EU2B Series: 30mm Hazardous Location Switches
EC2B Series: Hazardous Location Control Stations
PRODUCT DESCRIPTION
Complying with UL, IECEX, and ATEX
Directives for hazardous environments,
new 30mm EU2B Hazardous Location
Switches and EC2B Hazardous Location
Control Stations provide increased safety
for your applications.
Control Unit Options:
• Pushbuttons
• Pilot Lights
• Selector Switches
• Key Selector Switches
STANDARDS COMPLIANCE
Switches
Pilot Lights
Class I, Zone 1, Ex de IIC T6 Gb
Class I, Div 2, Groups A, B, C and D
Class I, Zone 1 AEx d e IIC T6 Gb
Class I Div 2, Groups A, B, C and D
Class I, Zone 1, Ex de IIB T6 Gb Class I, Zone 1, Ex de IIC T6 Gb
Class I, Div 2, Groups C and D Class I, Div 2, Groups A, B, C and D
UL
c-UL
II2G Ex de IIC
ATEX
II2D tD A21 IP65
ECEx PTB 15.0006U
IECEx PTB 15.0007U
IECEX
Meters
Control Boxes
II2G Ex de IIC Gb Ex d e IIC T6 Gb
II2D Ex tb IIIC Db Ex tb IIIC T80ºC Db
(dust)
IP65
Ex de IIC T6 Gb
Ex tb IIIC T80ºC Db
(dust)
ATEX
PTB 08 ATEX 1053 U
PTB 08 ATEX 1003 U
PTB 08 ATEX 1048
Standards
• Custom-configured stations
• Open control boxes
• Mounting holes for up to 18 control units
• UL Type 4X rated
• Up to 3 contact blocks
Mark
• Selector switches available with lever or
key
• Selector switches available with
overlapping contacts
UL60079-0
UL60079-1
UL60079-7
• Exposed and finger-safe (IP20) screw
terminals available
CAN/CSA C22.2 No. 60079-0
CAN/CSA C22.2 No. 60079-1
CAN/CSA C22.2 No. 60079-7
EN60079-0 EN60079-1
EN60079-7 EN60079-31
• Corrosion resistant stainless steel
enclosure (SUS304)
• Melamine coating
• NPT and Metric reducer options
IEC60079-0 IEC60079-1
IEC60079-7 IEC60079-31
Emergency
Stop Switches
• Pre-configured stations
• Applicable in explosive gas atmospheres
(AEx de IIC T6 Gb)
EN60947-5-1
Pushbuttons
Selector
Switches
Key Selector
Switches
Pilot Lights
Meters
(EU2B-YM)
Control Station Options:
• Class I, Zone 1/Division 2
IECEx
IECEx PTB 15.0006U
IECEx PTB 15.0007U
IECEx PTB 15.0032
APPLICABLE STANDARDS
Control Units
• Meters
KEY FEATURES
CERTIFICATE NUMBERS
UL/c-UL
E347230
• Emergency Stop Switches
EN60947-5-5
1
Pilot Lights
SPECIFICATIONS
Rated Insulation Voltage (Ui)
General Specifications
Rated Operating Voltage (Ue)
IP65 (IEC60529), Type 4X
100 MΩ minimum (500V DC megger)
−20 to +50°C (no freezing)
45 to 85% (no condensation)
2,000m Maximum
3
100-m/s²
Operating Extremes
Emergency Stop Switch:
150-m/s² (without Meter)
Damage Limits
1000-m/s²
5 to 55-Hz, amplitude 0.5 mm
Emergency Stop Switch:
Operating Extremes
5 to 500-Hz, amplitude 0.35-mm, acceleration
50-m/s² (without Meter)
30Hz, amplitude 1.5-mm
Emergency Stop Switch:
Damage Limits
5 to 500-Hz, amplitude 0.35-mm, acceleration
50-m/s²
Insulation Resistance
Operating Temperature
Operating Humidity
Altitude
Pollution Degree
Shock Resistance
Vibration Resistance
Insulation Resistance
Frequency
Impulse Withstand Voltage (Uimp)
Insulation Resistance
Short-Circuit Protection
Conditional Short-Circuit Current
Pushbutton
Selector Switch
Mechanical Life
Key Selector Switch
Emergency Stop Switch
Pushbutton
Selector Switch
Electrical Life
Key Selector Switch
Emergency Stop Switch
Minimum Operator
Stroke Required for
Emergency Stop Switch
Direct Opening Action
Meters
Insulation Resistance
Rated Operating Voltage (Ue)
Resistive Load (AC12)
Inductive Load (AC15)
Resistive Load (DC12)
120V
10A*
6A
2.2A
1.1A
240V
6A
3A
1.1A
0.55A
Inductive Load (DC13)
Note: Up to 2 contacts (per control unit): 10A
3 contacts (per control unit): 9A
Minimum applicable load: 3V AC/DC, 5mA
Applicable operating locations may vary according to operating conditions and load types.
A600
10
6.00
240 Volt
30
Operation
Impulse Withstand Voltage (Uimp)
Input
Power Consumption
Degree of protection
IP65 (IEC60529), Type 4X
Housing Material
Stainless steel (SUS304)
Insulation Resistance
Melamine
1-column: Outside coating
2-, 3-, 4-column: Inside and outside coating
600V
(with pilot light or ET2A-8PE screw terminal block: 500V)
Meter AC input: 300V
Meter DC input: 150V
100 MΩ minimum (500V DC megger)
Operating Temperature
−20 to +50°C (no freezing)
Operating Humidity
45 to 85% (no condensation)
Altitude
2000m maximum
Standard Coating
Rated Insulation
Voltage
500V
2.8A
1.4A
—
—
480 Volt
600 Volt
3.00
15
1.5
12
1.2
Agency Approvals
UL/c-UL, IECEx/ATEX certified
Applicable Enclosure
All enclosures expect for
6 Control Units x 4 Column
Wall Mount
Mounting Style
Pilot Light
Yes1
Pushbutton
Yes
Emergency Pushbutton
Yes
Selector Switch
Yes
Key Selector Switch
Yes
Meter
Yes
Reducer Screw
600 Volt
NPT Thread (standard)
Metric Thread
Make Break Make Break Make Break Make Break Make Break
60
Measurement
Control Boxes
Maximum
Volt-Amperes
Maximum current, Amperes
120 Volt
Power Consumption
Consumption Current
Note: Use a commercially available CT (current transformer) for all AC ammeters, and install the CT in a
non-hazardous location.
7200 720
Degree of Protection
IP65, TYPE4X (UL)
Grounding Terminal Screw Material
Stainless Steel
Applicable
Wire
Contact
Rating Code
Designation
Thermal
Continuous
Test
Current
Amperes
Moving core
4kV
1VA
5A, 10A, 30A, 50A, etc
1A, 5A
3 times, etc
150V
Moving coil
2.5kV
0 to10V DC, 4 to 20mA, etc.
0.15W
1mA
Impulse Withstand Voltage (Uimp)
Rated Insulation Voltage (Ui)
Control Unit
Rated Thermal Current (Ith)
DC
Operation
Extended Memory
Contact Rating (Switches)
Rated Operating
Current (Ie)
300V
Input (CT Ratio)
Maximum Operator
Emergency Stop Switch 9.0mm
Stroke
Note: Contacts will bounce during operation of pushbuttons and selector switches (reference value: 20ms). Be sure to take contact bounce time into consideration when designing a control circuit.
AC
50/60Hz
Rated Insulation Voltage (Ui)
7.0mm
600V
10A*
24V
10A*
10A*
8A
4A
2.5
100 MΩ minimum (500V DC megger)
Accuracy Class
600V
50mΩ maximum (initial value)
6kV
100MΩ minimum (500V DC megger)
250V/10A fuse
(Type aM IEC60269-1/IEC60269-2)
1,000A
1,000,000 operations minimum
500,000 operations minimum
500,000 operations minimum
50,000 operations minimum
250,000 (switching frequency 1800 operations/hr)
250,000 (switching frequency 900 operations/hr)
250,000 (switching frequency 900 operations/hr)
50,000 (switching frequency 900 operations/hr)
Rated Insulation Voltage (Ui)
Transformer
500V
6V, 12V, 24V AC/DC
120V, 230V, 240V, 380V, 480V AC
4kV
100 MΩ minimum (500V DC)
50/60Hz
0.3W
1.5VA
Approx. 40,000 hours
Life (reference value)
Note: Because the built-in LED lamp is a high-brightness version, the lamp may light dimly due to induction
even when power is off.
