Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8737 Multi-Conductor - Single-Pair Cable
For more Information
please call
1-800-Belden1
General Description:
22 AWG stranded (7x30) tinned copper conductors, PVC insulation, twisted pair, tinned copper spiral
wrapped shield (85% coverage), PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material Dia. (in.)
1
22
7x30
TC - Tinned Copper .030
Total Number of Conductors:
2
Insulation
Insulation Material:
Insulation Material
Dia. (in.)
PVC - Polyvinyl Chloride .060
Outer Shield
Outer Shield Material:
Type
Outer Shield Material Coverage (%)
Spiral Serve TC - Tinned Copper
85
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride
Overall Cable
Overall Nominal Diameter:
0.180 in.
Pair
Pair Color Code Chart:
Number Color
1
Black & Red
Mechanical Characteristics (Overall)
Operating Temperature Range:
-20°C To +80°C
UL Temperature Rating:
80°C (UL AWM Style 2095)
Bulk Cable Weight:
18 lbs/1000 ft.
Max. Recommended Pulling Tension:
20 lbs.
Min. Bend Radius/Minor Axis:
1.750 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CMG
CEC/C(UL) Specification:
CMG
AWM Specification:
UL Style 2095 (300 V 80°C)
EU Directive 2011/65/EU (ROHS II):
Yes
EU CE Mark:
Yes
EU Directive 2000/53/EC (ELV):
Yes
EU Directive 2002/95/EC (RoHS):
Yes
EU RoHS Compliance Date (mm/dd/yyyy):
04/01/2005
EU Directive 2002/96/EC (WEEE):
Yes
EU Directive 2003/11/EC (BFR):
Yes
CA Prop 65 (CJ for Wire & Cable):
Yes
Page 1 of 2
01-05-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8737 Multi-Conductor - Single-Pair Cable
CA Prop 65 (CJ for Wire & Cable):
Yes
MII Order #39 (China RoHS):
Yes
Flame Test
CSA Flame Test:
FT4
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
49
Nom. Inductance:
Inductance (µH/ft)
0.17
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
40
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
70
Nominal Velocity of Propagation:
VP (%)
66
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
16
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
11.7
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
Putup
Ship Weight
Color
8737 060U1000
1,000 FT
20.000 LB
CHROME
8737 060U500
500 FT
10.500 LB
CHROME
8737 0601000
1,000 FT
20.000 LB
CHROME
8737 060500
500 FT
10.000 LB
CHROME
8737 0605000
5,000 FT
100.000 LB
CHROME
Notes
Item Desc
1 PR#22 PVC SHLD PVC
2 #22 PVC SHLD PVC
C
1 PR#22 PVC SHLD PVC
1 PR#22 PVC SHLD PVC
C
1 PR #22 PVC SHLD PVC
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 1
Revision Date: 10-03-2012
© 2017 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 2 of 2
01-05-2017
很抱歉,暂时无法提供与“8737 060U1000”相匹配的价格&库存,您可以联系我们找货
免费人工找货