DF-G1 Expert™ Dual Display Fiber
Optic Light Receiver
Instruction Manual
Original Instructions
176768 Rev. D
9 September 2015
176768
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Contents
1 Product Description
........................................................................................................ 3
1.1 Models
....................................................................................................................................3
1.2 Overview
................................................................................................................................ 3
1.3 Top Panel Interface
.................................................................................................................. 4
2 External Light Detection Considerations
........................................................................ 5
3 Installation Instructions
................................................................................................ 7
3.1 Mounting Instructions
............................................................................................................... 7
3.2 Installing the Fibers
..................................................................................................................7
3.3 Wiring Diagrams
...................................................................................................................... 8
4 Operating Instructions
.................................................................................................. 9
4.1 Run Mode
............................................................................................................................... 9
4.2 Program Mode
......................................................................................................................... 9
4.2.1 TEACH Selection
........................................................................................................... 10
4.2.2 Response Speed
........................................................................................................... 11
4.2.3 Offset Percent
.............................................................................................................. 11
4.2.4 Delays/Timers
.............................................................................................................. 11
4.2.5 Display Readout
........................................................................................................... 12
4.2.6 Gain Selection
.............................................................................................................. 12
4.2.7 Factory Defaults
........................................................................................................... 12
4.3 Remote Input
......................................................................................................................... 12
4.4 Adjust Mode
.......................................................................................................................... 13
4.4.1 Two-Point TEACH
...........................................................................................................13
4.4.2 Dynamic TEACH
............................................................................................................ 15
4.4.3 Window SET
..................................................................................................................17
4.4.4 Light SET
......................................................................................................................19
4.4.5 Dark SET
..................................................................................................................... 21
4.4.6 Calibration SET
..............................................................................................................23
4.4.7 Troubleshooting
............................................................................................................24
5 Specifications
5.1 Dimensions
6 Accessories
.............................................................................................................. 25
............................................................................................................................ 26
.................................................................................................................. 27
6.1 Quick-Disconnect Cordsets
...................................................................................................... 27
7 Banner Engineering Corp Limited Warranty
................................................................. 29
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
1 Product Description
Advanced sensor with dual digital displays for use with plastic and glass fiber optic assemblies
•
•
•
•
•
•
•
•
•
•
•
A full feature DIN rail mounted fiber optic light receiver for external light
detection
Capable of detecting light level changes over all visible light colors plus
infrared and near ultraviolet
Easy to apply in many LED and lamp inspection stations
Easy to read dual digital displays show both signal level and threshold
simultaneously
Lever action fiber clamp provides stable, reliable, and trouble-free fiber
clamping
Simple user interface ensures easy sensor set-up and programming via
displays and switches/buttons or remote input teach wire
TEACH and SET methods ensure optimal gain and threshold settings
Operates over a wide range of light levels
User has full control over all operating parameters: threshold, Light
Operate or Dark Operate, output timing functions, gain level, and response
speed
Response speeds of 50 ms and 150 ms
Sleek 10 mm wide housing mounts to 35 mm DIN rail
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to
serious injury or death. This device does not include the self-checking redundant circuitry necessary
to allow its use in personnel safety applications. A sensor failure or malfunction can cause either an
energized or de-energized sensor output condition.
1.1 Models
Model
Outputs
DF-G1-NR-2M
Single NPN
DF-G1-PR-2M
Single PNP
DF-G1-NR-Q5
Single NPN
DF-G1-PR-Q5
Single PNP
DF-G1-NR-Q7
Single NPN
DF-G1-PR-Q7
Single PNP
Connector1
2 m (6.5 ft) cable, 4-wire
150 mm (6 in) PVC pigtail, M12 Euro QD connector,
4-pin
Integral M8 Pico QD connector, 4-pin
1.2 Overview
The DF-G1 is an easy-to-use, DIN-rail-mountable fiber optic light receiver. It provides high-performance sensing for
external light applications.
The sensor’s compact housing has dual digital displays (Red/Green) and a bright output LED for easy programming and
status monitoring during operation. The sensor features a single discrete output, either NPN or PNP, by model.
An accessory clamp is available to secure a bank of connected sensors together on a DIN rail (see Accessories on page
27).
1 Connector options:
•
•
•
A model with a QD connector requires a mating cordset (see Quick-Disconnect Cordsets on page 27).
For 9 m cable, change the suffix 2M to 9M in the 2 m model number (example, DF-G1-NR-9M).
For 150 mm (6 in) PVC pigtail, M8 Pico QD connector, 4-pin change the suffix 2M to Q3 in the 2 m model number (example,
DF-G1-NR-Q3).
www.bannerengineering.com - Tel: 763.544.3164
3
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
1
Output LED
2
LO/DO Switch
3
RUN/PRG/ADJ Mode Switch
4
Lever Action Fiber Clamp
5
Red Signal Level
6
Green Threshold
7
+/SET/- Rocker Button
Figure 1. DF-G1 Model Features
1.3 Top Panel Interface
Opening the dust cover provides access to the top panel interface. The top panel interface consists of the RUN/PRG/ADJ
mode switch, LO/DO switch, +/SET/- rocker button, dual red/green digital displays, and output LED.
