1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton Tripp Lite series SmartOnline 120V 1.5kVA
1.35kW Double-Conversion UPS, Tower,
Extended Run, Network Card Options, LCD, USB,
DB9
MODEL NUMBER: SU1500XLCD
Highlights
●
1500VA / 1.5kVA / 1350 watt
on-line double-conversion tower
UPS
●
100/110/120/127V 50/60Hz
output, 97% efficiency economy
mode option
●
Interactive LCD with 10
selectable screens of UPS and
site power data
●
USB, RS232 & EPO ports, slot
for network management card
options
●
Expandable runtime, Hotswappable batteries
●
2 independently switchable load
banks
●
NEMA 5-15P input; 6 5-15R
outlets
●
To use the Auto Probe feature,
this product requires a
WEBCARDLX network interface
(sold separately) running LX
firmware update 15.5.2 or later
Package Includes
Description
Do you need to protect small- to medium-size servers, networking equipment and telecom systems
against data loss, downtime and equipment damage due to power outages, voltage fluctuations and
transient surges? Tripp Lite’s SU1500XLCD SmartOnline® Tower UPS System is the solution! Featuring a
1500VA/1350W capacity and true on-line operation with pure sine wave output and zero transfer time to
battery, it provides the highest level of power protection for mission-critical equipment. The
SU1500XLCD’s large internal battery set supports connected equipment during blackouts, and runtime is
expandable with optional external battery packs BP48V60RT-3U and BP48V27-2US, sold separately. The
SU1500XLCD has 6 5-15R outlets, including 2 load banks of 3 outlets each that are individually
controllable to reboot select equipment on demand or maximize battery runtime for mission-critical
equipment. USB and DB9 communication ports support messaging of detailed UPS operational
parameters and line power status. PowerAlert UPS management software is available via free download.
The SU1500XLCD also accepts an optional network management card. It comes backed by $250,000 of
Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).
Features
Ideal for Protection of Mission-Critical EquipmentThe SU1500XLCD provides true on-line operation,
reliable battery backup and comprehensive power management capability in a compact tower form factor.
Featuring a 1500VA/1350W capacity, 6 5-15R outlets, a 10-ft. cord with standard 5-15P plug, USB/DB9
ports and a slot for an optional network management card, SU1500XLCD offers a complete power
protection solution for small- to medium-size servers, storage devices, telecom systems and other
mission-critical equipment.
True On-Line Operation with Pure Sine Wave Output and Zero Transfer TimeThe SU1500XLCD
provides the highest level of protection available for mission-critical equipment. It actively converts raw
incoming AC power to DC, then re-converts it back to regulated, filtered AC output with a pure sine wave,
completely isolating connected components from all power problems. Zero transfer time between AC and
battery operation maintains continuous output and further protects connected equipment from the
disruptive effects of blackouts and severe low-voltage conditions. Sine wave output guarantees
compatibility with all equipment types.
Individually Controllable OutletsThe SU1500XLCD includes 2 load banks of 3 outlets each that are
1/7
●
SU1500XLCD SmartOnline®
Tower UPS System
●
USB, DB9 and EPO Cabling
●
Owner’s Manual
1000 Eaton Boulevard
Cleveland, OH 44122
United States
individually controllable via a software interface for remote reboot of locked-up equipment or load
shedding to maximize battery backup time for mission-critical equipment.
Reliable, Expandable Battery BackupUPS battery backup keeps connected equipment operational
through short power failures, and provides time to save data and perform an orderly system shutdown in
case of a prolonged blackout. The SU1500XLCD features a large internal battery set that provides 14
minutes of battery support for a half load (675 watts) and 4.5 minutes for a full load (1350 watts).
Intelligent battery management system extends battery life. During normal operation, incoming utility
power keeps the UPS battery fully charged so that backup power will always be available if needed. For
mission-critical applications demanding continuous uptime, the fully scalable SU1500XLCD can provide
expandable runtime with optional external battery packs BP48V60RT-3U and BP48V27-2US, sold
separately.
High Power Factor and Highly Efficient Operation Reduces BTU OutputThe SU1500XLCD features a
high 0.9 power factor and an optional, highly efficient economy mode setting that can significantly reduce
a facility’s energy costs. In economy mode, the UPS operates with 97% efficiency, minimizing heat output,
reducing cooling requirements and consuming less electricity.
AC Line and Tel/Ethernet Surge SuppressionA sudden power surge or spike can damage or destroy
electronic components and wipe out irreplaceable data. The SU1500XLCD features a 570-joule surge
suppression rating to protect connected components and data from the harmful effects of power surges.
One set of tel/Ethernet (RJ45) jacks provides surge protection for a standard phone or network connection
(cable not included).
EMI/RFI Line Noise FilteringVarious electrical and radio sources can cause disruptive interference on
the AC line. This line noise is a common cause of incremental hardware damage, data corruption and
audio/video performance problems. The SU1500XLCD incorporates technology that filters out disruptive
line noise, preventing it from affecting your equipment.
LCD Screen and Audible AlarmThe SU1500XLCD features a front-panel LCD screen that enables IT
personnel to monitor line power, on-line mode, bypass mode, on-battery, overload, battery low, replace
battery and fault status information. It is supplemented by an audible alarm that signals UPS startup,
power failure, low battery, overload, UPS fault and remote shutdown conditions.