DC ammeter
Contact Resistance
Full Voltage
Power Consumption (approx.)
Switches
Rated Insulation Voltage
Transformer
Impulse Withstand Voltage (Uimp)
AC ammeter
Degree of Protection
Voltage
Stranded Wire (mm2)
1.5 to 2.5
Solid Wire (mm2)
1.2 to 1.6
Solid/Stranded Wire (AWG)
16-14
1: c-UL explosion protection is different when pilot light is installed.
2
SWITCHES (CONTROL UNITS)
Pushbuttons
Emergency Stop Switches
Pilot Lights
Selector Switches
Pushbuttons
Key Selector Switches
Meters
EU2B - YM 5 3 A 10 F R
EU2B - YB1 11 F S D
Operator (style / function)
Button color
Contact arrangement
B1 : Flush pushbutton / Momentary
Blank: Red, Green, Black,
10
:
1NO
01
:
1NC
B2 : Extended pushbutton / Momentary
and White included
20
:
2NO
02
:
2NC
Y : Yellow S : Blue
B3 : Mushroom pushbutton / Momentary
30 : 3NO
03 : 3NC
Terminals
11 : 1NO-1NC
12 : 1NO-2NC F : Finger-safe terminal (IP20)
C : Exposed screw terminal
21 : 2NO-1NC
Part Number
EU2B-YB110➃➀–D
EU2B-YB101➃➀–D
EU2B-YB111➃➀–D
EU2B-YB120➃➀–D
EU2B-YB102➃➀–D
EU2B-YB121➃➀–D
EU2B-YB112➃➀–D
EU2B-YB130➃➀–D
EU2B-YB103➃➀–D
EU2B-YB210➃➀–D
EU2B-YB201➃➀–D
EU2B-YB211➃➀–D
EU2B-YB220➃➀–D
EU2B-YB202➃➀–D
EU2B-YB221➃➀–D
EU2B-YB212➃➀–D
EU2B-YB230➃➀–D
EU2B-YB203➃➀–D
EU2B-YB310➃➀–D
EU2B-YB301➃➀–D
EU2B-YB311➃➀–D
EU2B-YB320➃➀–D
EU2B-YB302➃➀–D
EU2B-YB321➃➀–D
EU2B-YB312➃➀–D
EU2B-YB330➃➀–D
EU2B-YB303➃➀–D
Style and
Function
Flush
Momentary
Extended
Momentary
Mushroom
Momentary
Contact
Arrangement
1NO
1NC
1NO-1NC
2NO
2NC
2NO-1NC
1NO-2NC
3NO
3NC
1NO
1NC
1NO-1NC
2NO
2NC
2NO-1NC
1NO-2NC
3NO
3NC
1NO
1NC
1NO-1NC
2NO
2NC
2NO-1NC
1NO-2NC
3NO
3NC
Weight
(Approx.)
Function
Set pointer
M : Meter
blank : non -R : with set pointer
Input current
1 : 1A 5 : 5A
Terminals
Specification of overload scale
F : Finger-safe terminal (IP20)
3: 3 times 2 : 2 times 5 : 5 times N:Non
C : Exposed screw terminal
Type of meter
A : AC ammeter Measuring range
Direct measuring 1 : 1A 5 : 5A
For current transformers: 10 : 10A 15 : 15A 20 : 20A 30:30A 50:50A
60 : 60A 75 : 75A 100:100A 150:150A
➀ Button Color
68g
92g
➀ Blank - supplied with
red, green, black, and white
buttons
116g
For yellow or blue buttons,
specify Y (yellow) or S
(blue).
EU2B - YM 010 VD F-PER-R
Input
70g
94g
118g
76g
101g
Specify a button color code
in place of ➀ in the part
number
B : black
G : green
R : red
S : blue
W : white
Y : yellow
AC
input
meter
(ammeter)
125g
Emergency Stop Switches
EU2B - YBV3 11 F R
Operator (style / function)
BV3 : 40mm mushroom/push, pull or
twist release
Contact arrangement
01 : 1NC
11 : 1NO-1NC
02 : 2NC
03 : 3NC
12 : 1NO-2NC
Operator
Contact
Arrangement
EU2B-YBV301➃R
1NC
EU2B-YBV311➃R
1NO-1NC
EU2B-YBV302➃R
ø40 Mushroom
2NC
EU2B-YBV312➃R
1NO-2NC
EU2B-YBV303➃R
3NC
DC
input
meter
Button color
R : Red
Terminals
F : Finger-safe terminal (IP20)
C : Exposed screw terminal
Weight
(Approx.)
Description
Part Number
EU2B-YM53A5➃
Capacity: 5A
Expansion scale: x3
EU2B-YM53A10➃
Capacity:10/5A
Expansion scale: x3
EU2B-YM13A10➃
Capacity:10/1A
Expansion scale: x3
EU2B-YM53A15➃
Capacity:15/5A
Expansion scale: x3
EU2B-YM13A15➃
Capacity:15/1A
Expansion scale: x3
EU2B-YM13A20➃
Capacity:20/1A
Expansion scale: x3
EU2B-YM53A30➃
Capacity:30/5A
Expansion scale: x3
EU2B-YM13A30➃
Capacity:30/1A
Expansion scale: x3
EU2B-YM53A50➃
Capacity:50/5A
Expansion scale: x3
EU2B-YM53A60➃
Capacity:60/5A
Expansion scale: x3
EU2B-YM53A75➃
Capacity:75/5A
Expansion scale: x3
EU2B-YM53A100➃
Capacity:100/5A
Expansion scale: x3
EU2B-YM53A150➃
Capacity:150/5A
Expansion scale: x3
EU2B-YM010VD➃-PER
0-10V DC Input
Scale: 0 to 100%
EU2B-YM010VD➃-60HZ
0-10V DC Input
Scale: 0 to 60Hz
EU2B-YM001MD➃-PER
0-1mA DC Input
Scale: 0 to 100%
EU2B-YM001MD➃-60HZ
0-1mA DC Input
Scale: 0 to 60Hz
EU2B-YM001MD➃-80HZ
0-1mA DC Input
Scale: 0 to 80Hz
EU2B-YM420MD➃-PER
4-20mA DC Input
Scale: 0 to 100%
EU2B-YM420MD➃-60HZ
4-20mA DC Input
Scale: 0 to 60Hz
Weight
(approx.)
270g
Specify a terminal style in place of ➃ in the part number: F (Finger-safe terminal), C (Exposed
screw terminal)
Button Color
96g
120g
Set pointer
blank : non -R : with set pointer
Specification of scale
-PER : 0~100%
-60HZ : 0~60Hz
-80HZ : 0~80Hz
Function
M : Meter
Input voltage or current
Type of meter
010 : 0-10V
001 : 0-1mA
VD : DC voltmeter
420 : 4-20mA etc.
MD : DC ammeter
Terminals
F : Finger-safe terminal (IP20)
C : Exposed screw terminal
Note: ➀ Button Color. Specify a contact terminal style in place of ➃ in the part number: F (Finger-safe
terminal), C (Exposed screw terminal)
Part Number
Meters
R : Red
144g
Specify a terminal style in place of ➃ in the part number: F (Finger-safe terminal), C (Exposed screw
terminal)
3
Pilot Lights
Part Number
Operating
Voltage
Type
EU2B-YL1126➃D➀
120V AC
EU2B-YL1236➃D➀
230V AC
Transformer
EU2B-YL1246➃D➀
380V AC
EU2B-YL1486➃D➀
480V AC
EU2B-YL166➃D➀
6V AC/DC
Full Voltage
➀ Illumination
Color Code
EU2B - YL1 22 F D R
R : red
G : green
A : amber
Y : yellow
PW : white
S : blue
150g
240V AC
EU2B-YL1386➃D➀
EU2B-YL111➃D➀
Weight
(Approx.)
