1000 Eaton Boulevard
Cleveland, OH 44122
United States
SmartPro 120V 2200VA 1.92kW Line-Interactive
Sine Wave UPS, 2U, Extended Run, Network
Card Options, LCD, USB, DB9
Highlights
●
2.2kVA / 2200VA / 1920W line
interactive 2U rack/tower UPS,
Sine Wave output
●
120V output, Corrects
brownouts and overvoltages
from 83V to 145V
●
Interactive LCD interface, 4 post
compatible mounting
accessories
●
96% line-mode efficiency, 2
switched load banks
●
USB, RS232, EPO and slot for
Network Management Card
options
●
120V NEMA 5-20P input, 4
NEMA 5-15R, 4 NEMA 515/20R & 1 L5-20R outlets
●
To use the Auto Probe feature,
this product requires a
WEBCARDLX network interface
(sold separately) running LX
firmware update 15.5.2 or later
MODEL NUMBER: SMART2600RM2U
Package Includes
Description
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power
protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible
Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and
overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp
Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of
voltage boost to correct both slight undervoltages and severe brownout conditions. Interactive LCD
interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS
setup and configuration options. Super-fast switchover from line to battery power occurs within
milliseconds to maintain operation of connected equipment without interruption or reboot. 96% line-mode
efficiency offers reduced heat emissions and operating costs. Network management interfaces support
communications via USB, RS-232 and installed Network Management Card option. HID-compliant USB
interface enables integration with built-in power management and auto shutdown features of Windows and
Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test
data and utility power conditions. PowerAlert UPS monitoring software is available via free download.
Switched output load banks enable scheduled and real-time remote reboot and load shedding of select
outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount
or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode
configuration options. Programmable self-test. Field-replaceable, hot-swappable battery modules.
Features
●
Tripp Lite SMART2600RM2U line interactive 2U rack/tower UPS with 2200VA / 2.2kVA / 1920W
capacity and extended runtime options
●
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages
from 83 to 145V
●
NEMA 5-20P input plug; 4 NEMA 5-15/20R, 4 5-15R and 1 L5-20R output receptacles, Two
independently switched output load banks
●
Maintains uninterrupted operation of connected networking equipment during blackouts, surges,
brownouts and overvoltages
●
High 96% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
●
Internal batteries offer 12.9 minutes at 50% load (960W) and 4.6 minutes at 100% load (1920W)
●
Extended runtime is available with optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack
1/6
●
SMART2600RM2U UPS system
●
USB, Serial & EPO cabling
●
4 post installation kit
●
Owner's manual
1000 Eaton Boulevard
Cleveland, OH 44122
United States
compatible) and BP48V27-2US (multi-pack compatible)
●
External battery configurations require the use of Tripp Lite's External Battery Configuration Software
(see manual)
●
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no
disruption to connected equipment
●
Intelligent battery management system extends battery life
●
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar
battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
●
LCD interface also supports a number of advanced user setup and operating preferences
●
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post
rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
●
Built-in USB, RS-232 and slot for Network Management Card option
●
Compatible with Tripp Lite UPS management card options TLNETCARD, WEBCARDLX,
SNMPWEBCARD and RELAYIOCARD
●
HID-compliant USB interface enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
●
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from tripplite.eaton.com/products/power-alert
●
Built-in Emergency Power Off (EPO) interface with cable
Specifications
OVERVIEW
UPC Code
037332116819
UPS Type
Line-Interactive
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
16A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-20P
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
20A 120V
OUTPUT
Output Capacity (VA)
2200
Output Capacity (kVA)
2.2
Output Capacity (Watts)
1920
Output Capacity (kW)
1.92
Power Factor
0.87
Nominal Voltage Details
120v nominal output in battery mode
2/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line
Mode)
-14%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Load Management Receptacles
Two switchable single-outlet 5-15R load banks
Output Circuit Breakers
15A breaker protects 5-15R, 20A breaker protects 5-15/20R, L5-20R is unbreakered
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery
Mode)
Pure Sine wave
Nominal Output Voltage(s)
Supported
110V; 115V; 120V
Output Receptacles
(4) 5-15R; (4) 5-15/20R; (1) L5-20R
Individually Controllable Load Banks
Yes
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
4.6 min. (1920W)
Runtime Half Load (min.)
12.9 min. (960W)
Expandable Runtime
Yes
External Battery Pack Compatibility
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V272US (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Battery Access
Front panel battery access door
Internal UPS Replacement Battery
Cartridge
RBC94-2U
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction
Input voltages between 127 and 147 are reduced by 12%
Undervoltage Correction
Input voltages between 95 and 104 are boosted by 12%
Severe Undervoltage Correction
Input voltages between 83 and 94 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
3/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Rackmount
Rack Height
2U
Cooling Method
Fan
Included Mounting Accessory
Description
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to
914mm)
Installation Form Factors Supported
with Included Accessories
4 post 19 inch rackmount
Installation Form Factors Supported
with Optional Accessories
2 post rackmount ( 2POSTRMKITWM ); 4 post
rackmount short-depth ( 4POSTRAILKITWM ); Tower
( 2-9USTAND ); Wallmount ( 2POSTRMKITWM )
Minimum Required Rack Depth (cm)
58.42
Minimum Required Rack Depth
(inches)
23
Minimum Required Rack Depth with
External Battery Pack (cm)
67
Minimum Required Rack Depth with
External Battery Pack (in.)
26.5
Minimum Required Rack Depth
without External Battery Pack (cm)
62
Minimum Required Rack Depth
without External Battery Pack (in.)
24.5
Optional Mounting Accessory Notes
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation;
4POSTRAILKITWM enables installation in 4-post short-depth
racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post
racks using front vertical rails only, without rear support
4/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Primary UPS Depth (mm)
494
Primary UPS Height (mm)
88
Primary UPS Width (mm)
440
Shipping Dimensions (hwd / in.)
9.00 x 24.10 x 22.00
Shipping Dimensions (hwd / cm)
22.86 x 61.21 x 55.88
Shipping Weight (lbs.)
81.10
Shipping Weight (kg)
36.79
UPS Housing Material
Steel
UPS Power Module Dimensions
(hwd, cm)
8.79 x 43.99 x 49.43
UPS Power Module Dimensions
(hwd, in.)
3.46 x 17.32 x 19.46
UPS Power Module Weight (kg)
29.03
UPS Power Module Weight (lbs.)
64
Unit Weight (lbs.)
64.0000
Unit Weight (kg)
29.03
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
250
Battery Mode BTU / Hr. (Full Load)
980
AC Mode Efficiency Rating (100%
Load)
96%
Audible Noise
45 dBA maximum, front side 1m
COMMUNICATIONS
Network Management Cards
SNMPWEBCARD; TLNETCARD ; WEBCARDLX ; RELAYIOCARD
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card
Description
Network management card optional
Communications Interface
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
5/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
LINE / BATTERY TRANSFER
Transfer Time
5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
Low Voltage Transfer to Battery
Power (Setpoint)
83
High Voltage Transfer to Battery
Power (Setpoint)
145
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring and Reboot (requires WEBCARDLX); Automatic Voltage Regulation (AVR); Hot swappable
batteries; Remote management; Surge/noise protection
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
Grounding Lug
Back panel grounding lug
STANDARDS & COMPLIANCE
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Product Compliance
RoHS; FCC Part 15 Class A (USA)
WARRANTY & SUPPORT
Product Warranty Period
(Worldwide)
2-year warranty, 3 year with registration. Note: Registration is required for 3-year
warranty.
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
© 2023 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
6/6