48 SERIES
Relay interface modules 8 A
48
SERIES
48.12
2 CO forcibly guided contacts relay interface
modules,15.8 mm wide
Type 48.12
-- 2 CO 8 A
-- Screw terminals
• Relay with forcibly guided contacts according
to EN 50205 Type B
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
B
48.12
Screw terminal
• 2 CO 8 A
• Forcibly guided contacts relay
• Screw terminals
According to EN 50205 only 1 NO and 1 NC
(11-14 and 21-22 or 11-12 and 21-24) shall be
used as forcibly guided contacts.
48.12
For outline drawing see page 9
Contact specification
Contact configuration
2 CO (DPDT)
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
8/15
250/400
Rated load AC1
VA
2000
Rated load AC15 (230 V AC)
VA
500
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
A
8/0.65/0.2
mW (V/mA)
500 (10/10)
Minimum switching load
Standard contact material
0.37
AgNi
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
—
V DC
12 - 24
VA (50 Hz)/W
—/0.7
Rated power AC/DC
Operating range
AC
—
DC
(0.75…1.2)UN
Holding voltage
AC/DC
—/0.4 UN
Must drop-out voltage
AC/DC
—/0.1 UN
Mechanical life AC/DC
cycles
—/10 · 106
Electrical life at rated load AC1
cycles
100 · 103
Technical data
III-2016, www.findernet.com
Operate/release time
Insulation between coil
and contacts (1.2/50 µs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
ms
10/4
kV
6 (8 mm)
V AC
°C
1500
–40…+70
IP 20
Approvals relay (according to type)
1
48
SERIES
48 SERIES
Relay interface modules 10 A
48.P3
1 CO relay interface modules,
15.8 mm wide
48.31
Ideal interface for PLC and electronic systems
Type 48.P3
-- 1 CO 10 A
-- Push-in terminals
• AC coils or DC sensitive coils
• Supply status indication and EMC coil
• 1 CO 10 A
• Push-in terminals
suppression module as standard
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P3
Push-in terminal
• 1 CO 10 A
• Screw terminals
48.31
Screw terminal
For outline drawing see page 9
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
1 CO (SPDT)
1 CO (SPDT)
10/20
10/20
250/400
250/400
Rated load AC1
VA
2500
2500
Rated load AC15 (230 V AC)
VA
500
500
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
A
Minimum switching load
mW (V/mA)
Standard contact material
0.37
0.37
10/0.3/0.12
10/0.3/0.12
300 (5/5)
300 (5/5)
AgNi
AgNi
12 - 24 - 110 - 120 - 230
12 - 24 - 110 - 120 - 230
12 - 24 - 125
12 - 24 - 125
1.2/0.5
1.2/0.5
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/sens. DC
V DC
VA (50 Hz)/W
AC
(0.8…1.1)UN
(0.8…1.1)UN
sens. DC
(0.73…1.5)UN
(0.73…1.5)UN
Holding voltage
AC/DC
0.8 UN / 0.4 UN
0.8 UN / 0.4 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life
cycles
10 · 106
10 · 106
Electrical life at rated load AC1
cycles
200 · 103
200 · 103
ms
7/4 (AC) - 12/12 (DC)
7/4 (AC) - 12/12 (DC)
kV
6 (8 mm)
6 (8 mm)
1000
1000
–40…+70
–40…+70
IP 20
IP 20
Operating range
Technical data
Operate/release time
Insulation between coil