12V AC/DC
Lens/LED Colors
R : Red
G : Green A : Amber
Y : Yellow PW : White S : Blue
Operator (style / function)
L1 : Pilot Light / dome
Operating voltage
126 : AC 120V (Transformer type)
246 : AC 240V (Transformer type)
386 : AC 380V (Transformer type)
486 : AC 480V (Transformer type)
108g
66 : AC/DC 6V (Full voltage type)
11 : AC/DC 12V (Full voltage type)
22 : AC/DC 24V (Full voltage type)
Terminals
F : Finger-safe terminal (IP20)
C : Exposed screw terminal
24V AC/DC
EU2B-YL122➃D➀
Note: ➀ Illumination Color. Specify a contact terminal style in place of ➃ in the part number: F (Fingersafe terminal), C (Exposed screw terminal)
2 Position Selector Switches
EU2B - YS 2 11 N1 F A
Operator (style / function)
S : Selector (Knob operator)
SK: Key selector (Key operator)
Number of Positions / Spring Return Action
2 : 2-position / Maintained
3 : 3-position / Maintained
2R : 2-position / Maintained (Overlap)
31 : 3-position / Spring return from right
2J : 2-position / Maintained (Special function) 32 : 3-position / Spring return from left
21 : 2-position / Spring return from right
33 : 3-position / Spring return two-way
Selector Switches
Operator Position
Contact
Mounting
NO
L
1
R
●
NC
NO
3
1
NO
NC
3
1
NC
NO
3
1
●
NC
NO
NO
NO
NC
NC
NC
NO
NO
NC
NO
NC
NC
NO
3
1
2
3
1
2
3
1
2
3
1
2
3
1
●
NC
2
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Maintained
L
R
R
Maintained
L
R
Spring Return
from Right
L
Operator Position
R
L
Mounting
L
NO
1
●
EU2BYS2110 ➃
EU2BYSK210➃➂
EU2BYSK2110➃➂
EU2BYS201➃
EU2BYS2101➃
EU2BYSK201➃➂
EU2BYSK2101➃➂
EU2BYS220 ➃
EU2BYS2120 ➃
EU2BYSK220➃➂
EU2BYSK2120➃➂
NC
NO
3
1
EU2BYS202➃
EU2BYS2102➃
EU2BYSK202➃➂
EU2BYSK2102➃➂
NO
NC
3
1
EU2BYS211➃
EU2BYS2111➃
EU2BYSK211➃➂
EU2BYSK2111➃➂
NC
NO
3
1
EU2BYS230 ➃
EU2BYS2130 ➃
EU2BYSK230➃➂
EU2BYSK2130➃➂
EU2BYS203 ➃
EU2BYS2103 ➃
EU2BYSK203➃➂
EU2BYSK2103➃➂
EU2BYS221➃
EU2BYS2121➃
EU2BYSK221➃➂
EU2BYSK2121➃➂
EU2BYS212➃
EU2BYS2112➃
EU2BYSK212➃➂
EU2BYSK2112➃➂
NC
NO
NO
NO
NC
NC
NC
NO
NO
NC
NO
NC
NC
3
1
2
3
1
2
3
1
2
3
1
2
3
EU2BYS2R11➃
R
Contact
EU2BYS210 ➃
N/A
EU2BYSK2R11➃➂
N/A
Key is removable in all maintained positions. Specify key removal position in place of ➂ in the part number. See table.
Specify a terminal style in place of ➃ in the part number: F (Finger-safe terminal), C (Exposed screw terminal).
2-position
Terminals
F : Finger-safe terminal (IP20)
C : Exposed screw terminal
Circuit Number
Blank : No Designation
N* : See charts
Key Selector Switches
Spring Return
from Right
L
Key Removable Position
See option codes below
Contact arrangement
10 : 1NO
03 : 3NC
11 : 1NO-1NC 02 : 2NC
01 : 1NC
21 : 2NO-1NC
30 : 3NO
12 : 1NO20 : 2NO
2NC
R
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Selector
Switches
Key Selector
Switches
Maintained
Maintained
L
R
L
EU2BYS2J10 ➃
EU2BYSK2J10➃➂
EU2BYS2J01➃
EU2BYSK2J01➃➂
EU2BYS2J20 ➃
EU2BYSK2J20➃➂
EU2BYS2J02➃
EU2BYSK2J02➃➂
EU2BYS2J11➃
EU2BYSK2J11➃➂
EU2BYS2J30 ➃
EU2BYSK2J30➃➂
EU2BYS2J03 ➃
EU2BYSK2J03➃➂
EU2BYS2J21➃
EU2BYSK2J21➃➂
EU2BYS2J12➃
EU2BYSK2J12➃➂
➂ Key Removable Option Codes (2-position)
2-position/inverse cam
Contact Block 1
Contact Block 2
Contact Block 3
4
R
3 Position Selector Switches
Selector Switches
Operator Position
Contact
Mounting
L
NO
1
●
NO
3
NO
2
NO
3
NC
1
NC
3
NC
2
NC
3
NO
1
NC
3
NC
1
C
R
Maintained
L
C
R
Spring Return from
Right
L
C
R
Key Selector Switches
Spring Return
from Left
L
C
Spring Return Two
Way
R
L
C
R
Maintained
L
C
R
Spring Return from
Right
L
C
R
Spring Return from
Left
L
C
R
Spring Return Two
Way
L
C
R
EU2BYS320➃
EU2B-YS3120➃
EU2B-YS3220➃
EU2B-YS3320➃
EU2B-YSK320➃➂
EU2B-YSK3120➃➂
EU2B-YSK3220➃➂
EU2BYSK3320➃➂
EU2BYS320N1➃
EU2B-YS3120N1➃
EU2BYS3220N1➃
EU2BYS3320N1➃
EU2BYSK320N1➃➂
EU2BYSK3120N1➃➂
EU2BYSK3220N1➃➂
EU2BYSK3320N1➃➂
EU2BYS302➃
EU2B-YS302➃
EU2B-YS3202➃
EU2B-YS3302➃
EU2B-YSK302➃➂
EU2B-YSK302➃➂
EU2B-YSK3202➃➂
EU2BYSK3302➃➂
EU2BYS302N1➃
EU2BYS3102N1➃➂
EU2BYS3202N1➃➂
EU2BYS3302N1➃
EU2BYSK302N1➃➂
EU2BYSK3102N1➃➂
EU2BYSK3202N1➃➂
EU2BYSK3302N1➃➂
EU2BYS311➃
EU2B-YS311➃
EU2B-YS3211➃
EU2B-YS3311➃
EU2B-YSK311➃➂
EU2B-YSK311➃➂
EU2B-YSK3211➃➂
EU2BYSK3311➃➂
EU2BYS311N1➃
EU2B-YS3111N1➃
EU2BYS3211N1➃
EU2BYS3311N1➃
EU2BYSK311N1➃➂
EU2BYSK3111N1➃➂
EU2BYSK3211N1➃➂
EU2BYSK3311N1➃➂
●
●
●
●
●
●
NO
3
NO
1
NC
2
●
EU2BYS311N2➃
EU2B-YS3111N2➃
EU2BYS3211N2➃
EU2BYS3311N2➃
EU2BYSK311N2➃➂
EU2BYSK3111N2➃➂
EU2BYSK3211N2➃➂
EU2BYSK3311N2➃➂
NC
2
●
EU2B-YS3111N3➀
NO
3
EU2BYS311N3➃
EU2BYS3211N3➀
EU2BYS3311N3➀
EU2BYSK311N3➃➂
EU2BYSK3111N3➃➂
EU2BYSK3211N3➃➂
EU2BYSK3311N3➃➂
NO
2
●
EU2BYS311N4➃
EU2B-YS3111N4➃
EU2BYS3211N4➃
EU2BYS3311N4➃
EU2BYSK311N4➃➂
EU2BYSK3111N4➃➂
EU2BYSK3211N4➃➂
EU2BYSK3311N4➃➂
●
EU2BYS330➃
EU2B-YS3130➃
EU2B-YS3230➃
EU2B-YS3330➃
EU2B-YSK330➃➂
EU2B-YSK3130➃➂
EU2B-YSK3230➃➂
EU2BYSK3330➃➂
●
EU2BYS303➃
EU2B-YS3103➃
EU2B-YS3203➃
EU2B-YS3303➃
EU2B-YSK303➃➂
EU2B-YSK3103➃➂
EU2B-YSK3203➃➂
EU2BYSK3303➃➂
●
EU2B-YS3
21N1➃
EU2B-YS3121N1➃
EU2BYS3221N1➃
EU2BYS3321N1➃
EU2BYSK321N1➃➂
EU2BYSK3121N1➃➂
EU2BYSK3221N1➃➂
EU2BYSK3321N1➃➂
EU2B-YS3
12N1➃
EU2B-YS3112N1➃
EU2BYS3212N1➃
EU2BYS3312N1➃
EU2BYSK312N1➃➂
EU2BYSK3112N1➃➂
EU2BYSK3212N1➃➂
EU2BYSK3312N1➃➂
●
●
●
●
NC
3
NO
1
●
NO
2
●
NO
3
NC
1
NC
2
NC
3
NO
1
NC
2
NO
3
NC
1
NO
2
NC
3
●
●
●
●
●
Specify a terminal style in place of ➃ in the part number: F (Finger-safe terminal), C (Exposed screw terminal).