RUN/PRG/ADJ Mode Switch
The RUN/PRG/ADJ mode switch puts the sensor in RUN, PRG (Program), or ADJ (Adjust) mode. RUN
mode allows the sensor to operate normally and prevents unintentional programming changes via the
+/SET/- rocker button. PRG mode allows the sensor to be programmed through the display-driven
programming menu (see Program Mode on page 9 ). ADJ mode allows the user to perform Expert
TEACH/SET methods and Manual Adjust (see Adjust Mode on page 13 ).
LO/DO Switch
The LO/DO switch selects Light Operate or Dark Operate mode. In Light Operate mode, the output is
ON when the sensing condition is above the threshold. (For Window SET, the output is ON when the
sensing condition is inside the window.) In Dark Operate mode, the output is ON when the sensing
condition is below the threshold. (For Window SET, the output is ON when the sensing condition is
outside the window.)
+/SET/- Rocker Button
The +/SET/- rocker button is a 3-way button. The +/- positions are engaged by rocking the button left/
right. The SET position is engaged by clicking down the button while the rocker is in the middle position.
All three button positions are used during PRG mode to navigate the display-driven programming menu.
During ADJ mode, SET is used to perform TEACH/SET methods and +/- are used to manually adjust the
threshold(s). The rocker button is disabled during RUN mode, except when using Window SET, see
Window SET on page 17.
Red/Green Digital Displays
During RUN and ADJ modes, the Red display shows the signal level, and the Green display shows the
threshold. During PRG mode, both displays are used to navigate the display-driven programming menu.
Output LED
The output LED provides a visible indication when the output is activated.
4
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
2 External Light Detection Considerations
External lighting variations must be carefully considered when applying this sensor because the amount of background
light can measurably affect detection reliability.
The DF-G1 Fiber Optic Light Receiver detects both the light of interest and ambient light. Figure 2 on page 5 shows
simulated light levels for both the dark state and the light state. The dark state is the amount of light detected when the
external light of interest is not present. Conversely, the light state is the amount of light detected when both the ambient
and external light of interest are present. In the dark state, the graph shows that light detected can change with time.
Changes in the dark state light levels are caused by variations in the ambient light levels (perhaps sunlight or factory light
variations). Typical variations in the detected light level when the external light of interest is present (light state) are also
shown in the figure. Note again that the light level can vary with changes in the ambient light level.
Contrast =
DL
BD
Detected Light
Darkest
Light Level
Brightest
Dark Level
Dark
State
Light
State
DL
BD
Dark
State
Time
Figure 2. Light Levels
A successful sensing application is obtained when the sensor can detect between the light and dark conditions. Two
important points shown in Figure 2 on page 5 are the brightest dark level (BD) and the darkest light level (DL). These
values represent the key values for determining if the application will be successfully detected. The application goal is to
maximize the light level detected in the darkest light state. Using this concept of contrast, calculate the contrast available
to ensure a good sensing application. The contrast should be greater than 2 for robust sensing applications.
Contrast = DL/BD
The DF-G1 Fiber Optic Light Receiver detects light over a wide range of the light spectrum and over a wide range of light
intensity. Table 1 on page 5 and Table 2 on page 5 depict the typical minium light intensity as well as the maximum
light intensity values that can be detected. Use the tables as a guide for comparing detectable light levels for various light
sources. In Table 1 on page 5, values for the light intensity are in Lux and in Table 2 on page 5 values for light
intensity are in µW/cm².
Table 1: Typical Light Detection Capabilities in Lux
PIT26U
Light Source
PIT66U
Glass Fiber IMT.756.6S-HT
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
Green (535 nm)
3.0
50,000
0.9
15,000
0.9
15,000
Red (626 nm)
1.0
16,000
0.3
4,800
0.3
4,800
Blue (485 nm)
0.7
11,000
0.4
3,300
0.4
3,300
White (cool)
3.0
50,000
0.9
15,000
0.9
15,000
Table 2: Typical Light Detection Capabilities in µW/cm²
PIT26U
Light Source
PIT66U
Glass Fiber IMT.756.6S-HT
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
Green (535 nm)
0.5
7,500
0.2
2,250
0.2
2,250
Red (626 nm)
0.5
7,500
0.2
2,250
0.2
2,250
Blue (485 nm)
0.6
9,000
0.3
2,700
0.3
2,700
White (cool)
0.5
7,500
0.2
2,250
0.2
2,250
Infrared (850 nm)
2.0
30,000
0.6
9,000
0.1
1,500
www.bannerengineering.com - Tel: 763.544.3164
5
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
The two tables above are a guide for detecting external lights. The sensor does not measure absolute light levels. It
detects the presence of an external light source based on the received light intensity relative to a user-set threshold.
These tables demonstrate that the sensor will detect light sources typical in many industrial applications and highlights
that the selection of the fiber optic cable diameter affects the limits of light detection.
6
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
3 Installation Instructions
3.1 Mounting Instructions
Mount on a DIN Rail
1. Hook the DIN rail clip on the bottom of the DF-G1
over the edge of the DIN rail (1).
2. Push the DF-G1 up on the DIN rail (1).
3. Pivot the DF-G1 onto the DIN rail, pressing until it
snaps into place (2).
Mount to the Accessory Bracket
1. Position the DF-G1 in the SA-DIN-BRACKET.
2. Insert the supplied M3 screws.
3. Tighten the screws.
Remove from a DIN rail
1. Push the DF-G1 up on the DIN rail (1).
2. Pivot the DF-G1 away from the DIN rail and remove
it (2).
