››em4
em4 remote
em4 remote 2G
››All in one nanoPLC including remote
management and remote maintenance with
GPRS interface, for use with 2G networks
››Monitor and control remotely your application,
from a single installation to a fleet of machine
››Save time in designing your application using
the most intuitive graphical function block
language of the market
››Measure accurately your high end industrial
sensors with the embedded configurable
analog inputs (including 4-20 mA)
››Integrate easily one of our three high tech
designs in your machine
››Adapt your application along the way of its
lifecycle thanks to the enhanced controlling
performances
em4 remote - Robust
em4 remote - Glossy black
em4 remote - Glossy white
Specific characteristics
Part number
88 981 152
88 981 153
88 981 154
Type
B26-2GC
Inputs
16 digital inputs (including 4 High Speed, 8 analog 0-10 V / potentiometers
and 4 analog 0-10 V / 4-20 mA)
Outputs
10 digital outputs (including 2 solid states 0.5 A PWM, 2 relays 6 A and 6 relays 8 A)
Supply
Finish
On front panel color
24 VDC
Robust
Glossy black
Black RAL 9011
On terminal block color
Glossy white
White RAL 9003
Blue RAL 5017
Protection rating
(in accordance with IEC/EN 60529)
IP 50 on front panel
IP 20 on terminal block
IP 40 on front panel
IP 20 on terminal block
Weight
Without packing: 350 g
With packing: 400 g
Without packing: 345 g
With packing: 395 g
Dimensions
Without packing:
124.6 x 90 x 62.6 mm /
4.91 x 3.54 x 2.46 inch
With packing:
148 x 103 x 65 mm /
5.83 x 4.06 x 2.56 inch
Without packing:
124.6 x 90 x 60.4 mm / 4.91 x 3.54 x 2.38 inch
With packing:
148 x 103 x 65 mm / 5.83 x 4.06 x 2.56 inch
R&TTE Directive
Standards of North American type approval
1999/5/EC
US-Federal Communications Commission (FCC)
Frequency range GSM 900
880 - 960 MHz
Frequency range GSM 1800
1710 - 1880 MHz
Frequency range GSM 850
824 - 894 MHz
Frequency range GSM 1900
1850 - 1990 MHz
Antenna: impedance
50 Ω
Antenna: input power
>2W
Antenna: V.S.W.R
< 2:1 recommended
< 3:1 acceptable
Antenna: return loss
S11 < - 10 dB recommended
S11 < - 6 dB acceptable
Antenna: connector
RP SMA : SMA Female Reverse Polarity
I em4
I 02
I www.em4-remote-plc.com
General characteristics
Products certification (in accordance with IEC/EN 60529)
CE, cULus Listed
Conformity with the low voltage directive (in accordance
with BT 2006/95/EC)
IEC/EN 61131-2 (Open equipment)
Conformity with the EMC directive
(in accordance with 2004/108/EC)
IEC/EN 61000-6-1 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-2 (Industrial)
IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-4 (Industrial)
Earthing
None
Overvoltage category
3 in accordance with IEC/EN 60664-1
Pollution
Degree: 2 in accordance with IEC/EN 61131-2
Maximum utilization altitude
Operation: 2000 m
Transport: 3000 m
Mechanical resistance
Immunity to vibrations IEC/EN 60068-2-6, Fc test
Immunity to shock IEC/EN 60068-2-27, Ea test
Resistance to electrostatic discharge
Immunity to ESD IEC/EN 61000-4-2, level 3
Resistance to HF interference
(Immunity)
Immunity to radiated electrostatic fields IEC/EN 61000-4-3, level 3
Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3
Iuunity to shock waves IEC/EN 61000-4-5
Radio frequency in common mode IEC/EN 61000-4-6, level 3
Conducted and radiated emissions
(in accordance with EN 55022/11 group 1)
Class B
Operation temperature
-20°C (-4°F) +60°C (140°F) (+40°C (104°F) in a non-ventilated enclosure)
Storage temperature
-40°C (-40°F) +80°C (176°F)
Relative humidity
95% max. (no condensation or dripping water)
Screw terminals connection capacity
Flexible wire with ferrule: 1 conductor: 0.2 to 2.5 mm² (AWG 24-14)
Flexible wire with ferrule: 2 conductors: 0.2 to 0.75 mm² (AWG 24-18)
Rigid wire: 1 conductor: 0.2 to 2.5 mm² (AWG 24-14)
Rigid wire: 2 conductors: 0.2 to 0.75 mm² (AWG 24-18)
Tightening torque: 0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
Stripping length: 6 mm
Processing characteristics
LCD display
Display with 4 lines of 18 characters
Programming method
FBD (Function Block Diagram), including SFC (Sequential Function Chart, Grafcet)
Program size
Function blocks: typically 1000 blocks
Macro blocks: 64 max. (256 blocks per macro)
Program memory
Flash
Removable memory
N.A
Data memory
2 k octets
Backup time
(in the event of power failure)
Program and settings in the controller: 10 years
Data memory: 10 years
Data backup
Data backup in the flash memory is guaranteed if the product is powered on more
than 10 seconds
Cycle time
From 2 ms to 90 ms, default value: 10 ms
Clock data retention
10 years (lithium battery) at 25°C (77°F)
Clock drift
Drift < 12 min/year (at 25°C (77°F)
6 s / month (at 25°C (77°F) with user-definable correction of drift).
Synchronizable by network
Timer block accuracy
0.5 % +/- 2 cycle time
Start up time on power up
< 3 s base alone, < 1.5 s base + 2 expansions + accessory interface
(USB or Modbus RS485)
Self test
Test firmware integrity (checksum memory)
Stability of the internal power supply
Check the conformity of the em4 device configuration with the configuration in the
application program.
I em4
I 03
I www.em4-remote-plc.com
Supply
Nominal voltage
24 VDC (-15% / +20%)
Operating limits
20.4 - 28.8 VDC
Immunity from micro power cuts
y 1 ms (repetition 20 times)
Max. absorbed power
5.3 W
Protection against polarity inversions
Yes
Inputs
Digital and high speed digital inputs 24 VDC - 4 inputs from I1 to I4
Input used as digital input
Input voltage
24 VDC (-15% / +20%)
Input current
1.8 mA @ 20.4 V
2.1 mA @ 24 V
2.5 mA @ 28.8 V
Input impedance
11.6 kΩ
Logic 1 voltage threshold
u 15 VDC
Making current at logic state 1
u 1.3 mA
Logic 0 voltage threshold
y 10 VDC
Release current at logic state 1
y 0.8 mA
Response time
1 to 2 cycle times
Sensor type
Contact or 3-wire PNP
Conforming to IEC/EN 61131-2
Type 1
Input type
Resistive
Isolation between power supply and inputs
None
Isolation between inputs
None
Protection against polarity inversions
Yes
Status indicator
On LCD screen
Cable length
y 100 m
Input used as high speed digital input
Maximum counting frequency
Other functions
Cable length
3 channels encoder (I1, I2, I3): 20 kHz*
2 independent counters (I1, I2) (I3, I4) (Cumul, IND, DIR): 2 channels: 40 kHz*,
4 channels: 20 kHz*,
2 independent counters (I1, I2) (I3, I4) (PH, PH2): 2/4 channels: 20 kHz*
4 independent counters (I1, I2, I3, I4) (Up/Down) : 1 channel: 60 kHz*, 2 channels:
40 kHz*, > 2 channels: 20 kHz*
* with a time cycle y 10 ms and a ton / toff = 50% +/- 5%, level 0 < 2V and level 1 > 20,4V
4 chronometers (I1, I2, I3, I4 )
4 tachometers (I1, I2, I3, I4 )
y 3 m with shielded twisted cable
Digital 24 VDC and analog inputs 12 bits / 28.8 V - potentiometer - 8 inputs from I5 to IC
Input used as digital input
Input voltage
24 VDC (-15% / +20%)
Input current
1.8 mA @ 20.4 V
2.1 mA @ 24 V
2.5 mA @ 28.8 V
Input impedance
11.6 kