46 Series - Miniature industrial relays 8 - 16 A
Features
46
SERIES
46.61
46.52
1 & 2 Pole relay range
46.52 - 2 Pole 8 A
46.61 - 1 Pole 16 A
A
Socket mount or direct connection via Faston
connectors
• AC coils & DC coils
• Available with: lockable test button,
mechanical indicator & LED indicator
• 8 mm, 6 kV (1.2/50 µs) isolation, coil-contacts
• Cadmium Free contacts
• European Patent
•
•
•
2 Pole CO, 8 A
Plug-in/Solder terminals
•
•
1 Pole CO, 16 A
Plug-in/Faston 187
46.52
12.4
20
32.8
29
46.61
0.5
4.75
6.5
4.75
FOR UL RATINGS SEE:
“General technical information” page V
Contact specification
Contact configuration
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage V AC
2 CO (DPDT)
1 CO (SPDT)
8/15
16/25 *
250/440
250/440
Rated load AC1
VA
2,000
4,000
Rated load AC15 (230 V AC)
VA
350
750
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.37
0.55
6/0.5/0.15
12/0.5/0.15
300 (5/5)
300 (5/5)
AgNi
AgNi
* With the AgSnO2 material
the maximum peak current is
80 A - 5 ms on normally
open contact.
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
12 - 24 - 48 - 110 - 120 - 230 - 240
V DC
Rated power
VA/W
12 - 24 - 48 - 110 - 125
1.2/0.5
1.2/0.5
AC
(0.8...1.1)UN
(0.8...1.1)UN
DC
(0.73...1.1)UN
(0.73...1.1)UN
Holding voltage
AC/DC
0.8UN /0.4UN
0.8UN /0.4UN
Must drop-out voltage
AC/DC
0.2UN /0.1UN
0.2UN /0.1UN
10 · 106
10 · 106
Operating range
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
I-2014, www.findernet.com
Operate/release time
cycles
cycles
ms
Insulation between coil and contacts (1.2/50 µs)kV
Dielectric strength between open contacts V AC
Ambient temperature range
Environmental protection
°C
3
100 · 10
100 · 103
10/3
15/5
6 (8 mm)
6 (8 mm)
1,000
1,000
–40 ... +70
–40 ... +70
RT II
RT II
Approvals (according to type)
1
46
SERIES
46 Series - Miniature industrial relays 8 - 16 A
Ordering information
Example: 46 series Miniature industrial relay, 1 CO (SPDT), 24 V DC coil, lockable test button and mechanical indicator.
A
4 6. 6
A
B
C
D
1 . 9 . 0 2 4 . 0
0
4
0
A: Contact material
0 = AgNi
4 = AgSnO2 (46.61 only)
5 = AgNi + Au
Series
Type
5 = Spade/blade solder terminal
(2.5x0.5)mm
6 = Spade/blade terminal
Faston 187 (4.8x0.5)mm
D: Special versions
0 = Standard
C: Options
2 =Mechanical indicator
4 =Lockable test button +
mechanical indicator
54 =Lockable test button + LED (AC) +
mechanical indicator
74 =Lockable test button + double LED
(DC non-polarized) + mechanical indicator
B: Contact circuit
0 = CO (nPDT)
No. of poles
1 = 1 pole, 16 A
2 = 2 poles, 8 A
Coil version
9 = DC
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
46.52
46.61
Coil version
AC - DC
AC
DC
AC - DC
AC
DC
A
0-5
0-5
0-5
0-4-5
0-4-5
0-4-5
B
0
0
0
0
0
0
C
2-4
54
74
2-4
54
74
D
0
/
/
0
/
/
Special versions for Rail Applications on request
Descriptions: Options
C: Option 74
LED (DC, non-polarized)
3
EUR
N
T E
T
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly below the test button) remains intact. In this case, when
the test button is pushed, the contacts operate. When the test button is released the contacts return
to their former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition
to the above function), when the test button is pushed and rotated, the contacts are latched in
the operating state, and remain so until the test button is rotated back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
I-2014, www.findernet.com
1
P A
PEAN
EUR
Lockable test button and mechanical flag indicator (0040, 0054, 0074)
O
PEAN
2
O
C: Option 54
LED (AC)
2
46
SERIES
46 Series - Miniature industrial relays 8 - 16 A
Technical data
Insulation according to EN 61810-1
1 pole
V AC
230/400
Rated insulation voltage
V AC
250
400
250
400
3
2
3
2
Pollution degree
A
2 pole
Nominal voltage of supply system
230/400
Insulation between coil and contact set
Type of insulation
Reinforced (8 mm)
Overvoltage category
Rated impulse voltage
kV (1.2/50 µs)