and contacts (1.2/50 µs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
2
V AC
°C
III-2016, www.findernet.com
B
Type 48.31
-- 1 CO 10 A
-- Screw terminals
48 SERIES
Relay interface modules 8 A
48
SERIES
48.P5
2 CO relay interface modules,
15.8 mm wide
48.52
Ideal interface for PLC and electronic systems
Type 48.P5
-- 2 CO 8 A
-- Push-in terminals
Type 48.52
-- 2 CO 8 A
-- Screw terminals
B
• AC coils or DC sensitive coils
• Supply status indication and EMC coil
• 2 CO 8 A
• Push-in terminals
suppression module as standard
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P5
Push-in terminal
• 2 CO 8 A
• Screw terminals
48.52
Screw terminal
48.52 / 72
48.52 / 72
2 CO (DPDT)
2 CO (DPDT)
8/15
8/15
250/250
250/250
For outline drawing see page 9
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
Rated load AC1
VA
2000
2000
Rated load AC15 (230 V AC)
VA
400
400
Single phase motor rating (230 V AC)
kW
0.3
0.3
Breaking capacity DC1: 30/110/220 V
A
8/0.3/0.12
8/0.3/0.12
mW (V/mA)
300 (5/5)
300 (5/5)
AgNi
AgNi
12 - 24 - 110 - 120 - 230
12 - 24 - 110 - 120 - 230
12 - 24 - 125
12 - 24 - 125
1.2/0.5
1.2/0.5
Minimum switching load
Standard contact material
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/sens. DC
V DC
VA (50 Hz)/W
AC
(0.8…1.1)UN
(0.8…1.1)UN
sens. DC
(0.73…1.5)UN
(0.73…1.5)UN
Holding voltage
AC/DC
0.8 UN / 0.4 UN
0.8 UN / 0.4 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life
cycles
10 · 106
10 · 106
Electrical life at rated load AC1
cycles
100 · 103
100 · 103
ms
7/4 (AC) - 12/12 (DC)
7/4 (AC) - 12/12 (DC)
kV
6 (8 mm)
6 (8 mm)
1000
1000
–40…+70
–40…+70
IP 20
IP 20
Operating range
Technical data
III-2016, www.findernet.com
Operate/release time
Insulation between coil
and contacts (1.2/50 µs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
V AC
°C
Approvals relay (according to type)
3
48
SERIES
48 SERIES
Relay interface modules 16 A
48.P6
1 CO relay interface modules,
15.8 mm wide
48.61
Ideal interface for PLC and electronic systems
Type 48.P6
-- 1 CO 16 A
-- Push-in terminals
• AC coils or DC sensitive coils
• Supply status indication and EMC coil
• 1 CO 16 A
• Push-in terminals
suppression module as standard
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material available
48.P6
Push-in terminal
• 1 CO 16 A
• Screw terminals
48.61
Screw terminal
48.61 / 81
* For currents > 10 A,
contact terminals
must be connected in parallel
(21 with 11, 24 with 14, 22 with 12).
For outline drawing see page 9
48.61 / 81
* For currents > 10 A,
contact terminals
must be connected in parallel
(21 with 11, 24 with 14, 22 with 12).
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
1 CO (SPDT)
1 CO (SPDT)
16*/30
16*/30
250/400
250/400
Rated load AC1
VA
4000
4000
Rated load AC15 (230 V AC)
VA
750
750
Single phase motor rating (230 V AC)
kW
0.55
0.55
Breaking capacity DC1: 30/110/220 V
A
