Sentinel
Technical Specifications
ALARM NOTIFICATION METHODS:
BATTERY BACKUP:
E-Mail, Text Messages, Voice Phone Calls
4.8V 2000mAHr NiMh Battery pack (included)
Programmable alarm escalation levels
Provides 8 hours of backup
Comprehensive scheduling per input, profile, and
alarm destination
LOCAL INDICATORS:
Unlimited number of User Profiles
12 Alarm Status LEDs
Multiple contact types per user
• Power LED • Online LED
INPUTS:
12 Universal Inputs
• Standby LED • Ethernet link and Activity LEDs
POWER REQUIREMENTS:
• Normally Open / Normally Closed Dry Contact
Comes with 12VDC plug-in power supply.
• 2.8K / 10K Thermistor
(International power options available).
• 4-20mA Current Loop
• Pulse Count
• 12 Bit Resolution
TEMPERATURE SENSING RANGE:
-109° to 168°F | -85° to 76°C
RELAY OUTPUT:
Programmable. Rated for 1A 30VAC/ 1A 30VDC
DATA LOGGING:
Unlimited samples securely stored on the Sentinel
servers
Programmable sampling interval - 1 min to 24 hrs
User programmable channel selection
COMMUNICATION PORTS:
Ethernet 10/100Base–T
ENVIRONMENTAL:
Operating Humidity:
0-90% RH, non–condensing
Operating Temperature:
32° to 122°F | 0° to 50°C
PHYSICAL:
In metal enclosure:
5.5 x 6.3 x 1.5” | 140 x 160 x 38mm
1 lb. | .45kg
With Weatherproof Enclosure:
12.17 x 10.25 x 3.5” | 309 x 260 x 89mm
3.7 lb. | 1.67 kg
ENCLOSURE:
Durable powder coated metal housing suitable for
wall or panel installation or weatherproof NEMA
4X rated fiberglass enclosure.
STANDARDS:
FCC Part 15 – Class A Compliant
901 Tryens Road • Aston, PA 19014 • PH: 877-373-2700 • F: 610-558-0222 • www.sensaphone.com
很抱歉,暂时无法提供与“SCD-1200-4GRWCD”相匹配的价格&库存,您可以联系我们找货