SmartPro LCD 120V 50/60Hz 1500VA 900W LineInteractive UPS, AVR, Tower, LCD, USB, 10
Outlets
Highlights
●
Supports a basic desktop PC up
to 90 min. during power outage
●
Features 10 protected
outlets—5 battery-protected, 5
surge-only
●
Offers automatic voltage
regulation (AVR)
●
LCD screen reports real-time
UPS and power status
●
Plugs into any NEMA 5-15R
socket
MODEL NUMBER: SMART1500LCDT
Package Includes
Provides reliable 1500VA/900W power protection for your desktop computer, network workstation,
audio/video components or media center. Protects against surges, line noise, blackouts and brownouts.
Description
The SMART1500LCDT SmartPro LCD 120V, 1500VA/900W Line-Interactive Uninterruptible Power
Supply provides battery backup and AC power protection against blackouts, brownouts, power surges and
line noise that can damage electronics or destroy data. Ideal for backing up your desktop computer or
audio/visual components, this line-interactive UPS switches to battery backup mode in milliseconds to
keep your connected equipment running long enough to save files and shut down safely with no data loss.
While all ten NEMA 5-15R outlets protect against surges, five outlets also provide up to 90 minutes of
UPS battery support for a basic desktop PC and LCD monitor and up to 10 minutes of support at half load
(450W).
Automatic voltage regulation (AVR) corrects undervoltages as low as 92V and overvoltages as high as
150V without using any battery power. EMI/RFI noise filtering improves your equipment's performance
and prevents damage. A 650-joule surge suppression rating protects your equipment from harmful power
surges.
NEMA 5-15P plug with 6-ft. (1.83 m) cord connects to any NEMA 5-15R socket. Large LCD screen shows
real-time input voltage, overload, AVR, remaining battery runtime and battery statuses at a glance. Alarm
sounds to indicate power loss or low battery. With Tripp Lite's PowerAlert software (available via free
download), SMART1500LCDT enables safe unattended system shutdown and file saves in case of a
prolonged power failure.
Features
Reliable Battery BackupProvides 1500VA/900W high-performance power protection for desktop
computers, audio/video components, media centers and other electronicsSupports basic desktop
computer and LCD monitor up to 90 minutes during power outageSupports 50% load (450W) up to 10
minutesAudible alarm indicates loss of utility power or low battery
Optimized Outlets5 NEMA 5-15R outlets deliver battery backup for devices that require constant
powerAll 10 outlets protect against surges or spikes that can harm equipment or dataNEMA 5-15P plug
with 6-ft. (1.83 m) cord connects to any NEMA 5-15R socket
Automatic Voltage Regulation (AVR)Corrects undervoltages as low as 92V and overvoltages as high as
150V without drawing battery backup power
1/5
●
SMART1500LCDT SmartPro
LCD 120V 1500VA/900W LineInteractive UPS
●
USB cable
●
Owner’s Manual
1000 Eaton Boulevard
Cleveland, OH 44122
United States
LCD Status ScreenLarge LCD screen shows real-time input voltage, overload, AVR and battery
statusesAutomatically displays remaining battery runtime in minutes during power outage
AC Line, Tel/DSL and Ethernet Surge SuppressionSurge suppression rating of 650 joules protects
connected equipment and data from harmful power surgesTel/DSL RJ11 jacks protect standard dialup/DSL/Ethernet phone connectionCoaxial jacks protect CATV, broadband cable internet, satellite or
broadcast antenna connection
EMI/RFI Line Noise FilteringRemoves electromagnetic and radio frequency interference that can disrupt
or damage your equipment's performance
USB Communication Port and Free PowerAlert SoftwareHID-compliant USB port integrates with builtin power management and auto-shutdown of Windows and Mac OS XUSB port enables data-saving
unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from
tripplite.eaton.com/products/power-alert
Specifications
OVERVIEW
UPC Code
037332174109
UPS Type
Line-Interactive
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
12A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-15P
Input Circuit Breakers
20A
UPS Input Cord Length (ft.)