USB/DB9 Ports, SNMP Capability and Included PowerAlert SoftwareSU1500XLCD includes HIDcompliant USB interface that enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X. USB and DB9 ports enable data-saving unattended shutdown when
used with Tripp Lite's PowerAlert software, available via FREE download from
tripplite.eaton.com/products/power-alert. Compatible with Tripp Lite UPS management card options
TLNETCARD, WEBCARDLX, SNMPWEBCARD, MODBUSCARD and RELAYIOCARD.
Emergency Power Off (EPO) CapabilityThe SU1500XLCD features an EPO interface port that supports
emergency shutoff in large facilities (cable included).
Peace of MindThe SU1500XLCD comes with $250,000 Ultimate Lifetime Insurance (U.S., Canada, and
Puerto Rico only) for connected equipment.
Specifications
OVERVIEW
UPC Code
037332174642
UPS Type
On-Line
INPUT
Input Phase
Single-Phase
2/7
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Rated input current (Maximum Load)
12A
Nominal Input Voltage(s) Supported
100V AC; 110V AC; 120V AC; 127V AC
Nominal Input Voltage Description
120V factory default
UPS Input Connection Type
5-15P
Input Circuit Breakers
15A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
15A 120V
OUTPUT
Output Capacity (VA)
1500
Output Capacity (kVA)
1.5
Output Capacity (Watts)
1350
Output Capacity (kW)
1.35
Output Capacity Details
ON LINE MODE: Maximum output capacity rating is reduced to 1215W (115V), 1148W (110V) and 1080W (100V);
FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation
/ conversion mode (127/120V 945 watts, 115V 851 watts, 110V 804 watts, 100V 756 watts).
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Power Factor
0.9
Crest Factor
3:1
Nominal Voltage Details
120V default
Frequency Compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
when input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
BATTERY MODE: Output is regulated to +/-0.05Hz of selected nominal.
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Load Management Receptacles
Two switchable three-outlet load banks
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery
Mode)
Pure Sine wave
Nominal Output Voltage(s)
Supported
100V; 110V; 115V; 120V; 127V
Output Receptacles
(6) 5-15R
3/7
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Individually Controllable Load Banks
Yes
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
4.5 min. (1350W)
Runtime Half Load (min.)
14 min. (675W)
Expandable Runtime
Yes
Expandable Runtime Description
External battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual
for details
External Battery Pack Compatibility
BP48V27-2US (multi-pack compatible); BP48V60RT-3U (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included
Batteries)
Less than 3 hours from 10% to 90% (typical, full load discharge)
Battery Access
Battery access door
Internal UPS Replacement Battery
Cartridge
RBC48-SUTWR
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Online, double-conversion power conditioning
Overvoltage Correction
2% output voltage regulation during overvoltages to 150
Undervoltage Correction
2% output voltage regulation during undervoltages to 55V (33% load), 70V (70% load), 100V (100% load)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options
Switches
2 switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
UPS Dataline Suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
4/7
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Primary Form Factor
Tower
Cooling Method
Fan
Installation Form Factors Supported
with Included Accessories
Tower
Primary UPS Depth (mm)
495
Primary UPS Height (mm)
259
Primary UPS Width (mm)
229
Shipping Dimensions (hwd / in.)
14.80 x 12.90 x 23.30
Shipping Dimensions (hwd / cm)
37.59 x 32.77 x 59.18
Shipping Weight (lbs.)
55.00
Shipping Weight (kg)
24.95
UPS Housing Material
Steel
UPS Power Module Dimensions
(hwd, cm)
25.91 x 22.86 x 49.53
UPS Power Module Dimensions
(hwd, in.)
10.2 x 9 x 19.5
UPS Power Module Weight (kg)
23.72
UPS Power Module Weight (lbs.)
52.3
Unit Weight (lbs.)
48.5000
Unit Weight (kg)
22.00
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
512
AC Economy Mode BTU / Hr. (Full
Load)
142
Battery Mode BTU / Hr. (Full Load)
814
AC Mode Efficiency Rating (100%
Load)
90%
AC Economy Mode Efficiency Rating
(100% Load)
97%
Audible Noise
< 50.5 dB at front side 1m
Operating Elevation (m)
Up to 3000m
COMMUNICATIONS
5/7
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Network Management Cards
SNMPWEBCARD; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card
Description
Network management card optional
Communications Interface
Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time
Zero transfer time (0 ms.) in online, double-conversion and frequency regulation / conversion modes
Low Voltage Transfer to Battery
Power (Setpoint)
55V (33% load), 70V (70% load), 100V (100% load)
High Voltage Transfer to Battery
Power (Setpoint)
150
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring and Reboot (requires WEBCARDLX); Automatic inverter bypass; Hot swappable batteries;
Remote management; Surge/noise protection; Zero transfer time
Green Energy-Saving Features
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation
STANDARDS & COMPLIANCE
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Product Compliance
RoHS; FCC Part 15 Class A (USA)
WARRANTY & SUPPORT
Product Warranty Period
(Worldwide)
2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
6/7