Dielectric strength
V AC
Reinforced (8 mm)
III
III
6
6
4,000
4,000
Insulation between adjacent contacts
Type of insulation
—
Basic
Overvoltage category
—
III
kV (1.2/50 µs)
—
4
V AC
—
2,000
Micro-disconnection
Micro-disconnection
1,000/1.5
1,000/1.5
Burst (5...50)ns, 5 kHz, on A1 - A2
EN 61000-4-4
level 4 (4 kV)
Surge (1.2/50 µs) on A1 - A2 (differential mode)
EN 61000-4-5
level 3 (2 kV)
Rated impulse voltage
Dielectric strength
Insulation between open contacts
Type of disconnection
Dielectric strength
V AC/kV (1.2/50 µs)
Conducted disturbance immunity
Other data
46.61
Bounce time: NO/NC
ms
46.52
2/6
1/4
Vibration resistance (10…150)Hz: NO/NC
g
20/12
20/15
Shock resistance
g
20
20
Power lost to the environment
without contact current
W
0.6
0.6
with rated current
W
1.6
2
mm
≥ 5
Recommended distance between relays mounted on PCB
Contact specification
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
F 46 - Electrical life (AC) v contact current
Type 46.61
Cycles
Cycles
F 46 - Electrical life (AC) v contact current
Type 46.52
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
H 46 - Maximum DC1 breaking capacity
• When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100·103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC breaking current (A)
I-2014, www.findernet.com
46.61 current limit
46.52 current limit
DC voltage (V)
3
46
SERIES
46 Series - Miniature industrial relays 8 - 16 A
Coil specifications
AC coil data
DC coil data
A
Nominal
voltage
UN
V
12
24
48
110
125
Coil
code
9.012
9.024
9.048
9.110
9.125
Operating range
Umin
V
8.8
17.5
35
80
91.2
Resistance Rated coil
consumption
R
I at UN
Ω
mA
300
40
1,200
20
4,800
10
23,500
4.7
32,000
3.9
Umax
V
13.2
26.4
52.8
121
138
Nominal
voltage
UN
V
12
24
48
110
120
230
240
Coil
code
8.012
8.024
8.048
8.110
8.120
8.230
8.240
Operating range
Umin
V
9.6
19.2
38.4
88
96
184
192
Umax
V
13.2
26.4
52.8
121
132
253
264
Resistance Rated coil
consumption
R
I at UN
Ω
mA
80
90
320
45
1,350
21
6,900
9.4
9,000
8.4
28,000
5
31,500
4.1
R 46 - DC coil operating range v ambient temperature
R 46 - AC coil operating range v ambient temperature
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
Accessories
Flange mount adaptor for relays types 46.52 and 46.61
046.05
36.6
3.6
2
46
38
046.05
14.4
046.05 with relay
18.1
046.05
046.05 with relay
35 mm rail adaptor for relays types 46.52 and 46.61
046.07
42.4
39.8
14.4
046.07
046.07 with relay
Sheet of marker tags for relays types 46.52 and 46.61 (72 tags), 6x12mm
060.72
4
060.72
I-2014, www.findernet.com
35.4
46.9
046.07 with relay
34.8
046.07
46
SERIES
97 Series - Sockets and accessories for 46 series relays
Screw terminal socket panel or 35 mm rail (EN 60715) mount
For relay type
Accessories
Plastic retain and release clip
(supplied with socket - packaging code SPA)
Metal retaining clip
Identification tag
8-way jumper link
Modules (see table below)
Timer modules (see table below)
Technical data
Rated current
Dielectric strength
Protection category
Ambient temperature
°C
Screw torque
Nm
Wire strip length
mm
Max. wire size for 97.01 and 97.02 sockets
mm2
AWG
97.01
Approvals
(according to type):
097.01
97.01 (blue)
46.61
97.01.0 (black) 97.02 (blue)
46.52
97.02.0 (black)
A
097.01
095.18 (blue)
097.71
095.00.4
095.18.0 (black)
99.02
86.30
16 A - 250 V AC
8 A - 250 V AC
6 kV (1.2/50 µs) between coil and contacts
IP 20
–40…+70 (see diagram L97)
0.8
8
solid wire
stranded wire
1x6 / 2x2.5
1x4 / 2x2.5
1x10 / 2x14
1x12 / 2x14
Rated current (A)
L 97 - Rated current vs ambient temperature
(for 46.61 relay / 97.01 socket combination)
P A
PEAN
N
T E
O
O
T
EUR
EUR
97.01
97.01
97.02
97.02
8-way jumper link for 97.01 and 97.02 sockets
095.18 (blue)
Rated values
10 A - 250 V
095.18.0 (black)
PEAN
095.18
86 series timer module
86.30
99.02
I-2014, www.findernet.com
Approvals
(according to type):
DC Modules with
non-standard polarity
(+A2) on request.
