1000 Eaton Boulevard
Cleveland, OH 44122
United States
Smart Pro Line Interactive Tower UPS System NAFTA assembled version of the SMART1500
MODEL NUMBER: SM1500NAFTA
Highlights
●
1500VA / 1.5kVA line interactive
tower UPS
●
Maintains 120V nominal output
over an input range of 75 to
147V
●
Network communications
supported via USB port, serial
port
●
Input: NEMA 5-15P (120V 15A)
/ Output: 6 NEMA 5-15R (120V)
●
$250,000 Ultimate Lifetime
Insurance (USA, Puerto Rico
and Canada only)
Package Includes
Description
Tripp Lite's SM1500NAFTA intelligent, line interactive UPS system protects servers, networking
accessories and telecommunications equipment from blackouts, voltage fluctuations and transient surges.
Large internal batteries offer 20 minutes half load runtime and 7 minutes at full load during power failures.
1500VA/980 watt power handling capability supports a variety of networking, telecom and various other
application types, including the support of multiple network workstations. Includes a total of 6 outlets, 1 of
which can be individually powered on and off via software interface to selectively reboot remote
equipment or to automatically shed less significant loads to extend battery runtime for more critical
equipment. Supports remote monitoring of UPS and site power conditions via built-in USB and DB9
monitoring ports. Includes PowerAlert UPS monitoring and unattended shutdown software with complete
cabling. Built-in audible alarm and 5 front panel LEDs indicate status of line power, battery power, battery
low/replace, voltage regulation and load level. Wall mountable with optional UPSWM wallmount bracket.
Network-grade AC surge suppression protects equipment from damage and performance problems
resulting from transient surges. Attractive, small-footprint tower housing uses less than 66 square inches
of floor or desktop space. $250,000 connected equipment insurance (USA and Canada Only).
Features
●
1500VA/980 watt power handling capability supports a variety of networking, telecom and various other
application types
●
Built-in voltage regulation and battery support, plus complete AC suppression prevents equipment
damage, data loss and downtime
●
Large internal batteries offer 20 minutes half load runtime and 7 minutes at full load during power
failures
●
Automatic Voltage Regulation (AVR) circuits with two boost and one voltage reduction level maintains
usable 120V nominal output over an input voltage range of 75-147V
●
Includes a total of 6 NEMA5-15R outlets, 1 of which can be individually powered on and off via software
interface to selectively reboot remote equipment or shed less significant loads to extend battery runtime
for more critical equipment
1/5
●
SM1500NAFTA UPS System
●
USB and DB9 monitoring cables
●
PowerAlert unattended
shutdown and UPS/Power
monitoring software
●
Instruction manual with warranty
information
1000 Eaton Boulevard
Cleveland, OH 44122
United States
●
Includes 1 USB and 1 DB9 monitoring port for remote monitoring of UPS status and site power
conditions
●
Communications ports enable safe unattended shutdown without data loss during extended power
failures
●
Communications ports support messaging of UPS and line power status, including on-battery, lowbattery, power-restored, AC line voltage, DC battery voltage and battery capacity
●
Communications ports support timed inverter shutoff after unattended shutdown, activate self-test and
10 second reboot of connected equipment
●
PowerAlert UPS monitoring and unattended shutdown software with complete cabling included
●
Supports Tripp Lite's WatchDog software application to restore unresponsive programs by automatically
restarting them and rebooting completely locked computers by automatically switching UPS power off
and back on again
●
Notification of system status via 5 LEDs and multi-function audible alarms
●
Wall mountable with UPSWM wallmount bracket
●
Attractive small footprint beige tower housing uses less than 66 square inches
●
Hot-swappable/user replaceable batteries allow on-site battery replacement
●
Cold start capability enables UPS turn-on in battery mode during blackout conditions
●
UL (USA), cUL (Canada), NOM (Mexico), Class A (Emissions)
●
$250,000 Ultimate Lifetime Insurance (USA and Canada only)
●
$250,000 connected equipment insurance (USA and Canada Only)
Specifications
OVERVIEW
UPC Code
037332137678
INPUT
Rated input current (Maximum Load)
12A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-15P
Input Circuit Breakers
15A
UPS Input Cord Length (ft.)
6
UPS Input Cord Length (m)
1.8
Recommended Electrical Service
15A 120V
OUTPUT
Output Capacity (VA)
1500
Output Capacity (kVA)
1.5
Output Capacity (Watts)
980
Power Factor
0.7
Frequency Compatibility
60 Hz
2/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Output Voltage Regulation (Line
Mode)
-18%, +8%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Load Management Receptacles
One switchable single-outlet 5-15R load bank
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery
Mode)
PWM sine wave
Nominal Output Voltage(s)
Supported
120V
Output Receptacles
(6) 5-15R
BATTERY
Runtime Full Load (min.)
7 min. (980w)
Runtime Half Load (min.)
20 min. (490w)
DC System Voltage (VDC)
36
Battery Recharge Rate (Included
Batteries)
Less than 4 hours from 10% to 90%
Battery Access
Battery access door
Internal UPS Replacement Battery
Cartridge
RBC53
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage Correction
Input voltages between 128 and 147 are reduced by 12%
Undervoltage Correction
Input voltages between 93 and 107 are boosted by 14%
Severe Undervoltage Correction
Input voltages between 75 and 92 are boosted by 30%
USER INTERFACE, ALERTS & CONTROLS
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate lowbattery status
Audible Alarm
Audible alarm indicates power-failure, overload and low-battery conditions
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
480
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
3/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
PHYSICAL
Primary Form Factor
Tower
Cooling Method
Fan
Installation Form Factors Supported
with Included Accessories
Tower
Installation Form Factors Supported
with Optional Accessories
Wallmount ( UPSWM - tower mounting kit)
Primary UPS Depth (mm)
229
Primary UPS Height (mm)
325
Primary UPS Width (mm)
191
Shipping Dimensions (hwd / in.)
18.25 x 12.00 x 13.75
Shipping Dimensions (hwd / cm)
46.36 x 30.48 x 34.92
Shipping Weight (lbs.)
42.60
Shipping Weight (kg)
19.32
UPS Housing Material
PVC
UPS Power Module Dimensions
(hwd, cm)
32.51 x 19.05 x 22.86
UPS Power Module Dimensions
(hwd, in.)
12.8 x 7.5 x 9
UPS Power Module Weight (kg)
17.42
UPS Power Module Weight (lbs.)
38.4
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
138.8
Battery Mode BTU / Hr. (Full Load)
454.4
AC Mode Efficiency Rating (100%
Load)
96%
COMMUNICATIONS
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
Included
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Communications Interface
USB; DB9 Serial
4/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
LINE / BATTERY TRANSFER
Transfer Time
2-4 milliseconds
Low Voltage Transfer to Battery
Power (Setpoint)
75
High Voltage Transfer to Battery
Power (Setpoint)
147
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Hot swappable batteries
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
WARRANTY & SUPPORT
Product Warranty Period
(Worldwide)
2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
© 2022 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
5/5