13 SERIES MOULDED CASE
CURRENT TRANSFORMERS
DESCRIPTION
A range of compact low cost moulded case
current transformers suitable for primary
currents from 40A to 300A with built in
sealable terminal covers.
APPLICATION
For transforming various primary currents into
5A or 1A standard secondary using up to
20mm diameter cables.
FEATURES
• DIN rail mounting clip supplied.
• Built in sealable terminal covers.
• Mounting feet supplied.
• Narrow width - 45mm.
TECHNICAL SPECIFICATION
• Conforms to IEC185, BS 7626, BSEN 60044-1
and IEC 60044-1.
• Rated system voltage 0.72/3kV.
• Ambient temperature range -30°C to 85°C.
• Continuous current 1.2 x rated current.
Built in sealable terminal covers
RANGE
VA
40A
50A
60A
75A
80A
100A
120A
150A
200A
250A
300A
1
A1
B1
C1
D1
E1
F1
G1
H1
J1
K1
L1
DIMENSIONS (mm)
Class 3
1.5 2.5
5
1
–
B2
C2
D2
E2
F2
G2
H2
J2
K2
L2
–
–
–
–
–
–
–
H4
J4
K4
L4
–
B5
C5
D5
E5
F5
G5
H5
J5
K5
L5
–
–
–
D3
E3
F3
G3
H3
J3
K3
L3
Class 1
1.5 2.5
5
–
–
C6
D6
E6
F6
G6
H6
J6
K6
L6
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
– F9 F10 –
–
– G9 G10 G11 –
– H9 H10 H11 –
J8 J9 J10 J11 –
K8 K9 K10 K11 K12
L8 L9 L10 L11 L12
–
–
–
–
–
F7
G7
H7
J7
K7
L7
1
Class 0.5
1.5 2.5 5
45
30
21
65
27
1A secondary available by request.
Order Example: A moulded case current transformer type 13, with 5A
secondary and 200A primary 2.5VA class 1 is part number 13-5-J7
Our policy is one of continuous development and therefore specifications may change without notice.
HOWARD BUTLER LTD
CROWN WORKS, LINCOLN ROAD
WALSALL WS1 2EB ENGLAND
Tel: 01922 640003 Fax: 01922 723626
International Tel: +44 1922 640003
E-mail: sales@hobut.co.uk