L
Operator Position
C
Key is removable in all maintained positions. Specify key removal position in
place of ➂ in the part number. See table.
➂ Key Removable Option Codes (3-Position)
R
Code
A
B
C
D
E
G
H
Contact Block Position
Contact Block 1
Contact Block 2
Contact Block 3
The key can be released in any maintained position.
5
Description
Key removable in any position
Key removable in left and center positions
Key removable in center and right positions
Key removable in center position
Key removable in left and right positions
Key removable in left position
Key removable in right position)
CONTROL BOXES
1 control unit
2 control units
5 control units
4 control units
EC2BB51B051➀➁-U
EC2BB32B042➀➁-U
4 control units
EC2BB31B031➀➁-U
EC2BB51B041➀➁-U
6 control units
8 control units
EC2BB32B062➀➁-U
EC2BB52B082➀➁-U
10 control units
EC2B-B52B102➀➁-U
2 columns
1 column
EC2BEC2BB21B011➀➁-U B21B021➀➁-U
3 control units
6 control units
9 control units
15 control units
EC2BEC2BB33B093➀➁-U B53B123➀➁-U
EC2BB53B153➀➁-U
18 control units
EC2BB63B183➀➁-U
3 columns
EC2BB33B063➀➁-U
12 control units
➀ Thread Size
Code
Description
➁ Terminal Block Style
Code
Description
M1
M2
M3
M4
M5
N1
N2
N3
N4
blank
C
F
M16
M20
M25
M32
M40
NPT1/2
NPT3/4
NPT1
NPT1 1/4
no terminal block
Exposed screw terminals
Finger-safe terminals
Specify thread size in place of ➀ in part number.
Specify terminal block style in place of ➁ in part number
(standard versions do not contain a terminal block).
STANDARD CONTROL STATIONS
1 Control Unit × 1 Column
1 pushbutton
31
j
➀
42
1 pilot light
X1
X2
j
EC2B-1102BN2N 1-U
EC2B-1102BN2N 2-U
Flush momentary
1NO contact
Nameplate ON
Button color: black, green, red, and white
1NO-1NC contact
Flush momentary
1NC contact
Nameplate OFF
Button color: black, green, red, and white
Flush momentary
1NO-1NC contact
Nameplate OFF
Button color: black, green, red, and white
EC2B-1101BN2 3-U
EC2B-1101BN2 13-U
EC2B-1101BN2 14-U
EC2B-1101BN2 6-U
➀ 120V AC
Illumination color: red
240V AC
Illumination color: red
24V AC/DC
Illumination color: red
120V AC
Illumination color: green
240V AC
Illumination color: green
24V AC/DC
Illumination color: green
3
j
2
Flush momentary
1NO-1NC contact
Nameplate ON
Button color: black, green, red, and white
EC2B-1101BN2 12-U
EC2B-1106BN2N 1-U
1
EC2B-1102BN2N 4-U
EC2B-1101BN2 11-U
1 selector switch
OFF ON
EC2B-1102BN2N 3-U
4
Knob selector
2-position main➀ tained
1NO-1NC contact
Name plate
OFF-ON
1 key selector switch
1
OFF ON
3
OFF ON
j
2
1 emergency stop
switch
EC2B-1106BN2N 4-U
4
Key selector
2-position maintained
(removable at all
➀ positions)
1NO-1NC contact
Nameplate OFF-ON
OFF ON
EC2B-1102BN2N 7-U
1 1
Emergency stop switch
2NC contact
j ➀ Nameplate EMERGENCY STOP
Button color (red)
2 2
2 Control Units × 1 Column
2 flush pushbuttons
2 Mushroom Pushbuttons
EC2B-2102BN2N 1-U
3
4
1
Button color (black, green, red, and white buttons)
k
2
Flush momentary
➁ 1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
1 pilot light/1 pushbutton
X1
3
Flush momentary
j ➀ 1NO contact, Nameplate ON
X2
3
1
4
2
j
1
4
3
2
1
4
2
j
k
EC2B-2102BN2N 4-U
Mushroom momentary
➀ 1NO-1NC contact, Nameplate ON
Button color (black)
Mushroom momentary
1NO-1NC contact, Nameplate OFF
Button color (red)
EC2B-2110BN2N 5-U
EC2B-2110BN2N 6-U
EC2B-2110BN2N 3-U
➀
120V AC
Illumination color: red
240V AC
Illumination color: red
24V AC/DC
Illumination color: red
➁
Flush momentary
1NO-1NC contact
Name plate STOP
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact
Name plate STOP
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact
Name plate STOP
Button color (black, green, red, and white buttons)
k
Specify terminal style code in place of in part no. C (standard screw terminal), F (finger-safe screw terminal)
6
2 Control Units × 1 Column
1 pilot light / 1 selector switch
X1
EC2B-2117BN2N 3-U
EC2B-2117BN2N 4-U
X2 j
120V AC
➀
Illumination color: red
3
1
OFF ON
k
2
4
240V AC
Illumination color: red
OFF ON
Knob, 2-position,
➁ 1NO-1NC contact
Maintained, Name plate OFF-ON
Knob, 2-position,
1NO-1NC contact
Maintained, Name plate OFF-ON
OFF ON
3 Control Units × 1 Column
1 pilot light / 2 pushbuttons
X1
EC2B-3110BN2N 6-U
EC2B-3110BN2N 3-U
120V AC
➀
Illumination color: red
EC2B-3110BN2N 5-U
240V AC
Illumination color: red
24V AC/DC
Illumination color: red
k
Flush momentary
➁ 1NO contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO contact, Nameplate ON
Button color (black, green, red, and white buttons)
l
Flush momentary
➂ 1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
X2 j
4
3
2
1
3 pushbuttons
1 meter / 2 pushbuttons
EC2B-3102BN2N 1-U
3
1
4
3
2
1
4
3
2
1
4
2
A
j
➀
k
Flush momentary
1NO-1NC contact,
➁ Blank nameplate
Button color (black, green, red, and white buttons)
l
➂
3
EC2B-3152BN2N 1-U
➀
Specify input, capacity, and scale
k
➁
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
l
➂
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
j
1
4
3
2
1
4
2
Specify the meter's capacity and scale in place of in the part number
4 Control Units × 1 Column
2 pilot lights / 2 pushbuttons
X1
X1
EC2B-4110BN3N 5-U
EC2B-4110BN3N 6-U
EC2B-4110BN3N 3-U
240V AC, Illumination color: red
24V AC/DC, Illumination color: red
X2 j
➀ 120V AC, Illumination color: red
X2
➁ 120V AC, Illumination color: green
240V AC, Illumination color: green
24V AC/DC, Illumination color: green
Flush momentary
➂ 1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
➃ 1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
3
1
4
3
2
1
4
2
k
l
m
1 pilot light / 2 pushbuttons /
1 selector switch
EC2B-4113BN3N 5-U
EC2B-4113BN3N 6-U
EC2B-4113BN3N 3-U
X2 j
➀ 120V AC, Illumination color: red
240V AC, Illumination color: red
24V AC/DC, Illumination color: red
3
1
4
3
2
1
Flush momentary
➁ 1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
4
2
Flush momentary
➂ 1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
1
3
Knob, 2-position, maintained
➃ 1NO-1NC contact
Nameplate HAND-AUTO
Knob, 2-position, maintained
1NO-1NC contact
Nameplate HAND-AUTO
Knob, 2-position, maintained
1NO-1NC contact
Nameplate HAND-AUTO
X1
k
l
m
HAND AUTO
HAND AUTO
HAND AUTO
HAND AUTO
5 Control Units × 1 Column
2 pilot lights / 2 pushbuttons /
1 selector switch
X1
X1
3
OFF ON
X2 j
X2
k
1
4
3
2
1
4
2
2
4
l
m
n
1 3
EC2B-5113BN3N 5-U
EC2B-5113BN3N 6-U
EC2B-5113BN3N 3-U
➀ 120V AC, Illumination color: red
➁ 120V AC, Illumination color: green
240V AC, Illumination color: red
24V AC/DC, Illumination color: red
240V AC, Illumination color: green
24V AC/DC, Illumination color: green
Flush momentary
➂ 1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate ON
Button color (black, green, red, and white buttons)
Flush momentary
➃ 1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color (black, green, red, and white buttons)
Flush momentary
1NO-1NC contact, Nameplate OFF
Button color black, green, red, and white buttons)
Knob, 2-position, Maintained,
➄ 1NO-1NC contact,
Name plate HAND-AUTO
Knob, 2-position, Maintained,
1NO-1NC contact
Name plate HAND-AUTO
Knob, 2-position, Maintained,
1NO-1NC contact
Name plate HAND-AUTO
HAND AUTO
Specify terminal style code in place of in part no. C (standard screw terminal), F (finger-safe screw terminal)
7
HAND AUTO
HAND AUTO
DIMENSIONS
All dimensions in mm
Pilot Lights
Control Units
Shown with finger-safe contacts
Pushbuttons
61.4
67.7
24.5
1.0 to 4.5 (panel thickness)
67.7
62.0
ø 40.0
ø40
39.0
ø40
Extended
ø 24.0
Mushroom
Flush
19.3
20.3
Emergency Stop Switches
67.7
Meters
Shown with finger-safe contacts
32.2
35.0
1.0 to 4.5 (Panel thickness)
1.0 to 4.5 (panel thickness)
67.7
ø 64.0
47.4
8.0
38.4
ø 40.0
Shown with finger-safe contacts
ø 28.0
13.3
1.0 to 4.5 (panel thickness)
67.7
20.3
32.2
13.3
32.0
32.5
48.0
ø 40.0
33.0
ø 40.0
Shown with finger-safe contacts
Selector Switches
Shown with finger-safe contacts
50 min (*note)
+0.2
4.8 0
+0.5
1.0 to 4.5 (panel thickness)
67.7
Panel thickness: 1.0 to 4.5 mm.
