Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1031A Triad - 300V Power-Limited Tray Cable
For more Information
please call
1-800-Belden1
General Description:
16 AWG triads stranded (7x24) bare copper conductors, twisted triads, overall Beldfoil shield (100%
coverage), PVC insulation, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors # Triads AWG Stranding Conductor Material
1
1
16
7x24
BC - Bare Copper
Total Number of Conductors:
3
Insulation
Insulation Material:
Insulation Material
Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.016
Inner Shield
Inner Shield Color Code Chart:
Number Color
1
Black & Red & White and Numbered
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
18
7x26
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.037
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Nominal Diameter:
0.285 in.
Pair
Pair Lay Length & Direction:
Twists (twist/ft)
6
Mechanical Characteristics (Overall)
Operating Temperature Range:
-30°C To +105°C
Bulk Cable Weight:
58.300 lbs/1000 ft.
Max. Recommended Pulling Tension:
61 lbs.
Min. Bend Radius/Minor Axis:
1.140 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CMG, ITC-ER, PLTC-ER
CEC/C(UL) Specification:
CMG
AWM Specification:
UL Style 2464 (300 V 80°C)
EU Directive 2011/65/EU (ROHS II):
Yes
EU CE Mark:
Yes
Page 1 of 3
08-26-2016
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1031A Triad - 300V Power-Limited Tray Cable
EU Directive 2000/53/EC (ELV):
Yes
EU Directive 2002/95/EC (RoHS):
Yes
EU RoHS Compliance Date (mm/dd/yyyy):
04/01/2005
EU Directive 2002/96/EC (WEEE):
Yes
EU Directive 2003/11/EC (BFR):
Yes
CA Prop 65 (CJ for Wire & Cable):
Yes
MII Order #39 (China RoHS):
Yes
Flame Test
UL Flame Test:
UL1685 FT4 Loading
CSA Flame Test:
FT4
IEEE Flame Test:
1202
Suitability
Suitability - Burial:
Yes
Sunlight Resistance:
Yes
Plenum/Non-Plenum
Plenum (Y/N):
No
Surface Printing (Overall)
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/ft)
.156
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
54.1
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
97.3
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
3.7
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
4.9
Max. Operating Voltage - UL:
Voltage
300 V RMS
Notes (Overall)
Notes: Alternate color coding available upon request.
Put Ups and Colors:
Item #
Putup
Ship Weight
Color
Notes
Item Desc
1031A 0061000
1,000 FT
60.000 LB
BLUE, LIGHT
C
3 #16 PVC FS PVC
1031A 00610000
10,000 FT
600.000 LB
BLUE, LIGHT
C
TRANSFER REVIEW (20 TO 30)
1031A 0101000
1,000 FT
58.000 LB
BLACK
C
3 #16 PVC FS PVC
1031A 01010000
10,000 FT
600.000 LB
BLACK
CZ
3 #16 PVC FS PVC
1031A 0105000
5,000 FT
295.000 LB
BLACK
CZ
3 #16 PVC FS PVC
Notes:
C = CRATE REEL PUT-UP.
Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
Revision Number: 3
Revision Date: 03-15-2016
© 2016 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Page 2 of 3
08-26-2016
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1031A Triad - 300V Power-Limited Tray Cable
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 3 of 3
08-26-2016
很抱歉,暂时无法提供与“1031A 0061000”相匹配的价格&库存,您可以联系我们找货