Thermal-Magnetic Circuit Breaker 201/-WA
Description
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Featuring a narrow profile housing, recessed terminals,
standard EN rail mounting, and precision CBE performance.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Process control systems, instrumentation, rail vehicles.
201-...
standard type
Ordering information
10 A
ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current
rating (A)
Internal resistance (Ω)
201
201-WA
Current
rating (A)
Internal resistance (Ω)
201
201-WA
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
447
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
3
4
5
6
7
8
10
12
14
15
16
0.19
0.090
0.061
0.041
0.034
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
211
48
12.4
5.7
3.1
2.0
1.32
0.76
0.49
0.21
0.101
0.078
0.054
0.035
0.025
< 0.02
< 0.02
< 0.02
< 0.02
For further details please see chapter: Technical Information
Voltage rating
AC 240 V (50/60 Hz); DC 65 V
(UL: AC 250 V, DC 80 V)
Current rating range
201: 0.05...16 A
201-WA: 0.05...10 A
Typical life
5,000 operations at 1 x IN, inductive
5,000 operations at 2 x IN, resistive
Ambient temperature
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664 A) withstand voltage
degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
201
201-WA
0.05...0.8 A
1...2 A
2.5...16 A
Interrupting capacity
(UL 1077)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Approvals
Mass
Authority
VDE (EN 60 934)
CSA, UL
05/06(020505)
2
Technical data
Type No.
201
single pole, rail mounted version
201-WA low-resistance version
Option
2705 fitted with adapter X 200 409 01
Current ratings
0.05...16 A (type 201)
0.05...10 A (type 201-WA)
201 - .. - .... -
201-WA-...
low-resistance type
Voltage ratings
AC 240 V, DC 65 V
AC 250 V, DC 80 V
Current ratings
0.05...16 A
0.05...16 A
www.e-t-a.com
0.05...0.2 A
0.3...2 A
2.5...10 A
self-limiting
200 A
400 A
IN
UN
0.05...16 A
AC 250 V
1,000 A
0.05...16 A
DC 80 V
1,000 A
operating area IP40
terminal area IP20
5 g (57-500 Hz), ±0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms)
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-3, test Ca
approx. 60 g
Thermal-Magnetic Circuit Breaker 201/-WA
Installation drawing
5
.197
45
1.77
ø8.5
.335
11.5
.453
black
ON
OFF
11
.433
Dimensions
43
1.69
53
2.09
white
80
3.15
cable entry
cable entry
mounting area
6.5
.256
7.5
.295
2
4.8
.189
12-14
.472-.551
operating area
(reinforced insulation)
conductor cross
section max.
0.5 - 10 mm2
(AWG 20-AWG 8)
rigid conductor
0.5 - 6 mm2
(AWG 20-AWG 10)
flexible conductor
tightening torque
max. 0.8 Nm
12.5
.492
symmetrical rail EN 50022-35x7.5
current rating in A
slot for fitting labels from
2
Weidmüller
type dekafix
Phoenix
type ZBFM5 or ZB8
Phillips screw, size 2 to EN ISO 4757
Internal connection diagram
This is a metric design and millimeter dimensions take precedence ( mm )
inch
line 1
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section 9
– Technical information.
Ambient temperature °F
-22 -4
+14 +32 +73.4 +104 +122 +140
°C
-30 -20 -10 0
+23 +40 +50 +60
Derating factor
0.76 0.79 0.83 0.88 1
1.08 1.16 1.24
I>
2
Typical time/current characteristics
AC/DC 1)
Type 201 0.05...7 A
Type 201 8...16 A
1000
100
100
100
10
1
Trip time in seconds
1000
Trip time in seconds
1000
Trip time in seconds
10000
10
1
0.1
0.01
0.01
0.01
0.001
+60 °C
+140 °F
4 6 8 10
20
40 60 80100
… times rated current
+23 °C
+73.4 °F
DC/AC 2)
1
0.1
2
0.05...10 A
10
0.1
1
2)
Type 201-WA
10000
0.001
1)
AC/DC 1)
10000
0.001
1
2
4 6 8 10
20
40 60 80100
… times rated current
1
2
4 6 8 10 20
40 60 80100
… times rated current
-30 °C
-22 °F
Magnetic tripping currents are increased by 20% on DC supplies.
Magnetic tripping currents are decreased by 20% on AC supplies.
120
www.e-t-a.com
05/06(020505)
Thermal-Magnetic Circuit Breaker 201/-WA
Accessories
20
.787
Adapter for EN rail 50035-G32 specified as a separate item
X 200 409 01
Adapter X 200 409 01
G profile
EN 50035-G32
2
Connector bus links -K10
X 210 589 01/2.5 mm2, (AWG 14) (black) up to 20 A max. load
X 210 589 02/1.5 mm2, (AWG 16) (brown) up to 13 A max. load
ø2.5
.099
~70
~2.76
50 pin lugs to DIN 46230
tinned copper
Bus bar
X 221 498 01 (17-way)
up to 70 A max. load
16 x 12.5 = 200
16 x .492 = 7.87
12.5
.492
2.5
.099
1.3
207
8.15
14
.551
IEC 664 500 V/70 A (40 °C) CE
E-T-A® GERMANY
29
1.14
.051
3.5
.138
9.7
.382
2.5
.098
M5
13
.512
17
.669
5.2
.205
1.3
.051
22
.866
11.3
.445
Supply terminal for bus bar
X 221 496 01
up to 70 A max. load
4.6
.181
conductor size max. 10 mm2 (AWG 8)
rigid, solid or stranded
14.5
.571
This is a metric design and millimeter dimensions take precedence ( mm )
inch
05/06(020505)
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
www.e-t-a.com