16/0.3/0.12
16/0.3/0.12
mW (V/mA)
500 (10/5)
500 (10/5)
AgCdO
AgCdO
12 - 24 - 110 - 120 - 230
12 - 24 - 110 - 120 - 230
12 - 24 - 125
12 - 24 - 125
1.2/0.5
1.2/0.5
Minimum switching load
Standard contact material
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/sens. DC
Operating range
V DC
VA (50 Hz)/W
AC
(0.8…1.1)UN
(0.8…1.1)UN
sens. DC
(0.8…1.5)UN
(0.8…1.5)UN
Holding voltage
AC/DC
0.8 UN / 0.4 UN
0.8 UN / 0.4 UN
Must drop-out voltage
AC/DC
0.2 UN / 0.1 UN
0.2 UN / 0.1 UN
Mechanical life
cycles
10 · 106
10 · 106
Electrical life at rated load AC1
cycles
100 · 10
100 · 103
ms
7/4 (AC) - 12/12 (DC)
7/4 (AC) - 12/12 (DC)
kV
6 (8 mm)
6 (8 mm)
Technical data
Operate/release time
Insulation between coil
and contacts (1.2/50 µs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
Approvals relay (according to type)
4
V AC
°C
3
1000
1000
–40…+70
–40…+70
IP 20
IP 20
III-2016, www.findernet.com
B
Type 48.61
-- 1 CO 16 A
-- Screw terminals
48 SERIES
Relay interface modules 10 A
48
SERIES
48.P8
2 CO relay interface modules,
15.8 mm wide
48.62
Ideal interface for PLC and electronic systems
Type 48.P8
-- 2 CO 10 A
-- Push-in terminals
Type 48.62
-- 2 CO 10 A
-- Screw terminals
B
• DC sensitive coils
• Supply status indication and EMC coil
• 2 CO 10 A
• Push-in terminals
suppression module as standard
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P8
Push-in terminal
• 2 CO 10 A
• Screw terminals
48.62
Screw terminal
48.62 / 82
48.62 / 82
For outline drawing see page 9
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated voltage/
Maximum switching voltage
A
V AC
2 CO (DPDT)
2 CO (DPDT)
10/20
10/20
250/400
250/400
Rated load AC1
VA
2500
2500
Rated load AC15 (230 V AC)
VA
500
500
Single phase motor rating (230 V AC)
kW
Breaking capacity DC1: 30/110/220 V
A
Minimum switching load
mW (V/mA)
Standard contact material
0.37
0.37
10/0.3/0.12
10/0.3/0.12
300 (5/5)
300 (5/5)
AgNi
AgNi
—
—
12 - 24 - 125
12 - 24 - 125
—/0.5
—/0.5
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/sens. DC
Operating range
V DC
VA (50 Hz)/W
AC
sens. DC
—
—
(0.8…1.5)UN
(0.8…1.5)UN
Holding voltage
AC/DC
—/0.4 UN
—/0.4 UN
Must drop-out voltage
AC/DC
—/0.1 UN
—/0.1 UN
Mechanical life
cycles
20 · 106
20 · 106
Electrical life at rated load AC1
cycles
100 · 10
100 · 103
ms
12/12 (DC)
12/12 (DC)
kV
6 (8 mm)
6 (8 mm)
Technical data
III-2016, www.findernet.com
Operate/release time
Insulation between coil
and contacts (1.2/50 µs)
Dielectric strength
between open contacts
Ambient temperature range
Protection category
V AC
°C
3
1000
1000
–40…+70
–40…+70
IP 20
IP 20
Approvals relay (according to type)
5
48 SERIES
Relay interface modules 8 - 10 - 16 A
48
SERIES
Ordering information
Example: 48 series, 35 mm rail (EN 60715) mount, Push-in terminal relay interface module, 2 CO 8 A contacts, 24 V sensitive DC coil, green LED + diode,
99.02 coil indication.