3.2 Installing the Fibers
Follow these steps to install glass or plastic fibers.
1. Open the dust cover.
2. Move the fiber clamp forward to unlock it.
3. Insert the fiber(s) into the fiber port(s) until they
stop.
4. Move the fiber clamp backward to lock the fiber(s).
5. Close the dust cover.
www.bannerengineering.com - Tel: 763.544.3164
Slide forward
to release
fiber
Fiber Port
7
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
3.3 Wiring Diagrams
NPN Models
PNP Models
Key
10-30V dc
10-30V dc
Load
Load
Remote
Programming
(N.O.)
Remote
Programming
(N.O.)
NOTE: Open lead wires must be connected to a terminal block.
8
www.bannerengineering.com - Tel: 763.544.3164
1
2
3
4
=
=
=
=
Brown
White
Blue
Black
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
4 Operating Instructions
4.1 Run Mode
Run mode allows the sensor to operate normally and prevents unintentional programming changes. The +/SET/- rocker
button is disabled during RUN mode, except when using Window SET, see Window SET on page 17.
4.2 Program Mode
Program (PRG) mode allows the following settings to be programmed in the DF-G1 (refer to Figure 3 on page 10 and
Figure 5 on page 13 for programming).
www.bannerengineering.com - Tel: 763.544.3164
9
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Figure 3.
4.2.1 TEACH Selection
The DF-G1 can be programmed for one of the following TEACH/SET methods:
• Two-Point TEACH
• Dynamic TEACH
• Window SET
• Light SET
• Dark SET
10
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
•
Calibration SET
NOTE: A TEACH Selection must be selected by programming before TEACH/SET methods can be
used.
4.2.2 Response Speed
The DF-G1 can be programmed for one of the following Response Speeds:
Response Speed
Display Range
Crosstalk Avoidance Algorithm
50 ms
0 – 9999
Disabled
150 ms
0 – 9999
Enabled
4.2.3 Offset Percent
The Offset Percent is used during the Window, Light, or Dark SET methods. The threshold(s) are positioned a
programmable % offset from the taught condition. The allowable range depends upon the Response Speed Mode, as
shown below:
Response Speed
MIN %
MAX %
50 ms
10
999
150 ms
10
999
The offset percent can also be programmed to Minimum Offset. This allows the DF-G1 to set the
threshold(s) as close as possible to the presented condition, but still provide for reliable sensing.
NOTE: Offset Percent MUST be programmed to Minimum Offset for Dark SET to accept conditions of
no signal (0 counts).
4.2.4 Delays/Timers
ON/OFF Delays and ON/OFF One-Shot
timers can be programmed between 1 9999 ms (a value of 0 disables the delay/
timer). Figure 4 on page 11 defines how
the delays/timers affect the output
behavior.
ON
Output
OFF
OFF Delay
Some combinations of delays/timers are not
allowed. The DF-G1 programming menu
automatically disables invalid combinations
of delays/timers. When invalid timing
functions are attempted, only the last
timing function will be implemented. For
example, if an Off Delay is selected and
then an On One-Shot Timer is added, this
invalid combination will force the sensor to
have the On One-Shot Timer function and
not have the Off Delay.The following table
shows the allowable combinations of
delays/timers:
OFF Delay
OFF One-Shot Timer
OFF 1-Shot
D
D
D
D
ON Delay
D
D
ON 1-Shot
D
D
(D = 1 - 9999 ms)
Time
Figure 4. DF-G1 Delays/Timers
OFF Delay
OFF One-Shot Timer
ON Delay
ON One-Shot Timer
-
OK
OK
N/A
OK
-
N/A
N/A
www.bannerengineering.com - Tel: 763.544.3164
11
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
OFF Delay
OFF One-Shot Timer
ON Delay
ON One-Shot Timer
ON Delay
OK
N/A
-
OK
ON One-Shot Timer
N/A
N/A
OK
-
4.2.5 Display Readout
The readout of the digital displays can be programmed for the following options:
• Signal/Threshold readout - Numeric (1234) or % (123P)
• ECO mode - Enabled or Disabled (ECO mode dims the displays to reduce current consumption)
•
Display Orientation - Normal (
) or Flipped (
)
4.2.6 Gain Selection
The DF-G1 can operate in Auto Gain mode or the Gain can be fixed to be in Gain 1…8. In Auto Gain, the DF-G1 optimizes
the gain during a TEACH/SET method for the presented condition(s). While viewing the fixed gains in the Gain Selection
choice list, the DF-G1 will automatically switch to the selected gain and display the measured signal on the Red display.
This allows for easy and quick evaluation of the fixed gain mode.
4.2.7 Factory Defaults
The Factory Defaults menu allows the DF-G1 to be easily restored back to original factory default settings (see Factory
Default Settings in Specifications on page 25).
4.3 Remote Input
The remote input may be used to perform TEACH/SET methods and to program the sensor remotely. Connect the white
input wire of the sensor to ground (0 V dc), with a remote switch connected between them. Pulse the remote input
according to the diagram shown in Figure 5 on page 13. Follow the instructions in the TEACH/SET sections in Adjust
Mode on page 13 to perform a TEACH/SET method.
