NH Low Voltage Industrial Fuse Links
SIZE: 00 CLASS: aM
500Vac
DIMENSIONAL DATA ON PAGE 33
• For the protection of motor circuits
• Partial range breaking capacity
• Rated at 500Vac to IEC 60269-2-1 (VDE 0636)
• VDE Licence Mark
• Other voltage ratings available,
contact Bussmann for further information
1
2
3
23
FUSE LINK SELECTION TABLE
Rated Current
Part Number
Watts loss (W)
63
63NH00M
4.6
80
80NH00M
6.8
100
100NH00M
7.5
Breaking Capacity
120kA @ 500V ac
Weight
0.130 kg
Packaging
3 pcs per
Carton
FUSEHOLDER SELECTION TABLE FOR SIZE 00 FUSE LINKS
No.Poles
Part Number
Material
Max Rated
Current
Max Watts
Loss of Fuse Link
Weight
Packaging
1
SB00
Fibreglass
160A
12W
0.130 kg
3 per box
1
SBS00
Steatite
160A
12W
0.280 kg
1 per box
3
TB00
Fibreglass
160A
12W
0.500 kg
1 per box
FUSE SWITCH-DISCONNECTOR SELECTION TABLE FOR SIZE 00 FUSE LINKS
No.Poles
Part Number
1
LBS00/1
3
LBS00/3
Max Rated Current
of Fuse Links
Rated
Voltage
Max Watts
Loss of Fuse Link
Weight
Packaging
160A
690V ac
12W
0.720 kg
1 per Box
For more information visit our website at www.bussmann.com
NH Low Voltage Industrial Fuse Links: Performance Data
SIZE: 00 CLASS: aM 500Vac
Electrical Characteristics
Time Current Characteristics
104
103
PRE-ARCING TIME IN SECONDS
102
10
1
10-1
10-2
10-3
10-4
10
100
1000
10000
RMS SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
I2t CHARACTERISTICS
I2 t (A2 S)
Bussmann
Part Number
Rated Current
RMS-Amps
Pre Arcing at 500Vac
20 x In at 500Vac
63NH00M
63
1700
35000
75000
80NH00M
80
3400
50000
110000
100NH00M
100
16800
100000
190000
I1 120kA at 500Vac
For more information visit our website at www.bussmann.com
24
很抱歉,暂时无法提供与“100NH00M”相匹配的价格&库存,您可以联系我们找货