*Note: The meter can be mounted on the top mounting holes of a standard 50mm mounting centers. The meter can be mounted on any mounting hole with a 70mm or larger mounting center.
Key Selector Switch
32.2
38.4
ø 40.0
Shown with finger-safe contacts
47.4
70 min
33 0
37.3
.5
+0 0
0.5
ø3
32.2
47.4
62.1
Mounting Hole Dimensions
38.4
ø 40.0
33.5
27.3
1.0 to 4.5 (panel thickness)
67.7
8
1, 2 control units x 1 column
2, 3, 4, 5 control units x 2 columns
weight: 1.2kg/1.4kg
weight: 3.8/4.2/4.6/5.0 kg
4-ø7 (mounting hole)
110
95
10 6
1.5
Mounting tab
4 control units
70
70
230
220
210
3 control units
70
5 control units
A
(mounting
hole)
Hinge
70
2×50P
100
142
(mountin g
hole )
170
4-ø10
Reducer
M4 grounding terminal
M5 lid mounting screw
Hinge
2
Mounting tab
4×50P
36.5
36
50
2 control units
106
3×50P
50
(mounting
hole)
2 control units
R
1 control unit
(mounting
hole)
115
Reducer
M4 grounding terminal
M5 lid mounting screw
70
3 control units x 1 column
Dimensions
2, 3, 4, 5 control units x 3 columns
weight: 1.8kg
No. of
Control Units
A
R
2 or 3
250 180
4 or 5
350 280
weight: 4.8/5.2/6.5/7.1 kg
3 control units
4-ø7 (mounting hole)
106
(mounting
hole)
1.5
Mounting tab
320
310
300
3×50P
110
95
140
140
50
2×50P
4 control units
2 control units
115
106
2
Mounting tab
R
Hinge
4×50P
Reducer
M4 grounding terminal
M5 lid mounting screw
Hinge
A
5 control units
140
(mounting
hole)
2×50P
140
36.5
192
150
220
(mounting
hole)
4-ø10
(mounting hole)
3 control units
70
36
70
Reducer
M4 grounding terminal
M5 lid mounting screw
Dimensions
4, 5 control units x 1 column
2 or 3
250 180
4 or 5
350 280
weight: 8.1kg
115
110
95
5 control units
320
310
300
4-ø7 (mounting hole)
106
1.5
(mounting
hole)
Mounting tab
Control Unit
Mounting Holes
140
106
2
Mounting tab
4-ø10
70
9
70
330
(mounting
hole)
Hinge
36.5
Reducer
M4 grounding terminal
M5 lid mounting screw
Hinge
400
5×50P
322
250
(mounting
hole)
350
(mounting
hole)
36
4x40P
3x50P
A
6 control units x 3 columns
weight: 2.4kg
4 control units
No. of
Control Units
Reducer
M4 grounding terminal
M5 lid mounting screw
R
Terminal Blocks
Fittings and Reducers
Terminal blocks are not supplied with the standard control boxes (without wiring). When wiring
inside the control box is required, specify the wiring circuit. The terminal block type used on the
control boxes with wiring depends on the terminal style of the control unit.
Reducers installed at the bottom of the control box are as follows: 1 column: 1 reducer, 2 columns: 2 reducers, 3 columns: 3 reducers, 4 columns: 4 reducers. Material is nickel-plated brass.
Use cable lead-in fittings that are commercially available. See the following table for optional reducers.
Control Box Style Part No.
Thread Size Symbol UL c-UL
C terminal style
exposed screw terminal
ET2A-8PE
polyamide
IECEx TUR 15.0043U,
TÜV 15 ATEX 7799U
34
22
1 column
(1 to 3 control units)
2, 3 columns
(2, 3 control units)
101
123
F terminal style
1, 2, 3 columns
(4, 5 control units)
3, 4 columns
(6 control units)
32
22
finger-safe screw terminal
IP20 clamp terminal: 264-238 (WAGO)
polyamide
ECEx PTB 04.0003U, PTB 98 ATEX
3129U
84
96
1-column 1, 2 units
1-column 3 units
1-column 4, 5 units (1 2-column 2, 3 units (2
(1 terminal block/8 poles) (1 terminal block/ 8 poles) terminal block/ 8 poles) terminal blocks/16 poles)
3-column 2, 3 units
(3 terminal blocks/ 24
poles)
3-column 4, 5, 6 units
(6 terminal blocks/ 8
poles)
M16
M20
M25
M32
NPT 1/2
NPT 3/4
NPT 1
M25
M32
M40
NPT 3/4
NPT 1
NPT 1 1/4
M1
M2
M3
M4
N1
N2
N3
M3
M4
M5
N2
N3
N4
: Standard reducer : non-standard reducer
The number of terminal blocks, poles, and the installation direction that can be installed on the
control box are as follows:
2-column 4,5 units
(4 terminal blocks/ 32
poles)
EC9E-H3M16E-UL
EC9E-H3M20-UL
EC9E-H3M25-UL
EC9E-H3M32-UL
EC9E-H3NPT1-UL
EC9E-H3NPT2-UL
EC9E-H3NPT3-UL
EC9E-H4M25-UL
EC9E-H4M32-UL
EC9E-H4M40-UL
EC9E-H4NPT2-UL
EC9E-H4NPT3-UL
EC9E-H4NPT4-UL
The reducers in the table above are for replacement use only. All EC2B boxes are supplied with
a reducer that has been secured to the housing per UL regulations. If it is necessary to replace a
reducer, the user should follow appropriate UL standards for securing to EC2B housing.
4-column 6 units
(8 terminal blocks/ 64
6 units
poles)(84-column
terminal blocks/
64 poles)
ACCESSORIES
All dimensions in mm
Nameplates
Used for pilot light, pushbutton, selector switch, and key selector switch.
EU9Z-NM
Nameplate Inserts
Dimensions
40
(35)
Appearance
Marking Plate
4.5
28.5
Part Number
(6.5)
Appearance
0
ø4
1.5
Legend
Part Number
Blank
ON
EU9Z-NP0
EU9Z-NP1
OFF
EU9Z-NP2
START
EU9Z-NP3
STOP
EU9Z-NP4
OFF-ON
EU9Z-NP31
HAND-AUTO
EU9Z-NP35
HAND-OFF-AUTO
EU9Z-NP53
Material: Aluminum
Installing the Insert to the Nameplate
Removing the Insert from the Nameplate
Insert
➁
Flat screwdriver
Insert
➀
10
Nameplate
To remove the Insert, insert a flat screwdriver between the Insert and Nameplate.
