LED + Diode (+A1, standard polarity)
(6…24)V DC 99.02.9.024.99
LED + Diode (+A1, standard polarity)
(28…60)V DC 99.02.9.060.99
LED + Diode (+A1, standard polarity)
(110…220)V DC 99.02.9.220.99
LED + Varistor
(6…24)V DC/AC 99.02.0.024.98
LED + Varistor
(28…60)V DC/AC 99.02.0.060.98
LED + Varistor
(110…240)V DC/AC 99.02.0.230.98
RC circuit
(6…24)V DC/AC 99.02.0.024.09
RC circuit
(28…60)V DC/AC 99.02.0.060.09
RC circuit
(110…240)V DC/AC 99.02.0.230.09
Residual current by-pass
(110…240)V AC 99.02.8.230.07
X-2018, www.findernet.com
DC Modules with
non-standard polarity
(+A2) on request.
Approvals (according to type):
9
46
SERIES
97 SERIES
Sockets and accessories for 46 series relays
Screw terminal socket panel or 35 mm rail (EN 60715) mount
For relay type
Accessories
Plastic retaining and release clip
(supplied with socket - packaging code SPA)
Metal retaining clip
Marker tag holder
Identification tag
8-way jumper link
Modules (see table below)
Timer modules (see table below)
Sheet of marker tags for marker tag holder 097.00, 48 tags,
6 x 12 mm, for CEMBRE thermal transfer printers
Technical data
Rated values
Dielectric strength
Protection category
Ambient temperature
A
97.01
Approvals
(according to type):
097.01
Screw torque
97.01
(blue)
46.61
97.01.0
(black)
97.02
(blue)
46.52
97.02.0
(black)
097.01
097.71
097.00
095.00.4
095.18.0 (black)
99.02
86.30
095.18 (blue)
060.48
16 A-250 V AC
8 A-250 V AC
6 kV (1.2/50 μs) between coil and contacts
IP 20
°C –40…+70 (see diagram L97)
Nm 0.8
Wire strip length
Max. wire size for 97.01 and 97.02 socket
mm 8
solid wire
mm2 1 x 6 / 2 x 2.5
AWG 1 x 10 / 2 x 14
060.48
stranded wire
1 x 4 / 2 x 2.5
1 x 12 / 2 x 14
Rated current (A)
L 97 - Rated current v ambient temperature
(for 46.61 relay/97.01 socket combination)
R
97.01
OP
EAN
EU
N T
T E
P A
97.01
97.02
97.02
095.18 (blue)
10 A - 250 V
86 series timer modules
(12…24)V AC/DC; Bi-function: AI, DI; (0.05 s…100 h)
(110…125)V AC; Bi-function: AI, DI; (0.05 s…100 h)
(230…240)V AC; Bi-function: AI, DI; (0.05 s…100 h)
86.30.0.024.0000
86.30.8.120.0000
86.30.8.240.0000
095.18.0 (black)
EUR
8-way jumper link for 97.01 and 97.02 sockets
Rated values
OP
EAN
095.18
99.02
Approvals
(according to type):
DC Modules with
non-standard polarity
(+A2) on request.
10
Approvals (according to type):
99.02 coil indication and EMC suppression modules for 97.01 and 97.02 sockets
Diode (+A1, standard polarity)
(6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
LED + Diode (+A1, standard polarity)
(6…24)V DC 99.02.9.024.99
LED + Diode (+A1, standard polarity)
(28…60)V DC 99.02.9.060.99
LED + Diode (+A1, standard polarity)
(110…220)V DC 99.02.9.220.99
LED + Varistor
(6…24)V DC/AC 99.02.0.024.98
LED + Varistor
(28…60)V DC/AC 99.02.0.060.98
LED + Varistor
(110…240)V DC/AC 99.02.0.230.98
RC circuit
(6…24)V DC/AC 99.02.0.024.09
RC circuit
(28…60)V DC/AC 99.02.0.060.09
RC circuit
(110…240)V DC/AC 99.02.0.230.09
Residual current by-pass
(110…240)V AC 99.02.8.230.07
X-2018, www.findernet.com
86.30
97 SERIES
Sockets and accessories for 46 series relays
Screwless terminal socket panel or 35 mm rail (EN 60715)
mount
For relay type
46
SERIES
97.51
(blue)
46.61
97.51.0
(black)
97.52
(blue)
46.52
97.52.0
(black)
A
Accessories
97.51
Approvals
(according to type):
097.01
Plastic retaining and release clip
(supplied with socket - packaging code SPA)
Metal retaining clip
Modules (see table below)
Timer modules (see table below)
Technical data
Rated values
Dielectric strength
Protection category
Ambient temperature
Wire strip length
Max. wire size for 97.51 and 97.52 sockets
97.51
97.51
86 series timer modules
(12…24)V AC/DC; Bi-function: AI, DI; (0.05 s…100 h)
(110…125)V AC; Bi-function: AI, DI; (0.05 s…100 h)
(230…240)V AC; Bi-function: AI, DI; (0.05 s…100 h)
86.30
99.02
Approvals
(according to type):
10 A - 250 V AC
8 A - 250 V AC
6 kV (1.2/50 μs) between coil and contacts
IP 20
°C –25…+70
mm 8
solid wire
stranded wire
2 x (0.5…1.5)
mm2 2 x (0.5…1.5)
AWG 2 x (21…18)
2 x (21…18)
97.52
97.52
86.30.0.024.0000
86.30.8.120.0000
86.30.8.240.0000
Approvals (according to type):
99.02 coil indication and EMC suppression modules for 97.51 and 97.52 sockets
Diode (+A1, standard polarity)
(6…220)V DC 99.02.3.000.00
LED(6…24)V DC/AC 99.02.0.024.59
LED(28…60)V DC/AC 99.02.0.060.59
LED(110…240)V DC/AC 99.02.0.230.59
LED + Diode (+A1, standard polarity)
(6…24)V DC 99.02.9.024.99
LED + Diode (+A1, standard polarity)
(28…60)V DC 99.02.9.060.99
LED + Diode (+A1, standard polarity)
(110…220)V DC 99.02.9.220.99
LED + Varistor
(6…24)V DC/AC 99.02.0.024.98
LED + Varistor
(28…60)V DC/AC 99.02.0.060.98
LED + Varistor
(110…240)V DC/AC 99.02.0.230.98
RC circuit
(6…24)V DC/AC 99.02.0.024.09
RC circuit
(28…60)V DC/AC 99.02.0.060.09
RC circuit
(110…240)V DC/AC 99.02.0.230.09
Residual current by-pass
(110…240)V AC 99.02.8.230.07
X-2018, www.findernet.com
DC Modules with
non-standard polarity
(+A2) on request.
097.01
097.71
99.02
86.30
11
46
SERIES
97 SERIES
Sockets and accessories for 46 series relays
PCB socket
For relay type
Technical data
Rated values
A
97.11
Approvals
(according to type):
97.11 (blue)
46.61
97.12 (blue)
46.52
12 A - 250 V
8 A - 250 V
(see diagram L97)
6 kV (1.2/50 μs) between coil and contacts
IP 20
°C –40…+70
Dielectric strength
Protection category
Ambient temperature
L 97 - Rated current v ambient temperature
(for 46.61 relay/97.11 socket combination)
Rated current (A)
97.12
Approvals
(according to type):
97.11
97.12
Copper side view
Copper side view
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
12
1
S P
A
A
Standard packaging
SM
SL
Metal retaining clip
Plastic retaining clip
X-2018, www.findernet.com
9 7 . P
Please see general technical information