The sensor exits TEACH and remote programming modes after a 60 second timeout. Users may exit TEACH and remote
programming modes by setting the remote input low for more than 2 seconds. In either case, the sensor returns to Run
mode without saving any new settings.
12
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Remote
Input
NOTE: Follow procedure for the selected TEACH/SET method
(highlighted in black box) chosen in the TEACH Selection menu
Two Point TEACH 2Pt tch, then 1234 2nd
PASS or FAIL (with % Minimum Diff.)
TEACH METHODS
1x
Pulse Timing (T)
0.04 seconds < T < 0.8 seconds
Timing between Pulse groups > 1 second
1x
Dynamic TEACH dYn tch, then 1234 dYn
PASS or FAIL (with % Minimum Diff.)
1x
or
1x
Light SET Lt SEt then PASS or FAIL*
Dark SET dr SEt then PASS or FAIL*
Window SET wind SEt then PASS or FAIL*
Calibration SET CAL SET then PASS or FAIL
1x
1x
1x
1x
(continued from below)
PRO Advanced
3x
* with % offset if not hard fail
2x
PRO Basic
1x
1x
0 ms
2 Pt. TEACH
2x
100 ms
2x
Dynamic TEACH
3x
200 ms
3x
Window SET
Light SET
4x
500 ms
5x
1000 ms
6x
2000 ms
4x
Dark SET
CAL SET
5x
6x
2x
50 ms
150 ms
PROGRAM (Basic)
2x
Offset Percent
1x
Min. Offset
2x
25%
50%
75%
100%
200%
3x
4x
5x
6x
4x
5x
4x
Button Lock
1x
Button Unlock (uloc)
2x
Button Lock (loc)
5x
Display Readout
1x
Numeric
2x
Percent
3x
4x
ECO Numeric
ECO Percent
5x
Numeric Flipped
6x
Percent Flipped
ECO Numeric Flipped
ECO Percent Flipped
7x
8x
3x
3x
Response Speed
1x
3x
Off Delay
1x
TEACH Selection
PROGRAM (Advanced)
2x
PRO Advanced
(continued at top)
6x
Off One-Shot
1x
0 ms
2x
100 ms
3x
200 ms
4x
500 ms
5x
1000 ms
6x
2000 ms
On Delay
1x
0 ms
2x
100 ms
3x
200 ms
4x
500 ms
5x
1000 ms
6x
2000 ms
On One-Shot
1x
0 ms
2x
100 ms
3x
200 ms
4x
500 ms
5x
1000 ms
6x
2000 ms
Gain Select
1x
Auto Gain
2x
Gain 1
3x
Gain 2
Gain 3
4x
5x
4x
Button Lock (loc) or Unlock (uloc)
6x
8x
Factory Default Settings
8x
7x
9x
Gain 4
Gain 5
Gain 6
Gain 7
Gain 8
Figure 5. Remote Input Flowchart
4.4 Adjust Mode
Sliding the RUN/PRG/ADJ mode switch to the ADJ position allows the user to perform Expert TEACH/SET methods and
Manual Adjustment of the threshold(s).
4.4.1 Two-Point TEACH
•
•
Establishes a single switching threshold
Threshold can be adjusted by using the "+" and "-" rocker button (Manual Adjust)
www.bannerengineering.com - Tel: 763.544.3164
13
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Two-Point TEACH is used when two conditions can be presented statically to the sensor. The sensor locates a single
sensing threshold (the switch point) midway between the two taught conditions, with the Output ON condition on one side,
and the Output OFF condition on the other.
Darkest Taught
Condition
Lightest Taught
Condition
Sensor positions
threshold midway
between taught conditions
Output OFF
Darkest
(no signal)
Output ON
Position
adjusted by
Manual Adjust
Most Light
(saturated
signal)
Figure 6. Two-Point TEACH (Light Operate shown)
The Output ON and OFF conditions can be reversed by using the LO/DO (Light Operate/ Dark Operate) switch.
Two-Point TEACH and Manual Adjust
Moves switching threshold value up or down to make adjustments
•
•
•
Slide Mode switch to ADJ to enter Adjust mode
Press "+" to increase; press "-" to decrease
◦ GREEN display shows the switching threshold value
◦ 2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Follow these steps to perform a Two-Point TEACH:
Note: TEACH Selection must be programmed to 2Pt tcH.
1. Enter Adjust mode.
Method
Action
Result
SET Button 2
Set the Mode switch to ADJ.
Display: Red - Signal Level; Green Threshold
Remote Input 3
No action is required; sensor is ready
for the Two-Point TEACH method
2. Teach the first condition.
Method
SET Button
Action
Result
a. Present the first condition.
Display: Flashes "2Pt tch" then holds
on "1234 2nd"
b. Click the SET rocker button.
Remote Input
a. Present the first condition.
T
b. Single-pulse the remote input.
3. Teach the second condition.
2 SET Button: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
3 Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
14
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Method
SET Button
Action
Result
TEACH Accepted
a. Present the second condition.
Displays alternate "PASS" and %
Minimum Difference4; Sensor returns
to Adjust mode
b. Click the SET rocker button.
Remote Input
a. Present the second condition.
T
b. Single-pulse the remote input.
