Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1701A Multi-Conductor - Enhanced Category 5E Bonded-Pair Cable
For more Information
please call
1-800-Belden1
General Description:
CAT5e+ (350MHz), 4-Bonded-Pairs, U/UTP-Unshielded, Plenum-CMP, Premise Horizontal Cable, 24
AWG Solid Bare Copper Conductors, FEP insulation, Ripcord, Flamarrest® PVC jacket.
Usage (Overall)
Suitable Applications:
Premise Horizontal Cable, Gigabit Ethernet, POE, POE+,100BaseTX, 100BaseVG ANYLAN, 155ATM,
622ATM, NTSC/PAL Component or Composite Video, AES/EBU, Digital Video, RS-422, Noisy
Environments
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
4
24
Solid
BC - Bare Copper
Total Number of Conductors:
8
Insulation
Insulation Material:
Insulation Material
FEP - Fluorinated Ethylene Propylene
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Trade Name Outer Jacket Material
Flamarrest®
LS PVC - Low Smoke Polyvinyl Chloride
Outer Jacket Diameter:
Nom. Dia. (in.)
0.195
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Nominal Diameter:
0.195 in.
Pair
Pair Color Code Chart:
Number Color
1
White/Blue Stripe & Blue
2
White/Orange Stripe & Orange
3
White/Green Stripe & Green
4
White/Brown Stripe & Brown
Mechanical Characteristics (Overall)
Storage Temperature Range:
-20°C To +75°C
Installation Temperature Range:
+5°C To +50°C
Operating Temperature Range:
-20°C To +75°C
Bulk Cable Weight:
22 lbs/1000 ft.
Max. Recommended Pulling Tension:
40 lbs.
Min. Bend Radius/Minor Axis:
0.500 in.
Min. Bend/Installation:
2 in.
Page 1 of 4
02-01-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1701A Multi-Conductor - Enhanced Category 5E Bonded-Pair Cable
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CMP
CEC/C(UL) Specification:
CMP
EU Directive 2011/65/EU (ROHS II):
Yes
EU CE Mark:
Yes
EU Directive 2000/53/EC (ELV):
Yes
EU Directive 2002/95/EC (RoHS):
Yes
EU RoHS Compliance Date (mm/dd/yyyy):
01/01/2005
EU Directive 2002/96/EC (WEEE):
Yes
EU Directive 2003/11/EC (BFR):
Yes
CA Prop 65 (CJ for Wire & Cable):
Yes
MII Order #39 (China RoHS):
Yes
Telecommunications Standards:
Category 5e - TIA 568.C.2
Other Specification:
NEMA WC-63.1 Category 5e, UL Verified to Category 5e
Applicable Patents:
Country
www.belden.com/p
Flame Test
UL Flame Test:
NFPA 262
C(UL) Flame Test:
FT6
CSA Flame Test:
FT6
Suitability
Suitability - Indoor:
Yes
Suitability - Outdoor:
No
Suitability - Aerial:
No
Suitability - Burial:
No
Sunlight Resistance:
No - Indoor
Plenum/Non-Plenum
Plenum (Y/N):
Yes
Non-Plenum Number:
1700A
Electrical Characteristics (Overall)
Nom. Mutual Capacitance:
Capacitance (pF/ft)
15
Maximum Capacitance Unbalance (pF/100 m):
66
Nominal Velocity of Propagation:
VP (%)
72
Maximum Delay:
Delay (ns/100 m)
510
Max. Delay Skew:
Delay Skew (ns/100 m)
25
Maximum Conductor DC Resistance:
DCR @ 20°C (Ohm/100 m)
9
Max. Operating Voltage - Non-UL:
Voltage
80 V RMS
Maximum DCR Unbalanced:
DCR Unbalance @ 20°C (%)
Page 2 of 4
02-01-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1701A Multi-Conductor - Enhanced Category 5E Bonded-Pair Cable
3
Electrical Characteristics-Premise (Overall)
Premise Cable Electrical Table 1:
Freq. (MHz) Max. Attenuation (dB/100 m) Min. PSNEXT (dB) Min. PSACR (dB) Min RL (dB)