6
UPS Input Cord Length (m)
1.8
Recommended Electrical Service
15A 120V
OUTPUT
Output Capacity (VA)
1500
Output Capacity (kVA)
1.5
Output Capacity (Watts)
900
Output Capacity (kW)
0.9
Nominal Voltage Details
120v nominal output in battery mode
Frequency Compatibility
50 / 60 Hz
Frequency Compatibility Details
Automatic frequency selection
Output Voltage Regulation (Line
Mode)
120V (+9% / -12%)
2/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Output Voltage Regulation (Battery
Mode)
120V (±10%)
UPS Output Receptacles (Surge
Suppression Only)
5 UPS outlets, 5 surge-only outlets
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery
Mode)
PWM sine wave
Nominal Output Voltage(s)
Supported
110V; 115V; 120V
Output Receptacles
(10) 5-15R
Individually Controllable Load Banks
No
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
2.3 min. (900W)
Runtime Half Load (min.)
10 min. (450W)
Expandable Runtime
No
DC System Voltage (VDC)
24
Battery Recharge Rate (Included
Batteries)
Less than 8 hours from 10% to 90%
Internal UPS Replacement Battery
Cartridge
RBC51 (requires 2)
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 92 to 150
Overvoltage Correction
Input voltages between 129 and 147 are reduced by 15%
Undervoltage Correction
Input voltages between 92 and 108 are boosted by 18%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
LCD screen with scroll buttons indicates Input voltage, Output voltage, Frequency (Hz), AVR boost / cut status,
Output load in watts, Output load percentage, Battery voltage and Estimated runtime in minutes
Switches
Power switch offers whole UPS power control; Scroll/mute button enables LCD selection options and silences
audible alarm; Test button initiates self test
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Audible alarm indicates power-failure and low-battery conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
650
UPS AC Suppression Response
Time
Instantaneous
UPS Dataline Suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet; Coax jacks (1 set)
EMI / RFI AC Noise Suppression
Yes
3/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
PHYSICAL
Primary Form Factor
Tower
Cooling Method
Fan
Installation Form Factors Supported
with Included Accessories
Tower
Primary UPS Depth (mm)
391
Primary UPS Height (mm)
203
Primary UPS Width (mm)
146
Shipping Dimensions (hwd / in.)
11.10 x 9.00 x 19.30
Shipping Weight (lbs.)
28.00
Shipping Weight (kg)
12.70
UPS Power Module Dimensions
(hwd, cm)
20.32 x 14.60 x 39.12
UPS Power Module Dimensions
(hwd, in.)
8 x 5.75 x 15.4
UPS Power Module Weight (kg)
12.25
UPS Power Module Weight (lbs.)
27
Unit Weight (lbs.)
25.3300
Unit Weight (kg)
11.49
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
119
Battery Mode BTU / Hr. (Full Load)
867
AC Mode Efficiency Rating (100%
Load)
95%
Audible Noise
Less than 36 dB, front side 1m
COMMUNICATIONS
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
For local monitoring via the UPS’s built-in USB port, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
USB and cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card
Description
Network management not supported
4/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Communications Interface
USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time
2 milliseconds (AC to battery mode), 6 milliseconds (battery to AC mode)
Low Voltage Transfer to Battery
Power (Setpoint)
92
High Voltage Transfer to Battery
Power (Setpoint)
150
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Automatic Voltage Regulation (AVR); Hot swappable batteries; Surge/noise protection
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS
STANDARDS & COMPLIANCE
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Product Compliance
RoHS; FCC Part 15 Class A (USA)
WARRANTY & SUPPORT
Product Warranty Period (U.S. &
Canada)
3-year limited warranty
Product Warranty Period
(International)
2-year limited warranty
Product Warranty Period (Mexico)
3-year limited warranty
Product Warranty Period (Puerto
Rico)
3-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
© 2023 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
5/5