TEACH Not Accepted
Displays alternate "FAIL" and %
Minimum Difference4; Sensor returns
to Adjust mode
4. Return to Run mode.
Method
Action
Result
SET Button
Move the Mode switch to RUN
Display: Red - Signal Level; Green Threshold
Remote Input
No action is required; sensor returns to
RUN mode automatically
4.4.2 Dynamic TEACH
•
•
•
Teaches on-the-fly
Establishes a single switching threshold
Threshold can be adjusted using "+" and "-" rocker button (Manual Adjust)
Dynamic TEACH is best used when a machine or process may not be stopped for teaching. The sensor learns during actual
sensing conditions, taking multiple samples of the light and dark conditions and automatically setting the threshold at the
optimum level.
Darkest Taught
Condition
Lightest Taught
Condition
Sensor positions
threshold midway
between taught conditions
Output OFF
Darkest
(no signal)
Output ON
Position
adjusted by
Manual Adjust
Most Light
(saturated
signal)
Figure 7. Dynamic TEACH (Light Operate shown)
The output ON and OFF conditions can be reversed using the LO/DO switch.
Dynamic TEACH and Manual Adjust
Moves switching threshold value up or down to make adjustments
•
Slide Mode switch to ADJ to enter Adjust mode
4 See Troubleshooting on page 24 for more explanation of the % Minimum Difference displayed after the Two-Point TEACH
method.
www.bannerengineering.com - Tel: 763.544.3164
15
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
•
•
Press "+" to increase; press "-" to decrease
◦ GREEN display shows the switching threshold value
◦ 2 seconds after adjustment, GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Follow these steps to perform Dynamic TEACH:
NOTE: TEACH Selection must be programmed to dYn tcH.
1. Enter Adjust Mode.
Method
Action
Result
SET Button 5
Set Mode switch to ADJ
Display: Red - Signal Level; Green Threshold
Remote Input 6
No action required; sensor is ready for
Dynamic TEACH method
2. Enter Dynamic TEACH.
Method
Action
Result
SET Button
Click the SET rocker button
Display: Flashes "dYn tch" then holds
on "1234 dYn"
Remote Input
Single-pulse remote input
T
3. Present ON and OFF Conditions.
Method
Action
Result
SET Button
Present ON and OFF conditions
Display: Red - Signal Level; Green Threshold
Remote Input
Present ON and OFF conditions
4. Exit Dynamic TEACH.
5 SET Button: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
6 Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
16
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Method
Action
Result
SET Button
Click the SET rocker button
TEACH Accepted
Remote Input
Single-pulse remote input
T
Displays alternate "PASS" with %
Minimum Difference7, Sensor returns
to Adjust mode
TEACH Not Accepted
Displays alternate "FAIL" with %
Minimum Difference7, Sensor returns
to Adjust mode
5. Return to RUN Mode.
Method
Action
Result
SET Button
Move Mode switch to RUN
Display: Red - Signal Level; Green Threshold
Remote Input
No action required; sensor returns to
RUN mode automatically
4.4.3 Window SET
•
•
•
•
•
Sets window thresholds that extend a programmable % offset above and below the presented condition
All other conditions (lighter or darker) cause the output to change state
Sensing window center can be adjusted using "+" and "-" rocker button (Manual Adjust)
Recommended for applications where a product may not always appear in the same place, or when other signals
may appear
See Program Mode on page 9 for programming the Offset Percent setting (to increase/decrease the window size)
A single sensing condition is presented, and the sensor positions window thresholds a programmable % offset above and
below the presented condition. In LO mode, Window SET designates a sensing window with the Output ON condition inside
the window, and the Output OFF conditions outside the window.
NOTE: For Window SET and Light SET, the maximum offset threshold percent is 90%.
7 See Troubleshooting on page 24 for more explanation of the % Minimum Difference displayed after the Dynamic TEACH
method.
www.bannerengineering.com - Tel: 763.544.3164
17
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Sensing window
center adjusted by
Manual Adjust
Output OFF
Darkest
(no signal)
Output ON
Sensor positions
window thresholds
a programmable %
offset from the
presented condition
Output OFF
Condition
Presented
Most Light
(saturated
signal)
Figure 8. Window SET (Light Operate shown)
Output ON and OFF conditions can be reversed using the LO/DO switch.
Window SET and Manual Adjust
Moves sensing window center value up or down to make adjustments
•
•
•
Slide Mode switch to ADJ to enter Adjust mode
Press "+" to increase; press "-" to decrease
◦ GREEN display shows the sensing window center value
◦ 2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Follow these steps to perform a Window SET:
Note: TEACH Selection must be programmed to wind SEt.
1. Enter Adjust Mode
Method
Action
Result
SET Button 8
Set Mode switch to ADJ
Display: Red - Signal Level; Green Threshold
Remote Input 9
No action required; sensor is ready for
Window SET method
2. SET Sensing Condition
8 SET Button: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
9 Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
18
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Method
SET Button
Remote Input
Action
Result
•
Present sensing condition
•
Click the SET rocker button
•
Present sensing condition
•
Single-pulse the remote input
Threshold Condition Accepted
Displays read "wInd SEt" then
alternate "PASS" with % Offset10;
Sensor returns to Adjust mode
T
Threshold Condition Not Accepted
Displays read "wInd SEt" then
alternate "FAIL" with minimum %
Offset10 for sensing condition; Sensor
returns to Adjust mode
3. Return to RUN Mode
Method
Action
Result
SET Button
Move Mode switch to Run
Remote Input
No action required; sensor returns to
Run mode automatically
Display: Red - Signal Level; Green Window Center (see Figure 9 on page
19 for instructions on how to display
upper and lower thresholds)
Window SET (during RUN mode)
Upon sensor power-up, Window Center is displayed
Upper
Threshold
Displayed
Window
Center
Displayed
Lower
Threshold
Displayed
Figure 9. Upper and Lower Thresholds
4.4.4 Light SET
•
•
•
•
•
Sets a threshold a programmable % offset below the presented condition
Changes output state on any condition darker than the threshold condition
Threshold can be adjusted using "+" and "-" rocker button (Manual Adjust)
Recommended for applications where only one condition is known, for example a stable light background with
varying darker targets
See Program Mode on page 9 for programming the Offset Percent setting
A single sensing condition is presented, and the sensor positions a threshold a programmable % offset below the
presented condition. When a condition darker than the threshold is sensed, the output either turns ON or OFF, depending
on the LO/DO setting.
10 See Troubleshooting on page 24 for more explanation of the % Offset displayed after the Window SET method
www.bannerengineering.com - Tel: 763.544.3164
19
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
NOTE: For Window SET and Light SET, the maximum offset threshold percent is 90%.
Threshold position
adjusted by
Manual Adjust
Sensor positions
threshold a programmable
% offset below the
presented condition
Output OFF
Darkest
(no signal)
Output ON
Condition
Presented
Most Light
(saturated
signal)
Figure 10. Light SET (Light Operate shown)
Light SET and Manual Adjust
Moves switching threshold value up or down to make adjustments
•
•
•
Slide Mode switch to ADJ to enter Adjust mode
Press "+" to increase; press "-" to decrease
◦ GREEN display shows the switching threshold value
◦ 2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Follow these steps to perform a Light SET:
Note: TEACH Selection must be programmed to Lt SEt.
1. Enter Adjust Mode
Method
Action
Result
SET Button 11
Set Mode switch to ADJ
Display: Red - Signal Level; Green Threshold
Remote Input 12
No action is required; sensor is ready
for Light SET method
2. SET Sensing Condition
11 SET Button: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
12 Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
20
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Method
SET Button
Remote Input
Action
Result
•
Present sensing condition
•
Click the SET rocker button
•
Present sensing condition
•
Single-pulse the remote input
Threshold Condition Accepted
Displays read "Lt SEt" then alternate
"PASS" with % Offset13; Sensor
returns to Adjust mode
T
Threshold Condition Not Accepted
Displays read "Lt SEt" then alternate
"FAIL" with minimum % Offset13 for
sensing condition; Sensor returns to
Adjust mode
3. Return to RUN Mode
Method
Action
Result
SET Button
Move Mode switch to RUN
Display: Red - Signal Level; Green Threshold
Remote Input
No action required; sensor returns to
RUN mode automatically
4.4.5 Dark SET
•
•
•
•
•
Sets a threshold a programmable % offset above the presented condition
Any condition lighter than the threshold condition causes the output to change state
Threshold can be adjusted using "+" and "-" rocker button (Manual Adjust)
Recommended for applications where only one condition is known, for example a stable dark background with
varying lighter targets
See Program Mode on page 9 for programming the Offset Percent setting
NOTE: Offset Percent MUST be programmed to Minimum Offset to accept conditions of no signal (0
counts).
A single sensing condition is presented, and the sensor positions a threshold a programmable % offset above the
presented condition. When a condition lighter than the threshold is sensed, the output either turns ON or OFF, depending
on the LO/DO setting.
13 See Troubleshooting on page 24 for more explanation of the % Offset displayed after the Light SET method
www.bannerengineering.com - Tel: 763.544.3164
21
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Threshold position
adjusted by
Manual Adjust
Sensor positions
threshold a programmable
% offset above the
presented condition
Output OFF
Darkest
(no signal)
Output ON
Condition
Presented
Most Light
(saturated
signal)
Figure 11. Dark SET (Light Operate shown)
Dark SET and Manual Adjust
Moves switching threshold value up or down to make adjustments
•
•
•
Slide Mode switch to ADJ to enter Adjust mode
Press "+" to increase; press "-" to decrease
◦ GREEN display shows the switching threshold value
◦ 2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Follow these steps to perform a Dark SET:
Note: TEACH Selection must be programmed to dr SEt.
1. Enter Adjust Mode.
Method
Action
Result
SET Button 14
Set Mode switch to ADJ
Display: Red - Signal Level; Green Threshold
Remote Input 15
No action required; sensor is ready for
Dark SET method
2. SET Sensing Condition.
Method
Action
SET Button
Remote Input
Result
•
Present sensing condition
•
Click the SET rocker button
•
Present sensing condition
•
Single-pulse the remote input
Threshold Condition Accepted
Displays read "dr SEt" then alternate
"PASS" with % Offset16; Sensor
returns to Adjust mode
T
Threshold Condition Not Accepted
Displays read "dr SEt" then alternate
"FAIL" with minimum % Offset16 for
sensing condition; Sensor returns to
Adjust mode
3. Return to RUN Mode.
14 SET Button: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
15 Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
16 See Troubleshooting on page 24 for more explanation of the % Offset displayed after the Dark SET method
22
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Method
Action
Result
SET Button
Move Mode switch to RUN
Display: Red - Signal Level; Green Threshold
Remote Input
No action required; sensor returns to
RUN mode automatically
4.4.6 Calibration SET
•
•
Sets a threshold exactly at the presented condition
Threshold can be adjusted using "+" and "-" rocker button (Manual Adjust)
A single sensing condition is presented, and the sensor positions a threshold exactly at the presented condition. When a
condition lighter than the threshold is sensed, the output either turns ON or OFF, depending on the LO/DO setting.
Threshold position
adjusted by
Manual Adjust
Sensor positions
threshold exactly at
the presented condition
Output OFF
Darkest
(no signal)
Output ON
Condition
Presented
Most Light
(saturated
signal)
Figure 12. Calibration SET (Light Operate shown)
Calibration SET and Manual Adjust
Moves switching threshold value up or down to make adjustments
•
•
•
Slide Mode switch to ADJ to enter Adjust mode
Press "+" to increase; press "-" to decrease
◦ GREEN display shows the switching threshold value
◦ 2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Follow these steps to perform a Calibration SET:
Note: TEACH Selection must be programmed to CAL SEt.
1. Enter Adjust Mode
Method
Action
SET Button 17
Remote Input 18
•
Result
Set Mode switch to ADJ
Display: Red - Signal Level; Green Threshold
No action required; sensor is ready for
Calibration SET method
2. SET Sensing Condition
17 SET Button: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
18 Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
www.bannerengineering.com - Tel: 763.544.3164
23
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
Method
Action
SET Button
Remote Input
Result
•
Present sensing condition
•
Click the SET rocker button
•
Present sensing condition
•
Single-pulse the remote input
Threshold Condition Accepted
Displays read "cAL SEt" then flashes
"PASS"; Sensor returns to Adjust
mode
T
Threshold Condition Unacceptable
Displays read "cAL SEt" then flashes
"FAIL"; Sensor returns to Adjust
mode
3. Return to RUN Mode
Method
Action
Result
SET Button
Move Mode switch to RUN
Display: Red - Signal Level; Green Threshold
Remote Input
No action required; sensor returns to
RUN mode automatically
4.4.7 Troubleshooting
Percent Minimum Difference after TEACH
The Two-Point and Dynamic TEACH methods will flash a % minimum difference on the displays after a PASS or FAIL.
Value
PASS/FAIL
Description
0 to 99%
FAIL
The difference of the taught conditions does not meet the required minimum
100 to 300%
PASS
The difference of the taught conditions just meets/exceeds the required minimum,
minor sensing variables may affect sensing reliability
300 to 600%
PASS
The difference of the taught conditions sufficiently exceeds the required minimum,
minor sensing variables will not affect sensing reliability
600% +
PASS
The difference of the taught conditions greatly exceeds the required minimum, very
stable operation
Percent Offset after SET
The Window, Dark, and Light SET methods will flash a % offset on the displays after a PASS or FAIL.
SET Result
% Offset Meaning
PASS (with % Offset)
Displays the % offset used for the SET method
FAIL (with % Offset)
Displays the minimum required % offset necessary to PASS the SET method
FAIL (without % Offset)
Presented condition cannot be used for the SET method
NOTE: For Window SET and Light SET, the maximum offset threshold percent is 90%.
24
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
5 Specifications
Adjustments
3-way RUN/PRG/ADJ Mode Switch
2-way LO/DO Switch
Supply Voltage
3-way +/SET/- Rocker Button
10 to 30 V dc Class 2 (10% maximum ripple)
•
Expert-style teaching (Two-Point and Dynamic TEACH, Light/
Power and Current Consumption (exclusive of load)
Dark/Window/Calibration SET)
Standard display mode: 960 mW, Current consumption < 40 mA at
•
Manually adjust sensitivity (from "+" and "-" rocker button
24 V dc
only)
ECO display mode: 720 mW, Current consumption < 30 mA at 24 V dc
•
Response Speed, TEACH Selection, Offset Percent, Delays/
Supply Protection Circuitry
Timers, Display Readout, Gain Selection, Factory Defaults
Protected against reverse polarity and transient overvoltages
(from top panel or remote input)
•
Top panel interface lockout (from remote input only)
Delay at Power-Up
500 milliseconds maximum; outputs do not conduct during this time
Factory Default Settings:
Light Detection Range
400 to 1100 nm
Output Configuration
1 current sinking (NPN) or 1 current sourcing (PNP) output, depending
on model
Output Rating
100 mA maximum load (derate 1 mA per °C above 30 °C)
OFF-state leakage current: < 5 μA at 30 V dc
ON-state saturation voltage: NPN: < 1.5 V; PNP < 2 V
Output Protection
Protected against output short-circuit, continuous overload, transient
overvoltages, and false pulse on power-up
Output Response Time
50 ms
150 ms
Temperature Drift
0.2% per °C
Indicators
Red 4-digit Display: Signal Level
Green 4-digit Display: Threshold
(In Program Mode, Red and Green displays are used for programming
menus)
Yellow LED: Output conducting
Required Overcurrent Protection
WARNING: Electrical connections must be
made by qualified personnel in accordance
with local and national electrical codes and
regulations.
Overcurrent protection is required to be provided by end product
application per the supplied table.
Overcurrent protection may be provided with external fusing or via
Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to http://
www.bannerengineering.com.