1
2.000
69.3
67.3
20.000
4
4.000
60.3
56.3
23.000
8
5.700
55.8
50.1
24.500
10
6.400
54.3
47.9
25.000
16
8.100
51.2
43.1
25.000
20
9.100
49.8
40.7
25.000
25
10.200
48.3
38.2
25.000
31.25
11.400
46.9
35.5
25.000
62.5
16.400
42.4
26.0
25.000
100
21.000
39.3
18.3
25.000
155
26.600
36.4
9.8
19.000
200
30.400
34.8
4.4
19.000
250
34.400
32.3
>0
18.000
300
38.000
28.1
18.000
350
41.400
27.1
17.000
400
44.500
26.3
17.000
450
47.600
25.5
17.000
Premise Cable Electrical Table 2:
Freq. (MHz) Input (Unfitted) Imp. (Ohms) Fitted Impedance Min. PSACRF (dB)
1
100 ± 12
105 ± 10
65.8
4
100 ± 12
100 ± 10
53.8
8
100 ± 12
100 ± 10
47.7
10
100 ± 12
100 ± 10
45.8
16
100 ± 12
100 ± 10
41.7
20
100 ± 12
100 ± 10
39.8
25
100 ± 15
100 ± 10
37.8
31.25
100 ± 15
100 ± 10
35.9
62.5
100 ± 15
100 ± 10
29.9
100
100 ± 15
100 ± 10
25.8
155
100 ± 18
100 ± 10
22.0
200
100 ± 20
100 ± 10
19.8
250
100 ± 20
100 ± 10
17.8
300
100 ± 20
100 ± 10
14.3
350
100 ± 22
100 ± 10
12.9
400
100 ± 22
100 ± 10
11.8
450
100 ± 22
100 ± 10
10.7
Premise Cable Electrical Table 4:
Frequency (MHz) Min. TCL (dB) Min. ELTCTL (dB)
1.000
40.000
35.000
4.000
40.000
23.000
8.000
40.000
16.900
10.000
40.000
15.000
16.000
38.000
10.900
20.000
37.000
9.000
25.000
36.000
7.000
31.250
35.100
62.500
32.000
100.000
30.000
155.000
28.100
200.000
27.000
250.000
26.000
Notes (Overall)
Notes: Belden IBDN. Jacket sequentially marked at 2 ft. intervals. Third party verified to ANSI/TIA-568-C.2, Category 5e. Values above 350 MHz are for Engineering Information
Only.
Put Ups and Colors:
Item #
Putup
Ship Weight
Color
1701A B02U1000
1,000 FT
23.000 LB
PURPLE
Notes
1701A B021000
1,000 FT
24.000 LB
PURPLE
1701A D15U1000
1,000 FT
23.000 LB
BLUE
Item Desc
CAT5E+ 4PRB U/UTP CMP BOX
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
Page 3 of 4
02-01-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
1701A Multi-Conductor - Enhanced Category 5E Bonded-Pair Cable
1701A D151000
1,000 FT
24.000 LB
BLUE
C
CAT5E+ 4PRB U/UTP CMP REEL
1701A D153000
3,000 FT
69.000 LB
BLUE
C
CAT5E+ 4PRB U/UTP CMP REEL
1701A 002U1000
1,000 FT
23.000 LB
RED
1701A 0021000
1,000 FT
24.000 LB
RED
1701A 003U1000
1,000 FT
23.000 LB
ORANGE
1701A 0031000
1,000 FT
24.000 LB
ORANGE
1701A 004U1000
1,000 FT
23.000 LB
YELLOW
1701A 0041000
1,000 FT
24.000 LB
YELLOW
1701A 005U1000
1,000 FT
23.000 LB
GREEN, DARK
1701A 0051000
1,000 FT
24.000 LB
GREEN, DARK
1701A 008U1000
1,000 FT
23.000 LB
GRAY
1701A 0081000
1,000 FT
24.000 LB
GRAY
1701A 009U1000
1,000 FT
23.000 LB
WHITE
1701A 0091000
1,000 FT
24.000 LB
WHITE
C
CAT5E+ 4PRB U/UTP CMP REEL
1701A 010U1000
1,000 FT
23.000 LB
BLACK
C
CAT5E+ 4PRB U/UTP CMP BOX
1701A 0101000
1,000 FT
24.000 LB
BLACK
CAT5E+ 4PRB U/UTP CMP REEL
1701A 012A1001
1,000 FT
26.000 LB
PINK
CAT5E+ 4PRB U/UTP CMP RIB
1701A 877U1000
1,000 FT
23.000 LB
NATURAL
1701A 8771000
1,000 FT
24.000 LB
NATURAL
C
CAT5E+ 4PRB U/UTP CMP REEL
1701A 8773000
3,000 FT
69.000 LB
NATURAL
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
C
CAT5E+ 4PRB U/UTP CMP REEL
CAT5E+ 4PRB U/UTP CMP BOX
CAT5E+ 4PRB U/UTP CMP BOX
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 12
Revision Date: 06-09-2016
© 2017 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 4 of 4
02-01-2017