Emergency Stop Switch Padlock Cover
Rubber Boots
Used with EU2B-YBV emergency stop switch to maintain the switch in the latched status.
Appearance
Description/Usage
Appearance
Part Number
Part Number
Dimensions
For Flush Pushbuttons
Base
EU9Z-DB1
46
Not for use with name plate
EU9Z-PCE
For Flush Pushbuttons
For use with name plate
EU9Z-DB1N
8
32.2
50
55.4
For Extended Pushbuttons
Coating: yellow Material: Stainless Steel
Not for use with name plate
EU9Z-DB2
Mounting Hole Plug
Used to plug unused mounting holes (ø30.5) on the mounting panel.
Appearance
Part Number Dimensions / Usage
For Extended Pushbuttons
23.2
EU9Z-DB2N
ø40
For use with name plate
EU9Z-BP
13.3
Emergency Stop Switch Nameplate Stickers
Appearance
Legend
Buttons
Part Number
Appearance
Dimensions
8
ø5
ø5
Blank
8
Style
Part Number
Flush
HW1A-B1➀
Button Color Code
EU9Z-NVS0
ø4
ø4
0.5
0.5
8
8
ø5
ø5
Emergency
Stop
EU9Z-NVS27
ø4
Extended
HW1A-B2➀
ø40 Mushroom
HW1A-B4➀
ø4
0.5
0.5
Specify a color code in place of ➀
in the Ordering Number.
R : red
G : green
B : black
Y : yellow
W : white
S : blue
Material: yellow vinyl Legend: black
Padlock Cover
Material: Polyacetal
EU2B-YB2 extended pushbutton: to maintain latched status
EU2B-YB1 flush pushbutton/EU2B-YSK key selector switch: to prevent operation
Appearance
Part
Number
1.0 to 10.5
(panel thickness)
Lenses
Appearance
Dimensions
46
32.1
EU9Z-PC
Material: AS resin (gasket supplied)
44
8
24.5
Note: mounted to outside of enclosure with screws, not provided by IDEC
Material: Stainless Steel
11
Lens Color
Part Number
Red
Green
Amber
Yellow
White
Blue
EU9Z-LR
EU9Z-LG
EU9Z-LA
EU9Z-LY
EU9Z-LW
EU9Z-LS
Control Box Shade
LED Lamps
Shape
Part No.
D
Operating
Voltage
6V AC/
DC±10%
Current Draw
AC
DC
8mA
7mA
(A, R, W)
5.5mA
(G, PW, S)
Part
Number
LSTD-6➀
12V AC/
DC±10%
11mA
10mA
LSTD-1➀
24V AC/
DC±10%
11mA
10mA
LSTD-2➀
Illumination Color Code
Specify a color code in place
of ➀ in the part number
R : red
G : green
A : amber
PW : white
S : blue
Use a white (PW) LED with
yellow (Y) lens.
Base
W
EC9Z-F2A21M
EC9Z-F2A31M
H
EC9Z-F2A51
EC9Z-F2A32
BA9S/13
Material: stainless steel
Thickness: 1mm
Photo: Part No. EC9Z-F2A52
EC9Z-F2A52
EC9Z-F2A33
EC9Z-F2A53
EC9Z-F2A63
EC9Z-F2A64
Applicable
Control Box
EC2B-11*B
EC2B-21*B
EC2B-31*B
EC2B-41*B
EC2B-51*B
EC2B-22*B
EC2B-32*B
EC2B-42*B
EC2B-52*B
EC2B-23*B
EC2B-33*B
EC2B-43*B
EC2B-53*B
EC2B-63*B
EC2B-64*B
Dimensions (mm)
H
W
D
180
160
160
230
160
160
360
160
160
260
420
160
360
420
160
260
510
160
360
510
160
410
410
510
580
160
160
Protects control units from direct sunlight and rain. The surface of the control box shade is uncoated.
Can be installed by tightening to the mounting tabs on the control box. Control box shade cannot be
installed later. Specify shade at time of order.
OPERATING INSTRUCTIONS
Installation Area
Determine the operating current so that the total heat value of 1 wire bundle is below 300 [A2 ×
wires]. Also, when calculating the heat value, take the current fluctuation (10%) into consideration. [calculation example: EC2B-41**B (8 circuit)]
➀ Apply 10A to 1 circuit, 1A to the remaining 7 circuits:
{(10A × 1.1)2 × 2 wires} + {(1A ×1.1)2 × 14 wires} ≈ 259 (can be used because < 300)
➁ Apply 10A to 1 circuit, 2A to the remaining 7 circuits:
{(10A × 1.1)2 × 2 wires} + {(2A × 1.1)2× 14 wires} ≈ 310 (cannot be used because > 300)
See the table below for the allowable operating current when applying current evenly to each
control box.
Do not install the EC2B control box in an environment where more than IP65 protection degree
(more than Type 4X in North America) is required.
Use the EC2B control box under ambient temperature of –20 to +50°C. If the control box is
exposed to direct sunlight and the surface temperature may rise above 50°C, provide a shade to
keep the surface temperature below 50°C.
Installation
Use four M6 bolts for 1-column, four M8 bolts for 2- and 3-column, or other methods with
equivalent strength to install the control box. Mounting tab thickness is 1.5mm for 1 column and
2mm for 2, 3, and 4 columns.
• If bolts become may loose due to vibration, use spring washers.
• If bolt corrosion is anticipated, use anti-corrosion bolts or other countermeasures.
Allowable Operating Current
Notes on Emergency Stop Switches
When using the emergency stop switches on safety-related parts of the control system, observe
safety standards and regulations of the relevant country or region. Also be sure to perform a risk
assessment before operation.
Opening/Closing the Lid
Use a Philips screwdriver to loosen lid mounting screws. While holding the unhinged side, open
the lid slowly without exerting excessive force on the hinge.
Before closing the lid, make sure of the following:
• No foreign substances are on the packing or joint surfaces.
• No displacement of the waterproof packing.
• Wires are not caught between the joint surfaces.
• Next, close the lid slowly and tighten the screws to a proper torque of 1.6 to 2.4 N·m.
Limitation of the Operating Current
Major heat sources comes from the wiring which is connected to the control box. Therefore,
not only the operating current but wiring conditions (size, no. of wires, no. of wire bundles) may
cause temperature rise. When wiring, observe the following conditions.
Stranded wire: 1.5 to 2.5 mm2 (UL-c-UL certified) / Solid wire: ø1.2 to ø1.6 mm (16 to 14 AWG)
• Maximum no. of wires per bundle: 16
• Maximum operating current: 10A
When using the control box under an operating environment of 40°C minimum, use a heat
resistant cable of 70°C minimum.
Control
Box
Part No.
Max.
No. of
Circuits
EC2B-11
EC2B-21
EC2B-31
EC2B-41
EC2B-51
EC2B-22
EC2B-32
EC2B-42
EC2B-52
EC2B-23
EC2B-33
EC2B-43
EC2B-53
EC2B-63
EC2B-64
3
6
9
12
15
12
18
24
30
18
27
36
45
54
72
Max No. of Wires per Bundle (*1)
[wires] ([wires]×[bundle])
Without terminalWith terminal
blocks
blocks
16 (16×1)
8 (8×1)
16 (16×1)
8 (8×1)
16 (16×1)
8 (8×1)
16 (16×1)
16 (16×1)
16 (16×1)
16 (16×1)
32 (16×2)
16 (8×2)
32 (16×2)
16 (8×2)
32 (16×2)
32 (16×2)
32 (16×2)
32 (16×2)
48 (16×3)
24 (8×3)
48 (16×3)
24 (8×3)
48 (16×3)
48 (16×3)
48 (16×3)
48 (16×3)
48 (16x3)
48 (16x3)
64 (16x4)
64 (16x4)
Allowable Operating
Current
(reference) (*2)
7A
5A
4A
3A
3A
5A
4A
3A
3A
5A
4A
3A
3A
3A
3A
*1: Make sure that the number of wires per bundle is a maximum of 16 by reducing the wiring or by jumper
wiring. The maximum number of wires per bundle may need to be further reduced depending on the
wire size, lead-in fitting, or conduit size.
*2: The allowable current value (reference) when applying current evenly to all circuits of the maximum
number of circuits.
12
Wiring
Removing and Installing the Contact Unit / Lamp Unit
Wiring Construction
To remove the contact unit or the lamp unit from the operator, pull the protruding yellow part of
the locking lever outwards as shown in the figure below using a screwdriver, and turn it to the
left. The contact unit or lamp unit can be removed.
Observe the laws and regulations in each country concerning wiring construction.Use cable
wiring or metal conduit wiring for installation in hazardous locations. If foreign objects or water
may enter the box, install a sealing fitting near the cable entry of the box and seal the control box
using a compound. Standard type control boxes do not contain a terminal block. Wire the control
units directly.
EU2B-YB/ YBV
EU2B-YS/ YSK
8.0 max.
∗£1.8 max.
∗£1.8 max.
mi
n.
6.9 max.
6.9 max.
3.6 min
ø3
.6
5.5 min.
Without
insulating
sheath
With
insulating
sheath
Insulation
sheath
Wire
locking lever
indicator (red)
8.0 max.
Panel mounting for the operator, lens unit and meter
For IP20 clamp terminal
(WAGO: 264-238)
Remove the locking ring from the operator and check that the rubber gasket is in place. Insert the
operator from the panel front into the panel hole. Place the projection on the operator with TOP
.2 m
Insulation sheath
ø4
8.5 max.
in.
.2 m
ø4
Insulation sheath
in.
(Ring terminal)
(Ring terminal)
8.5 max.
➂
(Pull)
(Ferrule)
∗ Dimensions after crimping
For screw terminal ET2A-8PE
locking lever
TOP
When the contact unit is removed from the emergency stop switch operator, the NO contact
closes and the NC contact opens.
Do not turn the locking lever when the contact unit is removed from the operator (the red indicator protruding out, see the figure below) or the switch can be damaged.
Ring and spade terminals cannot be used for EU2B control units with IP20 finger-safe terminals.
Ring and spade terminals cannot be used for IP20 clamp type terminal blocks. When connecting
two ferrules to an EU2B control unit, use ferrules without insulating sheath.
5.5 min.
(Pull)
locking lever
Applicable crimping terminal
3.4 max.
(Turn)
➂
(Ring terminal)
(Lift)
➁
➁
Stranded wire: 1.25 to 2.5 mm2, solid wire: ø1.2 to ø1.6 mm (AWG16 to 14). Do not connect more
than 2 wires to the same terminal.
➀
EU2B-YL
(Turn)
Applicable Wires
(Spade terminal)
➀
(Lift)
5 to 6.6
5 to 6.6
Recommended crimping terminal (WAGO) Ferrule with insulating sheath: 216-204
Ferrule without insulating sheath: 216-104 Crimping plier: 206-204
marking upward and the recess on the mounting panel in the same direction. Meters have no
projection.
Tighten the locking ring using ring wrench XN9Z-T1 to a torque of 2.5 Nm. When using a nameplate or padlocking cover, install it between the operator and panel. Make sure that the groove
of the namplate or padlocking cover and the projection on the TOP marking of the operator are in
the same direction.
Note: The locking ring for emergency stop switches and meter
Insulation Sheath
is metallic. The meter can’t mount the nameplate or podlocking
cover.
Recommended Tightening Torque
EU2B control units (M3.5) and ET2A-8PE terminal block (M4): 1.0 to 1.3 N·m
Warning
Incorrect wiring may cause fire hazard. Observe the following conditions.
Be sure to install an insulating sheath on the crimping terminal or the crimping terminal with
insulation.
Installing the contact unit and lamp unit
5.5 to 6.0
Wire
All dimensions in mm.
To install the contact unit, place the TOP marking on the operator
and the TOP marking on the contact block adapter in the same
direction, and then attach the contact unit to the operator. Then turn the locking lever to the right.
Follow the same procedure when installing the lamp unit.
When installing the lamp unit, check that the inner lens is not loose.
The contact block adapters for emergency stop switches cannot be used for pushbuttons, selector, or key selector switches.
When connecting solid wires or stranded wires directly, strip the insulation as mentioned below,
and insert the wire all the way in.
EU2B Control units: 8.6 mm maximum
IP20 crimping terminal: 8 to 9 mm
When using stranded wires, make sure that there are no wire whiskers.
Make sure that the spade crimping terminals and ferrules are inserted all the way in.
Use insulated ring terminals for the ET2A-8PE terminal block. Use only applicable crimping
terminals and do not directly connect stranded wires or solid wires.
TOP marking
Projection
Nameplate or
Padlocking cover
Recess on the panel
Rubber
gasket
Locking ring
Recess on the
Nameplate
Nameplate
gasket
EU2B-YL
EU2B-YB
EU2B-YS
TOP marking
TOP marking
➀
➀
➁
➁
TOP
inner lens
13
Removing the Contact Block
Installing EU9Z-PC Padlock Cover
To remove the contact block, insert a flat screwdriver under the latch of the contact block adaptor
and disengage the latch as shown in the figure below.
(Flush/extended pushbtton/key selector switch)
EU9Z-PC can be installed in the following two ways.
Remove the cover in the reverse step of installing the cover. Do not install or remove the cover
forcefully, or it will cause failure.
[Installation A]
Cover
Flat Screwdriver
Installing the Contact block
[Installation B]
This method is effective when the neighboring control unit interferes when installing in method
A.
When installing the contact block after maintenance or wiring, make sure that the contact
configuration is correct. Installing the contact block in the incorrect position or incomplete installation may cause malfunction of the switch.
Remove the contact block from the operator before installing the contact block to the contact
block adaptor. Also make sure that the contact block is correctly installed to the contact block
adaptor before attaching the operator. Do not install the contact block adaptor with the operator
attached. Otherwise, malfunction may result.
Cover
Protective Grounding
Protective grounding must be performed according to the installation environment and rating
requirements. Observe laws and regulations set by each country.
• Connect the M4 grounding terminal of the EC2B control box to a proper ground (grounding
resistance 10Ω maximum). When operating the EC2B control box by connecting to circuits
of 300V or below, the grounding resistance must be 100Ω maximum.
• When using cables, connect one of the cable cores to the grounding terminal in the
enclosure.
• If the grounding terminal in the enclosure cannot be used, use the M4 grounding terminal
on the outside of the enclosure.
Recommended tightening torque:
M4: 1.0 to 1.3 Nm
M6: 3.9 to 5.4 Nm
• For grounding, use appropriate wires (size, material, insulation) that can tolerate the expected maximum grounding current. Be sure to protect the grounding wire with protection,
such as metal conduit, from external damage.
Accessories
Padlock Cover
The following padlocks and hasps can be used.
(Padlock Size)
a
Flush/extended pushbutton/key selector
switch
Emergency Stop Switch
b
ø3.5 to
7.0 mm
ø5.5 to
7.0 mm
c
15 mm min.
70 mm max.
—
—
Installing EU9Z-DB Rubber Boots
To install the rubber boot on flush and extended pushbuttons, place the rubber boot on the cap
and push the rubber boot holder straight. The notches around the rubber boot must show evenly.
Rubber boot holder
Notches
Rubber boot
Cap
Notches for
screwdriver
Push-in position
Push the rubber boot holder further around on the two notches on the holder so that the holder
fits the button completely
Make sure that the rubber boot and rubber boot holder are installed straight.
On Nameplate Types, the EU2B and the rubber boot holder must be aligned so that when installed, the anti-rotation projection on the EU2B comes to the center of the groove on the holder.
Make sure that the rubber boot is installed completely, otherwise water droplets might enter the
rubber boot, but no water will enter the control box.
Align
Recommended Hasp
Manufacturer
Part No.
Panduit
PSL-1, PSL-1A, PSL-1.5, PSL-1.5A, PSL-HD1
Master Lock
420, 421
To remove the rubber boot from the flush and extended pushbuttons, gently insert the slotted screwdriver (0.5t x 4w or below)
inside a notch on the rubber boot holder and tilt to the direction
shown by the arrow ➀. To prevent damage, do not apply excessive
force to the EU2B when removing the rubber boot.
Padlock and hasp are available in various shapes and sizes. Make sure that they do not interfere
with the control units. Note: Not supplied by IDEC.
Keep the total weight of padlock and hasp under 1500g max, otherwise the switch may malfunction or result in failure. No vibration should be applied when padlock or hasp are installed. When
padlock or hasp are disfigured, stop usage immediately.
Ensure that no shock or electric sparks are generated.
When using the plate lock padlock cover with the extended pushbutton, the switch contact may
turn on/off when the cover is being installed. Ensure to provide functional safety measure to
prevent unexpected startup.
When using the padlock cover on the safety-related part of the control system, observe safety
standards and regulations of the relevant country or region. Also be sure to perform risk assessment before operation.
14
Maintenance and Inspection
EC2B Control Boxes
EU2B switches should be installed in an appropriate control box.
• EC2B control boxes can be installed only in zones 1 and 2. Do not use in zone 0. In North
America, the EC2B can be installed in Division 2 areas, but cannot be installed in Division
1 areas.
• Turn power off to the EC2B control box before installation, removal, wiring, or maintenance, otherwise explosion, fire hazard, or electric shock may result.
• Special skills and knowledge of explosion protection, electric system installation, and relevant laws/regulations are required to transport, install, wire, operate, repair, and inspect
the EC2B control box. People without such expertise must not use the EC2B control box,
otherwise damage or accident may result.
• Do not modify the EC2B, otherwise damage or accident may result.
• Do not use a damaged EC2B control box, otherwise damage or accident may result.
• W hen connecting external devices, make sure that each cable is connected to the correct
terminal, otherwise electric shock, fire hazard, or explosion may result.
• Use wires of a proper size to meet voltage and current requirements. Incorrect wiring may
cause abnormal temperature rise and lead to fire hazard and explosion.
• Connect the grounding terminal to a proper ground, otherwise electric shock, fire hazard,
or explosion may result.
• Do not sit on or hang from the EC2B control box, otherwise damage, personal injury, or
accident may result.
• Do not open the lid of the EC2B control box when it is energized, otherwise electric shock,
fire hazard, or explosion may result.
• Operate the EC2B control box at the rated current and voltage specified in this catalog,
otherwise short-circuiting, fire hazard, or explosion may result.
• When measuring the insulation resistance of the EC2B control box, make sure that
potentially explosive atmosphere of explosive gas or vapor does not exist in the vicinity,
otherwise explosion may result. Also, do not touch the terminals without paying attention,
otherwise electric shock will result.
• Do not place any obstacles in front of the nameplate.
• Do not remove the nameplate.
• When opening the lid for wiring, maintenance or inspection, make sure that substances
such as dust, concrete powder, or metal powder do not enter inside the box, otherwise
contact failure or insulation failure may result.
• Do not drop the EC2B control box during transportation.
• Be sure to open the carton the right way up, otherwise damage or personal injury may
result.
• Check that the product is what you have ordered. Using an incorrect model might result in
malfunction or accident.
• Stop operation immediately if abnormal operation occurs. Otherwise, a secondary accident may occur.
• The surface temperature of the EC2B control box may become extremely hot during operation. Before maintenance or inspection of the EC2B, be sure to wear gloves to prevent
burning your hand.
Maintenance and Inspection Method
Perform daily or periodical maintenance and inspection for items such as damage and temperature rise of the EU2B switches listed in the Maintenance and Inspection table below.
Observe laws and regulations set by each country. Do not open the lid when inspecting the EC2B
while it is energized. Never disassemble the control box. Do not use tools that cause sparks during maintenance and inspection. When using measuring devices, use explosion-protected types.
When the EC2B needs to be disassembled or assembled for maintenance or repair, contact IDEC.
Maintenance and Inspection
Inspection Items
Inspection Method Inspections
Enclosure base
Visual
Tightening bolt,
screws
Visual, tactile
Packings
Visual
Connecting parts
Visual, tactile
Temperature rise
Thermometer, tactile
No rusting
No damages
No loosening
No rusting
No cracks
No apparent deformation
No loosening of screws
No dirt on insulation
materials
Surface temperature
80ºC max.
Measures
Cleaning
Rust-resistant treatment
Tightening
Cleaning
Replacement
Tightening
Cleaning
Investigate the cause
Disposal
Observe laws and regulations set by each country concerning refuse disposal.
Safety Precautions
EU2B Control Units
Use EU2B switches that are applicable for use in hazardous areas (potentially explosive atmosphere where explosive gas or vapor may exist), otherwise explosion or fire hazard may result.
• EU2B switches can be installed only in zones 1 and 2. Do not use in zone 0.
• Turn power off to the EU2B switches before installation, removal, wiring, or maintenance,
otherwise explosion, fire hazard, or electric shock may result.
• Do not disassemble, repair, or modify, otherwise damage or accident may result.
• Do not use damaged EU2B switches, otherwise damage or accident may result.
• When connecting external devices, make sure that each cable is connected to the correct
terminal, otherwise electric shock, fire hazard, or explosion may result.
• Use wires of a proper size to meet voltage and current requirements. Incorrect wiring may
cause abnormal temperature rise and lead to fire hazard and explosion.
• Connect the grounding terminal to a proper ground, otherwise electric shock, fire hazard,
or explosion may result.
• Operate the EU2B switches at the rated current and voltage specified in this catalog,
otherwise short-circuiting, fire hazard, or explosion may result.
• Stop operation immediately if abnormal operation occurs. Otherwise, a secondary accident may occur.
• Use explosion-proof electrical equipment that are applicable for use in hazardous areas
(potentially explosive atmosphere where explosive gas or vapor may exist), otherwise
explosion or fire hazard may result.
15
EC2B
1-column Control Box Specification Sheet
TO: IDEC Corporation
Company:
TEL:
Contact Person:
FAX:
No. of Control Box
Select the required specifications by checking the checkboxes, and specify the details.
Control box size
£ EC2B-110
£ EC2B-210
£ EC2B-310
£ EC2B-410
NP
Nameplate
NP
1
E1
Nameplate (NP)
£ No
nameplate
£ EC2B-510
NP
NP
1
1
2
2
E1
NP
1
1
2
2
3
3
3
E1
4
4
5
E2
E2
Material: Acrylic (53 mm × 12 mm, plate thickness 2 mm)
Legend color: black letter, white background
Maximum no. of letters: 19 letters per line (up to 2 lines)
£ 1 line
1st line
£ 2 lines
2nd line
Control Units
Position
Control Unit Part No.
Control Unit Nameplate
1
£ ON
£ OFF
£ START
£ OFF ON
£ HAND AUTO
£ HAND OFF AUTO
£ STOP
£ No nameplate £ Specify letters (
2
£ ON
£ OFF
£ START
£ OFF ON
£ HAND AUTO
£ HAND OFF AUTO
£ STOP
£ ON
£ OFF
£ START
£ OFF ON
£ HAND AUTO
£ HAND OFF AUTO
£ OFF
£ START
£ OFF ON
£ HAND AUTO
£ HAND OFF AUTO
£ EMERGENCY STOP
£ Blank
)
£ ON
£ OFF
£ START
£ OFF ON
£ HAND AUTO
£ HAND OFF AUTO
£ STOP
£ EMERGENCY STOP
£ Blank
)
EC2B-110, 210, 310
EC2B-110, 210, 310
Code Cable lead-in method
E1
Reducer
With specification
• Specify wiring diagram when wiring is required.
EC2B-410, 510
NPT 3/4
UL/c-UL, IECEx/ATEX certified
•
£ Blank
£ STOP
£ No nameplate £ Specify letters (
Without specification
(standard reducer)
£ EMERGENCY STOP
)
£ ON
Lead-in Fitting (E1/E2)
£ Blank
£ STOP
£ No nameplate £ Specify letters (
5
£ EMERGENCY STOP
)
£ No nameplate £ Specify letters (
4
£ Blank
)
£ No nameplate £ Specify letters (
3
£ EMERGENCY STOP
Check
£
£
£
£
£
£
£
Specification
NPT 1
EC2B-410, 510
Cable lead-in method
Code
M16
M20
M25
M32
E2
Reducer
NPT 1/2
NPT 3/4
Check
£
£
£
£
£
£
Specification
M25
M32
M40
NPT 3/4
NPT 1
NPT 1 1/4
NPT 1
• Specify when other accessories are required.
IDEC Corporation • 1175 Elko Drive • Sunnyvale, CA 94089 • 800-262-IDEC (4332) • Fax: 408-745-5258 • www.IDEC.com/usa