High Performance Thermal Circuit Breaker 4130-...
Description
Single pole high performance thermal circuit breaker, with push-toreset tease free, trip-free snap action mechanism (R-type TO CBE to
EN 60934). Designed for threadneck panel mounting and for
applications with a high fault current switching requirement.
Approved to CBE standard EN 60934 (IEC 60934).
1
Typical applications
Motors, transformers, solenoids, battery chargers, power supplies,
appliances, machinery, extra low voltage systems.
4130-...
Ordering information
Technical data
Type No.
4130 single pole thermal circuit breaker
Mounting
G threadneck panel mounting
Threadneck design
2 M 12x1, knurled nut (bulk shipped)
4 M 12x1, hex nut and knurled nut (bulk shipped)
Number of poles
1 single pole, thermally protected
Actuator configuration
1 black push button
Terminal design
K4 terminal M6x8
screw and washer bulk shipped
Characteristic curve
M1 medium delay
Current ratings
20... 70 A
4130 - G 2
1
1 - K4 M1 - 20 A
Voltage rating
Current rating range
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664)
(reinforced insulation in the mounting area)
Dielectric strength
operating area
Insulation resistance
Interrupting capacity Icn
Interrupting capacity
(UL 1077)
ordering example
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Standard current ratings and typical internal resistance values
Current
rating (A)
20
25
30
35
Internal
resistance (Ω)
< 0.02
< 0.02
< 0.02
< 0.02
Current
rating (A)
40
50
60
70
Internal
resistance (Ω)
< 0.01
< 0.01
< 0.01
< 0.01
AC 240 V; DC 50 V
20... 70 A
300 operations at 2 x IN (DC 50 V)
500 operations at 2 x IN (DC 28 V)
-30...+60 °C (-22...+140 °F)
rated impulse
pollution
withstand voltage
degree
2.5 kV
2
Shock
Corrosion
Humidity
Mass
test voltage
AC 3,000 V
> 100 MΩ (DC 500 V)
800 A
IN
UN
20...70 A
AC 240 V
1,000 A
20...60 A
AC 120 V
3,500 A
70 A
AC 120 V
2,000 A
20...50 A
DC 50 V
3,500 A
60...70 A
DC 50 V
2,000 A
operating area IP40
terminal area IP00
8 g (57-500 Hz) ±0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms)
to IEC 60068-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-3, test Ca
approx. 55 g
Approvals
Authority
VDE (EN 60934)
UL
Issue G
Voltage ratings
AC 240 V; DC 50 V
AC 240 V; DC 50 V
☎
Current ratings
20...70 A
20...70 A
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com
101
High Performance Thermal Circuit Breaker 4130-...
Typical time/current characteristics
ON
ø6.6
.260
23 °C
-30 °C
0.6±0.2
.024±.008
Trip time in seconds
10.3
.406
1000
LINE
64
2.52
50
1.97
1
60 °C
10000
tightening torque max. 1.5 Nm
M12x1
black
23.8±0.5
.937±.020
17.2±0.5
.677±.020
OFF
Dimensions
I
10
2
13.5
.531
22.3
.878
screw M6x8 with washer
tightening torque max. 2.5 Nm
1
0,1
11.5 -0.1
.453 -.004
32
1.26
12
.472
17
.669
0,8 1
mounting hole
18
.709
D-shaped threadneck
12.2 -0.1
.480 -.004
max. 3.5
max .138
100
3 4 5 6 8 10
... times rated current
40
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also
section 9 – Technical information.
Ambient temperature °F -22 -4
+14 +32 +73.4 +104 +122 +140
°C -30 -20 -10 0
+23 +40 +50 +60
Derating factor
0.68 0.76 0.84 0.92 1
1.08 1.16 1.24
Hex nut with splash cover, black
X 201 296 01 without O ring (IP64)
X 200 801 03 with O ring (IP66)
Hex nut with splash cover,
transparent
X 200 801 08 with O ring (IP66)
LINE
5
.197
operating area
Water splash cover,
transparent with knurled
nut and O ring (IP64)
X 210 663 01
M12x1
M12x1
2
Separate hardware
Hex nut Y 300 116 02
30
1.18
20
Accessories
Intstallation drawing
I
2
6
.236
Knurled nut
Y 302 065 01
mounting area
M12x1
Internal connection diagram
SW14
.551
M12x1
2.5
.098
ø17
.669
3.2
.126
0.5 x 45°
.020 x 45°
line 1
This is a metric design and millimeter dimensions take precedence ( mm )
inch
2
102
☎
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com