1000 Eaton Boulevard
Cleveland, OH 44122
United States
TAA SmartPro 120V 2.2kVA 1.92kW LineInteractive Sine Wave UPS, 2U, Extended Run,
Network Card Options, LCD, USB, DB9
Highlights
●
2.2kVA / 2200VA / 1920W line
interactive 2U rack/tower UPS,
Sine Wave
●
Extended runtime options up to
1600W, 0.9 Power Factor,
Interactive LCD interface
●
USB, RS232, EPO and slot for
network communication card
options
●
120V NEMA 5-20P input, 4
NEMA 5-15R & 4 NEMA 515/20R outlets
●
TAA Compliant for GSA
Schedule purchases
●
To use the Auto Probe feature,
this product requires a
WEBCARDLX network interface
(sold separately) running LX
firmware update 15.5.2 or later
MODEL NUMBER: SM2200RMXL2UTAA
Package Includes
Description
The SM2200RMXL2UTAA is compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule
purchases. Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade
power protection for critical server, network and telecommunications equipment. Line Interactive
Uninterruptible Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects
brownouts and overvoltages back to usable levels while maintaining a full battery charge in case of power
failure. Tripp Lite's unique configuration excels in exceptionally poor-power environments with two
separate levels of voltage boost to correct both slight undervoltages and severe brownout conditions.
Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a
variety of UPS setup and configuration options. Super-fast switchover from line to battery power occurs
within milliseconds to maintain operation of connected equipment without interruption or reboot. 96% linemode efficiency offers reduced heat emissions and operating costs. Communications interfaces support
communications via USB, DB9 serial and a slot for an optional network management card. HID-compliant
USB port enables integration with built-in power management and auto shutdown features of Windows
and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, selftest data and utility power conditions. PowerAlert UPS monitoring and auto-shutdown software is available
via free download. Switched output load banks enable scheduled and real-time remote reboot and load
shedding of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for
viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel
and silent-mode configuration options. Programmable self-test. Field-replaceable, hot-swappable battery
modules.
Features
●
Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
●
Tripp Lite SMART2200RMXL2U line interactive 2U rack/tower UPS with 2200VA / 2.2kVA / 1920W
capacity and extended runtime optionsLine interactive UPS with Automatic Voltage Regulation (AVR)
corrects brownouts and overvoltages from 83 to 145V
●
NEMA 5-20P input plug; 4 NEMA 5-15/20R and 4 5-15R output receptacles, Two independently
switched output load banks
●
Maintains uninterrupted operation of connected networking equipment during blackouts, surges,
brownouts and overvoltages
●
High 96% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
●
Internal batteries offer 12 minutes at 50% load (960W) and 4.5 minutes at 100% load (1920W)
1/6
●
SM2200RMXL2UTAA TAA
Compliant UPS system
●
USB, Serial & EPO cabling
●
4 post installation kit
●
Owner's manual
1000 Eaton Boulevard
Cleveland, OH 44122
United States
●
Extended runtime is available with optional BP48V24-2U / BP48V242UTAA (limit 1) OR BP48V60RT3U
/ BP48V60RT3UTAA (no limit), Output is reduced to 1600 watts maximum with external battery packs
●
External battery configurations require the use of Tripp Lite's External Battery Configuration Software
(see manual)
●
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no
disruption to connected equipment
●
Following an extended power outage, the UPS will automatically restart into line-power mode, begin
powering connected equipment and recharge the battery system, all without user interaction
●
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar
battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
●
LCD interface also supports a number of advanced user setup and operating preferences
●
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post
rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
●
Communications interfaces support communications via USB, DB9 serial and slot for network
management card options; Compatible with Tripp Lite UPS management card options TLNETCARD,
WEBCARDLX and SNMPWEBCARD
●
HID-compliant USB port enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
●
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from tripplite.eaton.com/products/power-alert
●
Built-in Emergency Power Off (EPO) interface with cable
Specifications
OVERVIEW
UPC Code
037332152800
UPS Type
Line-Interactive
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
16A (120V)
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-20P
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
20A 120V
OUTPUT
Output Capacity (VA)
2200
Output Capacity (kVA)
2.2
Output Capacity (Watts)
1920
Output Capacity (kW)
1.92
Output Capacity Details
Output is reduced to 1600 watts maximum when used with external battery packs
2/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Power Factor
0.87
Nominal Voltage Details
120v nominal output in battery mode
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line
Mode)
-14%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Load Management Receptacles
Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery
Mode)
Pure Sine wave
Nominal Output Voltage(s)
Supported
110V; 115V; 120V
Output Receptacles
(4) 5-15R; (4) 5-15/20R
Individually Controllable Load Banks
Yes
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
4.5 min. (1920W)
Runtime Half Load (min.)