Supply Wiring
Required Overcurrent Protection
20
5.0 Amps
22
3.0 Amps
24
2.0 Amps
26
1.0 Amps
28
0.8 Amps
30
0.5 Amps
Setting
Factory Default
Threshold
5000
TEACH Selection
Two-Point TEACH
Response Speed
50 ms
Offset Percent
50%
OFF Delay
0 (Disabled)
OFF One-Shot
0 (Disabled)
ON Delay
0 (Disabled)
ON One-Shot
0 (Disabled)
Display Readout
Numeric, ECO disabled, Normal
Orientation
Gain Selection
Auto Gain
Connections
PVC-jacketed 2 m or 9 m (6.5 ft. or 30 ft.) 4-wire integral cable; or
integral 4-pin M8/Pico-style quick disconnect; or 150 mm (6 in.) cable
with a 4-pin M12/Euro-style quick disconnect; or 150 mm (6 in.) cable
with a 4-pin M8/Pico-style quick disconnect.
Construction
Black ABS/polycarbonate alloy (UL94 V-0 rated) housing, clear
polycarbonate cover
Environmental Rating
IEC IP50, NEMA 1
Operating Conditions
Temperature: −10 °C to +55 °C (+14 °F to +131 °F)
Storage Temperature: −20 °C to +85 °C (−4 °F to +185 °F)
Humidity: 90% at +60 °C maximum relative humidity (noncondensing)
Certifications
www.bannerengineering.com - Tel: 763.544.3164
Industrial
Control
Equipment
3TJJ
25
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
5.1 Dimensions
All measurements are listed in millimeters (inches), unless noted otherwise.
26
www.bannerengineering.com - Tel: 763.544.3164
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
6 Accessories
DIN-35-..
35 mm DIN Rail
Model
Length
DIN-35-70
70
DIN-35-105
105
DIN-35-140
140
L
35
SA-DIN-CLAMP
Pair of metal DIN rail end stops; slide onto DIN rail at
•
either side of the sensor stack
•
Combination (#2 Phillips, #8 standard slotted) set screw
L = 70, 105 or 140 mm
9.1 mm
(0.63")
Hole center spacing: 35.1
Hole size: 25.4 x 5.3
9.1 mm
(0.36")
45.0 mm
(1.77")
SA-DIN-BRACKET
•
Plastic bracket with
mounting screws
10
SA-DIN-BRACKET-10
Package of 10 plastic
•
brackets with mounting
screws
35
10
35
Hole center spacing: A = 16, B = 25.4, C = 15.2
Hole center spacing: A = 16, B = 25.4, C = 15.2
Hole size: A = ø 3.2, B = ø 3.3, C = ø 4.4
Hole size: A = ø 3.2, B = ø 3.3, C = ø 4.4
6.1 Quick-Disconnect Cordsets
All measurements are listed in millimeters, unless noted otherwise.
4-Pin Threaded M12/Euro-Style Cordsets
Model
Length
MQDC-406
1.83 m (6 ft)
MQDC-415
4.57 m (15 ft)
MQDC-430
9.14 m (30 ft)
MQDC-450
15.2 m (50 ft)
MQDC-406RA
1.83 m (6 ft)
MQDC-415RA
4.57 m (15 ft)
MQDC-430RA
9.14 m (30 ft)
Style
Dimensions
44 Typ.
Straight
M12 x 1
ø 14.5
15.2 m (50 ft)
2
1
3
4
32 Typ.
[1.26"]
30 Typ.
[1.18"]
Right-Angle
MQDC-450RA
Pinout (Female)
1
2
3
4
=
=
=
=
Brown
White
Blue
Black
M12 x 1
ø 14.5 [0.57"]
www.bannerengineering.com - Tel: 763.544.3164
27
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
4-Pin Threaded M8/Pico-Style Cordsets
Model
Length
PKG4M-2
2 m (6.56 ft)
PKG4M-5
5 m (16.4 ft)
PKG4M-9
9 m (29.5 ft)
PKW4M-2
2 m (6.56 ft)
PKW4M-5
5 m (16.4 ft)
Style
Dimensions
35 Typ.
Straight
ø 9.5
M8 x 1
4
2
1
3
28 Typ.
1 = Brown
2 = White
3 = Blue
4 = Black
20 Typ.
Right Angle
PKW4M-9
Pinout (Female)
9 m (29.5 ft)
M8 x 1
ø 9.5
4-Pin Snap-on M8/Pico-Style Cordsets
Model
Length
PKG4-2
2 m (6.6 ft)
PKG4-5
5 m (16.4 ft)
Style
Dimensions
Pinout (Female)
32 Typ.
Straight
PKG4-10
10 m (32.8 ft)
PKW4Z-2
2 m (6.6 ft)
PKW4Z-5
5 m (16.4 ft)
ø 9.0
4
15 Typ.
ø 10.9
28
3
29 Typ.
Right-Angle
www.bannerengineering.com - Tel: 763.544.3164
2
1
1 = Brown
2 = White
3 = Blue
4 = Black
DF-G1 Expert™ Dual Display Fiber Optic Light Receiver
7 Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following
the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture
which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty
does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR
IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR
TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO
EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR
ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR
SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE
PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY,
NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any
obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp.
www.bannerengineering.com - Tel: 763.544.3164