1000 Eaton Boulevard
Cleveland, OH 44122
United States
SmartPro 120V 2.2kVA 1.92kW Line-Interactive
Sine Wave UPS, 2U Rack/Tower, Pre-Installed
WEBCARDLX Network Interface, LCD Display,
USB, DB9 Serial
MODEL NUMBER: SMART2200RM2UN
Highlights
●
2.2kVA / 2200VA / 1920W line
interactive 2U rack/tower UPS;
0.9 power factor
●
120V nominal output during
brownouts to 83V and
overvoltages to 145V
●
Interactive LCD provides UPS
status information and advanced
configuration options
●
Hot-swap batteries, 96%
efficiency, Sine wave output
●
USB, RS232 & EPO ports, PreInstalled WEBCARDLX Network
Interface
●
NEMA 5-20P input; 4 NEMA 515R & 4 5-15/20R outlets
●
To enable the Auto Probe
feature, this product requires LX
firmware update 15.5.2 or later
to be installed
Package Includes
●
SMART2200RM2UN UPS
system with WEBCARDLX
Network Interface
Description
●
USB, Serial & EPO cabling
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power
protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible
Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and
overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp
Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of
voltage boost to correct both slight undervoltages and severe brownout conditions. Interactive LCD
interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS
setup and configuration options. Super-fast switchover from line to battery power occurs within
milliseconds to maintain operation of connected equipment without interruption or reboot. 96% line-mode
efficiency offers reduced heat emissions and operating costs. Network management interfaces support
communications via USB port, DB9 serial port and pre-installed WEBCARDLX network management
interface card.
The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS
status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or
SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network.
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring
capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet,
SSH, FTP, DHCP and NTP.
HID-compliant USB port enables integration with built-in power management and auto shutdown features
of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load
levels, self-test data and utility power conditions. PowerAlert UPS monitoring software is available via free
download. Switched output load banks enable scheduled and real-time remote reboot and load shedding
of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in
rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silentmode configuration options. Programmable self-test. Field-replaceable, hot-swappable battery modules.
●
4 post rackmount installation kit
●
Instruction manual
Features
●
Tripp Lite SMART2200RM2UN line interactive 2U rack/tower UPS with 2200VA / 2.2kVA / 1920W
capacity
●
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages
from 83 to 145V
●
NEMA 5-20P input plug; 4 NEMA 5-15R & 4 NEMA 5-15/20R output receptacles, Two independently
1/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
switchable output load banks
●
Maintains uninterrupted operation of connected networking equipment during blackouts, surges,
brownouts and overvoltages
●
High 96% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
●
Internal batteries offer 12 minutes at 50% load (960W) and 4.5 minutes at 100% load (1920W)
●
Hot-swappable, user-replaceable internal batteries can be replaced with no disruption to connected
equipment
●
Intelligent battery management system extends battery life
●
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar
battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
●
LCD interface also supports a number of advanced user setup and operating preferences
●
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post
rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
●
Network interfaces support communications via built-in USB, DB9 serial / contact-closure and preinstalled WEBCARDLX network management card
●
WEBCARDLX interface allows full remote access for power monitoring, configuration, control and email
notifications via secure web browser, SNMP, telnet or SSH
●
Optional E2 sensors enable site monitoring of temperature, humidity and contact-closure status
●
Reduce Service Calls with Auto Probe Autonomous Device Management. Auto Probe feature (Firmware
15.5.2 and greater) of the LX Platform Interface checks the connectivity status of any networked device
and automatically takes one or more user-configured actions if the device fails to respond; actions
include outlet reboot, set SNMP traps, SNMP OID sets, and even script execution when used in
conjunction with the Tripp Lite PowerAlert Network Shutdown Agent (PANSA)
●
HID-compliant USB port enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
●
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from tripplite.eaton.com/products/power-alert
●
Built-in Emergency Power Off (EPO) interface with cable
Specifications
OVERVIEW
UPC Code
037332178015
UPS Type
Line-Interactive
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
16A (120V)
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-20P
Input Circuit Breakers
20A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
20A 120V
2/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
OUTPUT
Output Capacity (VA)
2200
Output Capacity (kVA)
2.2
Output Capacity (Watts)
1920
Output Capacity (kW)
1.92
Power Factor
0.87
Nominal Voltage Details
120v nominal output in battery mode
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line
Mode)
-14%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Load Management Receptacles
Two switchable single-outlet load banks
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery
Mode)
Pure Sine wave
Nominal Output Voltage(s)
Supported
110V; 115V; 120V
Output Receptacles
(4) 5-15R; (4) 5-15/20R
Individually Controllable Load Banks
Yes
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
4.5 min. (1920W)
Runtime Half Load (min.)