4 8 . P
B
C
D
5 . 7 . 0 2 4 . 0
0
5
0
Series
A: Contact material
0 = Standard AgNi for
48.P3/P5/P8/31/52/62
AgCdO, Standard
for 48.P6/61
1= AgNi, for 48.12
4 = AgSnO2, for 48.P6/P8/
61/62 only
5 = AgNi + Au, for
48.P3/P5/31/52 only
Type
Screw terminal
1 = 35 mm rail (EN 60715) mount,
forcibly guided contacts relay
3 = 35 mm rail (EN 60715) mount
5 = 35 mm rail (EN 60715) mount
6 = 35 mm rail (EN 60715) mount
Push-in terminal
P = 35 mm rail (EN 60715) mount
D: Special versions
0 = Standard
2 = Standard (for 48.12 only)
C: Options
0 = Standard (for 48.12 only)
5 = Standard for DC:
green LED + diode (polarity +A1)
6 = Standard for AC:
green LED + Varistor
B: Contact circuit
0 = CO (nPDT)
Type
Screw terminal
1 = for 48.31, 10 A
48.61, 16 A
2 = for 48.12 (DC only), 48.52, 8 A
48.62 (DC only), 10 A
Push-in terminal
3 = for 48.P3, 10 A
5 = for 48.P5, 8 A
6 = for 48.P6, 16 A
8 = for 48.P8 (DC only), 10 A
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Coil version
7 = Sensitive DC
8 = AC (50/60 Hz)
9 = DC (for 48.12 only)
Coil voltage
See coil specifications
Type
Coil version
A
B
C
D
48.12
DC
1
0
0
2
48.P3/P5/31/52
AC
0-5
0
6
0
48.P3/P5/31/52
Sensitive DC
0-5
0
5
0
48.P6/61
AC
0-4
0
6
0
48.P6/61
Sensitive DC
0-4
0
5
0
48.P8/62
Sensitive DC
0-4
0
5
0
Technical data
Insulation
Insulation according to EN 61810-1
48.12/31/61/P3/P6 48.52/P5
insulation rated voltage
rated impulse withstand voltage
V 250
48.12/31/61/62/P3/P6/P8
250
400
kV 4
4
4
pollution degree
3
2
2
overvoltage category
III
III
III
Insulation between coil and contacts (1.2/50 µs)
kV 6 (8 mm)
Dielectric strength between open contacts
V AC 1000; 1500 (48.12)
Dielectric strength between adjacent contacts
V AC 2000 (48.P5/52); 2500 (48.12/P6)
Conducted disturbance immunity
Burst (5…50)ns, 5 kHz, on A1 - A2
EN 61000-4-4
level 4 (4 kV)
Surge (1.2/50 µs) on A1 - A2 (differential mode)
EN 61000-4-5
level 3 (2 kV)
Other data
Bounce time: NO/NC
ms 2/5; 2/10 (48.12)
Vibration resistance (10…200)Hz: NO/NC
g 20/5 (for 1 pole)
Power lost to the environment
W 0.7
without contact current
with rated current
Wire strip length
Screw torque (only for 48.12/31/52/61/81)
Max. wire size
6
W 1.2 (48.12/31/P3)
15/3; 20/6 (48.12) for 2 pole
1.3 (48.52/P5)
1.2 (48.61/62/P6/P8)
mm 8
Nm 0.5
Screw terminal
solid cable
Push-in terminal
stranded cable solid cable
stranded cable
mm2 1 x 6 / 2 x 2.5
1 x 4 / 2 x 2.5
2 x (0.5…1.5)
2 x (0.5…1.5)
AWG 1 x 10 / 2 x 14
1 x 12 / 2 x 14
2 x (21…18)
2 x (21…18)
III-2016, www.findernet.com
B
A
48 SERIES
Relay interface modules 8 - 10 - 16 A
48
SERIES
Contact specification
F 48 - Electrical life (AC) v contact current
Types 48.P3/P6/31/61
F 48 - Electrical life (AC) v contact current
Types 48.P8/62
Cycles
Cycles
Resistive load - cosϕ = 1
Inductive load- cosϕ = 0.4
B
Resistive load - cosϕ = 1
Inductive load- cosϕ = 0.4
limit for 48.31
DC breaking current (A)
H 48 - Maximum DC1 breaking capacity
Types 48.P3/P5/P6/31/52/61
48.P6/61 current limit
48.P3/31 current limit
48.P5/52 current limit
2 contacts in series
single contact
DC voltage (V)
Resistive load - cosϕ = 1
Inductive load- cosϕ = 0.4
Cycles
Resistive load - cosϕ = 1
Inductive load- cosϕ = 0.4
