NH Low Voltage Industrial Fuse Links
SIZE: C00 (000) CLASS: aM
500Vac
DIMENSIONAL DATA ON PAGE 33
• For the protection of motor circuits
• Partial range breaking capacity
• Rated at 500Vac to IEC 60269-2-1 (VDE 0636)
• VDE Licence Mark
• Other voltage ratings available,
contact Bussmann for further information
1
2
FUSE LINK SELECTION TABLE
Rated Current
Part Number
Watts loss (W)
4
4NHC00M
0.4
6
6NHC00M
0.5
8
8NHC00M
0.6
10
10NHC00M
0.6
12
12NHC00M
0.7
16
16NHC00M
0.9
20
20NHC00M
1.1
25
25NHC00M
1.4
32
32NHC00M
1.8
40
40NHC00M
2.4
50
50NHC00M
3.1
21
120kA @ 500V ac
Weight
0.130 kg
Packaging
3 pcs per
Carton
FUSEHOLDER SELECTION TABLE FOR SIZE C00 (000) FUSE LINKS
Part Number
Material
Max Rated
Current
Max Watts
Loss of Fuse Link
Weight
Packaging
1
SB00
Fibreglass
160A
12W
0.130 kg
3 per box
1
SBS00
Steatite
160A
12W
0.280 kg
1 per box
3
TB00
Fibreglass
160A
12W
0.500 kg
1 per box
No.Poles
3
Breaking Capacity
FUSE SWITCH-DISCONNECTOR SELECTION TABLE FOR SIZE C00 (000) FUSE LINKS
No.Poles
Part Number
1
LBS00/1
3
LBS00/3
Max Rated Current
of Fuse Links
Rated
Voltage
Max Watts
Loss of Fuse Link
Weight
Packaging
160A
690A ac
12W
0.720 kg
1 per Box
For more information visit our website at www.bussmann.com
NH Low Voltage Industrial FuseLinks: Performance Data
SIZE: C00 (000) CLASS: aM 500Vac
Electrical Characteristics
Time Current Characteristics
104
103
PRE-ARCING TIME IN SECONDS
102
10
1
10-1
10-2
10-3
10-4
10
100
1000
10000
RMS SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
I2t CHARACTERISTICS
I2 t (A2 S)
Bussmann
Part Number
Rated Current
RMS-Amps
Pre Arcing at 500Vac
4NHC00M
4
6NHC00M
6
8NHC00M
20 x In at 500Vac
I1 120kA at 500Vac
31
80
330
64
210
820
8
93
390
1500
10NHC00M
10
290
1100
3700
12NHC00M
12
290
1600
4900
16NHC00M
16
700
2100
6900
20NHC00M
20
860
2700
8300
25NHC00M
25
1300
3700
11000
32NHC00M
32
3000
8000
21000
40NHC00M
40
6000
12000
32000
50NHC00M
50
10000
20000
47000
For more information visit our website at www.bussmann.com
22
很抱歉,暂时无法提供与“20NHC00M”相匹配的价格&库存,您可以联系我们找货