12 min. (960W)
Expandable Runtime
Yes
Expandable Runtime Description
Extended runtime supported via optional external battery packs; 1600 watts maximum load with external battery
packs
External Battery Pack Compatibility
BP48V24-2U (limit 1); BP48V242UTAA (limit 1); BP48V27-2US (multi-pack compatible); BP48V60RT-3U (multi-pack compatible); BP48V60RT3UTAA (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90%
Battery Access
Front panel battery access door
Internal UPS Replacement Battery
Cartridge
RBC94-2U
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction
Voltage reduction of 12% applies when input is between 127 and 145
Undervoltage Correction
Voltage boost of 12% applies when input voltage is between 96 and 108
3/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Severe Undervoltage Correction
Voltage boost of 24% applies when input voltage is between 83 and 95
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Switches
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Rackmount
Rack Height
2U
Cooling Method
Fan
Included Mounting Accessory
Description
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to
914mm)
Installation Form Factors Supported
with Included Accessories
4 post 19 inch rackmount
Installation Form Factors Supported
with Optional Accessories
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail
rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 29USTAND ); Wallmount ( 2POSTRMKITWM )
Minimum Required Rack Depth (cm)
55.88
Minimum Required Rack Depth
(inches)
22
Minimum Required Rack Depth with
External Battery Pack (cm)
66
Minimum Required Rack Depth with
External Battery Pack (in.)
26
Minimum Required Rack Depth
without External Battery Pack (cm)
62
Minimum Required Rack Depth
without External Battery Pack (in.)
24.5
4/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Optional Mounting Accessory Notes
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation;
4POSTRAILKITWM enables installation in 4-post short-depth
racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post
racks using front vertical rails only, without rear support
Primary UPS Depth (mm)
490
Primary UPS Height (mm)
88
Primary UPS Width (mm)
440
Shipping Dimensions (hwd / in.)
8.80 x 24.00 x 20.90
Shipping Dimensions (hwd / cm)
22.35 x 60.96 x 53.09
Shipping Weight (lbs.)
78.00
Shipping Weight (kg)
35.38
UPS Housing Material
Steel
UPS Power Module Dimensions
(hwd, cm)
8.79 x 43.99 x 49.00
UPS Power Module Dimensions
(hwd, in.)
3.46 x 17.32 x 19.29
UPS Power Module Weight (kg)
26.13
UPS Power Module Weight (lbs.)
57.6
Unit Weight (lbs.)
57.600
Unit Weight (kg)
26.13
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
306
Battery Mode BTU / Hr. (Full Load)
1157
Audible Noise
45 dBA maximum, front side 1m
COMMUNICATIONS
Network Management Cards
SNMPWEBCARD; TLNETCARD ; WEBCARDLX
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
5/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Network UPS Tools (NUT)
Compatibility
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stablehcl.html?manufacturer=Tripp%20Lite
Network Management Card
Description
Network management card optional
Communications Interface
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time
5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
Low Voltage Transfer to Battery
Power (Setpoint)
83
High Voltage Transfer to Battery
Power (Setpoint)
145
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring and Reboot (requires WEBCARDLX); Automatic Voltage Regulation (AVR); Hot swappable
batteries; Remote management; Surge/noise protection
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
Grounding Lug
Back panel grounding lug
STANDARDS & COMPLIANCE
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Product Compliance
RoHS; FCC Part 15 Class A (USA); Trade Agreements Act (TAA)
WARRANTY & SUPPORT
Product Warranty Period
(Worldwide)
2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
© 2023 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
6/6