F 48 - Electrical life (AC) v contact current
Type 48.12
H 48 - Maximum DC1 breaking capacity
Types 48.P8/62
DC breaking current (A)
Cycles
F 48 - Electrical life (AC) v contact current
Types 48.P5/52
2 contacts in series
single contact
DC voltage (V)
DC breaking current (A)
III-2016, www.findernet.com
H 48 - Maximum DC1 breaking capacity
Type 48.12
• When switching a resistive load (DC1) having voltage and current
DC voltage (V)
values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
7
48 SERIES
Relay interface modules 8 - 10 - 16 A
48
SERIES
Coil specifications
DC coil data (0.5 W sensitive)
Nominal
voltage
Coil
code
UN
V
B
12
AC coil data
Operating range
7.012
Umin*
Umax
V
V
8.8
24
7.024
17.5
125
7.125
91
Rated coil
consumption
I at UN
Nominal
voltage
UN
mA
V
12
Coil
code
Operating range
Umin
V
8.012
Umax
V
mA
18
41
36
22.2
24
8.024
19.2
188
4
110
8.110
88
121
10.1
120
8.120
96
132
11.8
230
8.230
184
253
7.0
* Umin = 0.8 UN for 48.61, 48.62, 48.P6, 48.P8
9.6
Rated coil
consumption
I at UN (50 Hz)
13.2
90.5
26.4
46
DC coil data, 2 pole relay - Type 48.12
Nominal
voltage
UN
Coil
code
Operating range
Umin
V
Umax
V
Resistance
R
Rated coil
consumption
I at UN
V
Ω
mA
12
9.012
9
14.4
205
58.5
24
9.024
18
28.8
820
29.3
R 48 - DC coil operating range v ambient temperature
48.P3/P5/31/52
48.P6/P8/61/62
R 48 - AC coil operating range v ambient temperature
1
1
48.P6/P8/61/62
48.P3/P5/31/52
2
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
2
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
R 48 - DC coil operating range v ambient temperature
Type 48.12
III-2016, www.findernet.com
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
8
48 SERIES
Relay interface modules 8 - 10 - 16 A
Combinations
Code
48.12
48.31
48.52
48
SERIES
Type of socket
Type of relay
Module
Retaining clip
95.05.0
50.12
—
095.71
95.03
40.31
99.02
095.01
95.05
40.52
99.02
095.01
48.61
95.05
40.61
99.02
095.01
48.62
95.05
44.62
99.02
095.01
48.P3
95.P3
40.31
99.02
095.91.3
48.P5
95.P5
40.52
99.02
095.91.3
48.P6
95.P5
40.61
99.02
095.91.3
48.P8
95.P5
44.62
99.02
095.91.3
B
Outline
drawing
64.5
25.9
17.5
17.5
25.5
35.4
78.6
21.6
15.8
32
48.31
48.52 / 48.61 / 48.62
Screw terminal
48.12
Screw terminal
III-2016, www.findernet.com
48.P3 48.P5 48.P6 48.P8
Push-in terminal
9
48 SERIES
Relay interface modules 8 - 10 - 16 A
48
SERIES
Accessories
8-way jumper link for type 48.P3/P5/P6/P8
097.58
Rated values
10 A - 250 V
2-way jumper link for type 48.P3/P5/P6/P8
097.52
Rated values
10 A - 250 V
2-way jumper link for type 48.P3/P5/P6/P8
097.42
Rated values
10 A - 250 V
Marker tag holder for type 48.P3/P5/P6/P8 and 48.12/31/52/61/62
097.00
097.58
B
097.52
097.42
P A
N
T E
PEAN
095.18
PEAN
O
O
T
EUR
EUR
097.00
8-way jumper link for screw terminal version
095.18 (blue)
Rated values
10 A - 250 V
Sheet of marker tags (CEMBRE'S Thermal transfer printers),
plastic, 48 tags, 6 x 12 mm
095.18.0 (black)
060.48
060.48
Sheet of marker tags (plotter printing), plastic, 72 tags, 6 x 12 mm
060.72
060.72
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
5 . 7 . 0 2 4 . 0
0
5
0
S P
A
A Standard packaging
B Blister packaging
SP Plastic retaining clip
10
III-2016, www.findernet.com
4 8 . P