(12…24)V AC/DC; Bi-function: AI, DI; (0.05s…100h)
86.30.0.024.0000
(110...125)V AC; Bi-function: AI, DI; (0.05s…100h)
86.30.8.120.0000
(230...240)V AC; Bi-function: AI, DI; (0.05s…100h)
86.30.8.240.0000
Approvals
(according to type):
99.02 coil indication and EMC suppression modules for 97.01 and 97.02
Diode (+A1, standard polarity)
(6...220)V DC
LED
(6...24)V DC/AC
LED
(28...60)V DC/AC
LED
(110...240)V DC/AC
LED + Diode (+A1, standard polarity)
(6...24)V DC
LED + Diode (+A1, standard polarity)
(28...60)V DC
LED + Diode (+A1, standard polarity)
(110...220)V DC
LED + Varistor
(6...24)V DC/AC
LED + Varistor
(28...60)V DC/AC
LED + Varistor
(110...240)V DC/AC
RC circuit
(6...24)V DC/AC
RC circuit
(28...60)V DC/AC
RC circuit
(110...240)V DC/AC
Residual current by-pass
(110...240)V AC
sockets
99.02.3.000.00
99.02.0.024.59
99.02.0.060.59
99.02.0.230.59
99.02.9.024.99
99.02.9.060.99
99.02.9.220.99
99.02.0.024.98
99.02.0.060.98
99.02.0.230.98
99.02.0.024.09
99.02.0.060.09
99.02.0.230.09
99.02.8.230.07
5
46
SERIES
97 Series - Sockets and accessories for 46 series relays
A
97.51
Approvals
(according to type):
097.01
Screwless terminal socket panel or 35 mm rail (EN 60715) mount 97.51 (blue)
For relay type
46.61
Accessories
Plastic retain and release clip
(supplied with socket - packaging code SPA)
Metal retaining clip
Modules (see table below)
Timer modules (see table below)
Technical data
Rated current
Dielectric strength
Protection category
Ambient temperature
Wire strip length
Max. wire size for 97.51 and 97.52 sockets
97.52.0 (black)
097.01
097.71
99.02
86.30
°C
mm
mm2
AWG
97.51
97.51.0 (black) 97.52 (blue)
46.52
97.51
10 A - 250 V AC
8 A - 250 V AC
6 kV (1.2/50 µs) between coil and contacts
IP 20
–25…+70
8
solid wire
stranded wire
2x(0.2...1.5)
2x(0.2...1.5)
2x(24...18)
2x(24...18)
97.52
97.52
86 series timer module
86.30
99.02
Approvals
(according to type):
86.30.0.024.0000
86.30.8.120.0000
(230...240)V AC; Bi-function: AI, DI; (0.05s…100h)
86.30.8.240.0000
Approvals (according to type):
99.02 coil indication and EMC suppression modules for 97.51 and 97.52
Diode (+A1, standard polarity)
(6...220)V DC
LED
(6...24)V DC/AC
LED
(28...60)V DC/AC
LED
(110...240)V DC/AC
LED + Diode (+A1, standard polarity)
(6...24)V DC
LED + Diode (+A1, standard polarity)
(28...60)V DC
LED + Diode (+A1, standard polarity)
(110...220)V DC
LED + Varistor
(6...24)V DC/AC
LED + Varistor
(28...60)V DC/AC
LED + Varistor
(110...240)V DC/AC
RC circuit
(6...24)V DC/AC
RC circuit
(28...60)V DC/AC
RC circuit
(110...240)V DC/AC
Residual current by-pass
(110...240)V AC
sockets
99.02.3.000.00
99.02.0.024.59
99.02.0.060.59
99.02.0.230.59
99.02.9.024.99
99.02.9.060.99
99.02.9.220.99
99.02.0.024.98
99.02.0.060.98
99.02.0.230.98
99.02.0.024.09
99.02.0.060.09
99.02.0.230.09
99.02.8.230.07
I-2014, www.findernet.com
DC Modules with
non-standard polarity
(+A2) on request.
(12…24)V AC/DC; Bi-function: AI, DI; (0.05s…100h)
(110...125)V AC; Bi-function: AI, DI; (0.05s…100h)
6
97 Series - Sockets and accessories for 46 series relays
PCB socket
For relay type
Technical data
Rated values
Dielectric strength
Protection category
Ambient temperature
97.11
Approvals
(according to type):
97.11 (blue)
46.61
46
SERIES
97.12 (blue)
46.52
A
12 A - 250 V (see diagram L97) 8 A - 250 V
6 kV (1.2/50 µs) between coil and contacts
IP 20
°C –40…+70
Rated current (A)
L 97 - Rated current vs ambient temperature
(for 46.61 relay / 97.11 socket combination)
97.12
Approvals
(according to type):
97.11
97.12
Copper side view
Copper side view
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
I-2014, www.findernet.com
9 7 . 0
1
S P
A
A
Standard packaging
SM Metal retaining clip
SP Plastic retaining clip
9 7 . 0
1
Without retaining clip
7