12 min. (960W)
Expandable Runtime
No
DC System Voltage (VDC)
48
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Battery Access
Front panel battery access door
Internal UPS Replacement Battery
Cartridge
RBC94-2U
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction
Input voltages between 127 and 145 are reduced by 12%
Undervoltage Correction
Input voltages between 108 and 96 are boosted by 12%
3/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Severe Undervoltage Correction
Input voltages between 83 and 95 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions. LX
Platform Interface: Recessed reset switch for interface reboot and factory reset
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
LED Indicators
Network Link/Activity (Green): Flashes for network activity. Network Speed (Yellow): 10 Mbps (Flashing), 100 Mbps
(On steady). LX Platform Interface Status: Normal Operation (Solid Green); Software Update (Alternating
Green/Orange ~1/sec); Factory Reset (Alternating Green/Orange ~2/sec).
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Rackmount
Rack Height
2U
Cooling Method
Fan
Included Mounting Accessory
Description
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to
914mm)
Installation Form Factors Supported
with Included Accessories
4 post 19 inch rackmount
Installation Form Factors Supported
with Optional Accessories
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail
rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 29USTAND ); Wallmount ( 2POSTRMKITWM )
Minimum Required Rack Depth (cm)
63.50
Minimum Required Rack Depth
(inches)
25
Optional Mounting Accessory Notes
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation;
4POSTRAILKITWM enables installation in 4-post short-depth
racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post
racks using front vertical rails only, without rear support
4/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Primary UPS Depth (mm)
494
Primary UPS Height (mm)
87
Primary UPS Width (mm)
440
Shipping Dimensions (hwd / in.)
8.80 x 24.00 x 21.80
Shipping Dimensions (hwd / cm)
22.35 x 60.96 x 55.37
Shipping Weight (lbs.)
77.00
Shipping Weight (kg)
34.93
UPS Housing Material
Steel
UPS Power Module Dimensions
(hwd, cm)
8.71 x 43.99 x 49.43
UPS Power Module Dimensions
(hwd, in.)
3.43 x 17.32 x 19.46
UPS Power Module Weight (kg)
26.13
UPS Power Module Weight (lbs.)
57.6
Unit Weight (lbs.)
57.5600
Unit Weight (kg)
26.11
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
306
Battery Mode BTU / Hr. (Full Load)
1157
AC Mode Efficiency Rating (100%
Load)
96%
Audible Noise
45 dBA maximum, front side 1m
COMMUNICATIONS
Network Management Cards
WEBCARDLX
Network Monitoring Port Description
Pre-installed WEBCARDLX Network Management Card interface
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
Micro-USB, USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
EPO Port
RJ11 interface jack with 4-meter cable included. Supports normally open and normally closed EPO systems
SNMP Compatibility
SNMP V1, V2c, V3
Network UPS Tools (NUT)
Compatibility
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stablehcl.html?manufacturer=Tripp%20Lite
5/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Network Management Card
Description
Network management card included
Communications Interface
DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface; USB (HID
enabled)
LINE / BATTERY TRANSFER
Transfer Time
5 milliseconds (AC to battery mode), 1 millisecond (Battery to AC mode)
Low Voltage Transfer to Battery
Power (Setpoint)
83
High Voltage Transfer to Battery
Power (Setpoint)
145
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring and Reboot (included); Automatic Voltage Regulation (AVR); Hot swappable batteries;
Remote management; Surge/noise protection
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
Grounding Lug
Back panel grounding lug
STANDARDS & COMPLIANCE
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Product Compliance
RoHS; FCC Part 15 Class A (USA)
WARRANTY & SUPPORT
Product Warranty Period
(Worldwide)
2-year warranty, 3 year with registration. Note: Registration is required for 3-year
warranty.
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
© 2023 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
6/6