AC Power Transducer
DIN RAIL / PANEL MOUNT, ACTIVE / REACTIVE
The CR6200 Series, Power Transducers and Transmitters are
designed to provide a controlled output that is proportional to
the average power. These devices are specifically targeted to
provide an efficient solution to most power sensing needs.
Units are designed for operation in systems with sinusoidal
voltage and current wave forms.
Applications
Energy Management
Motor Efficiency
Multi-point power sensing
Remote power sensing over long distances
CR6210 CR6211
CR6220 CR6221
Features
35mm DIN Rail or Panel Mount
Ranges available for any power sensing need
Active and Reactive power sensing
0 - 5 VDC and 4 - 20 mADC outputs
Connection diagram printed on case
Transducers
C
Regulatory Agencies
Approved to UL3111-1, First Edition, Amendment 2
Approved to CAN/CSA-C22.2, No. 1010.1-92
Meets requirement of IEC 61010-1 and BS EN 61010-1
CR6230 CR6231
CR6240 CR6241
E199795
CR6250 CR6251
CR6260 CR6261
V
CR Magnetics has a wide selection of
current and potential transformers to
extend the range of any part.
See Sections G & H for details.
I
- ACTIVE POWER
- REACTIVE POWER
POWER TRANSDUCERS CAN BE ORDERED
TO MEASURE ACTIVE OR REACTIVE POWER
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
Another HUNTINGTON ELECTRIC Company
46
E-mail: sales@crmagnetics.com
AC Power Transducer
DIN RAIL / PANEL MOUNT, ACTIVE / REACTIVE
Add suffix for input range
-
PART NUMBERS
CR6210
CR6211
CR6220
CR6221
CR6230
CR6231
CR6240
CR6241
CR6250
CR6251
CR6260
CR6261
-
-
1 Phase, Active Power with 0 - 5 VDC Output
1 Phase, Reactive Power with 0 - 5 VDC Output
1 Phase, Active Power with 4 - 20 mADC Output
1 Phase, Reactive Power with 4 - 20 mADC Output
3-Phase, 3-Wire, Active Power with 0 - 5 VDC Output
3-Phase, 3-Wire, Reactive Power with 0 - 5 VDC Output
3-Phase, 3-Wire, Active Power with 4 - 20 mADC Output
3-Phase, 3-Wire, Reactive Power with 4 - 20 mADC Output
3-Phase, 4-Wire, Active Power with 0 - 5 VDC Output
3-Phase, 4-Wire, Reactive Power with 0 - 5 VDC Output
150
250
500
0-150 VAC
0-250 VAC
0-500 VAC *
-
other ranges available
* not UL recognized
5
20
50
-
0-5 AAC
0-20 AAC
0-50 AAC
3-Phase, 4-Wire, Active Power with 4 - 20 mADC Output
3-Phase, 4-Wire, Reactive Power with 4 - 20 mADC Output
C
SPECIFICATIONS
Cleaning:................. Water-dampened cloth
Relative Humidity:... 80% for temperatures up to
31°C and decreasing linearly to 50% at 40°C
Supply Current:
CR6210:......................Typical 35mA
Max 45mA
CR6220:
Typical 75mA
Max 110mA
CR6230:......................Typical 50mA
Max 70mA
CR6240:
Typical 75mA
Max 110mA
CR6250:......................Typical 50mA
Max 70mA
CR6260:
Typical 75mA
Max 120mA
Torque Specs.:................ 3.0 inch lbs. (0.4Nm)
Weight:.............................0.5 lbs.
2.874
(73)
1.42
(36)
0.79 1.22 Sp
(20) (31) D
0.14
(3.5)
1
2
9
3
8
4
7
1.06
(26.8)
2.99 3.86 Sp
(76) (98)
6
5
2.874
(73)
0.79 1.22
( ) (31)
1.42
0.20
(5.1)
3.268
(83)
(36)
1 hole: 0.79(20) Dia. for CR6210, 6211, 6220 & 6221 (shown)
2 holes: 0.26(6.5) Dia. for CR6230, 6231, 6240, & 6241
3 holes: 0.26(6.5) Dia. for CR6250, 6251, 6260 & 6261
OUTLINE DRAWING
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
Another HUNTINGTON ELECTRIC Company
47
E-mail: sales@crmagnetics.com
Transducers
Basic Accuracy:......................... 0.5%
Thermal Drift:............................ 500 PPM/°C
Operating Temperature:............ 0°C to +60°C
Installation Category:................. CAT II
Pollution Degree:........................2
Response Time: ....................... 250 ms max. 0-90% FS
Supply Voltage:......................... 12 to 24 VDC
MTBF:............................... Greater than 100 K hours
Frequency Range:................. 50 Hz - 400 Hz, sine wave
Insulation Voltage:................. 2500 VDC
Altitude:................................. 2000 meter max.
Output Load:............ 4-20 mADC -0 to 300 Ω
0-5 VDC - 2K Ω or Greater
AC Power Transducer
DIN RAIL / PANEL MOUNT, AVERAGE SENSING
N L1
N L1
1
2
3
4
7
6
5
+ -
-
+
1
2
3
4
OUTPUT 1
9
8
9
8
OUTPUT 1
7
6
+
LOAD
Supply
LOAD
CR6210
CR6211
CR6220
Single element, 0 - 5 VDC Output
Transducers
C
CR6210
CR6211
L1
L2
CR6221
Single element, 4 - 20 mADC Output
CR6220
Single element, 0 - 5 VDC Output
with external voltage transformers
CR6221
Single element, 4 - 20 mADC Output
with external voltage transformers
L3
L1
L2
1
2
8
7
9
3
4
OUTPUT 1
-
+ -
5
CR6231
SUPPLY
CR6240
3 element - 3 Wire, 0 - 5 VDC Output
+
8
7
6
LOAD
SUPPLY
LOAD
CR6230
2
+ -
6
5
L3
1
OUTPUT 1
9
3
4
L1
-
5
SUPPLY
CR6241
3 element - 3 Wire, 4 - 20 mADC output
L3
L2
1
2
3
4
OUTPUT 1
9
8
7
6
5
+
-
SUPPLY
LOAD
CR6230
CR6231
CR6240
3 element - 3 Wire, 0 - 5 VDC Output
with external voltage and
current transformers
L1
L2
L3
3 element - 3 Wire, 4 - 20 mADC Output
with external current transformer
L1
N
1
2
3
4
9
8
7
6
5
L2
L3
N
1
2
3
4
OUTPUT 1
+
CR6241
-
+
9
8
7
6
5
SUPPLY
OUTPUT 1
+
-
SUPPLY
LOAD
LOAD
CR6250
CR6251
3 element - 4 Wire, 0 - 5 VDC Output
shown with external voltage and
current transformers
CR6260
CR6261
3 element - 4 Wire, 4 - 20 mADC Output
shown with external current transformers
CONNECTION DIAGRAMS
CR Magnetics, Inc. 3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
Another HUNTINGTON ELECTRIC Company
48
E-mail: sales@crmagnetics.com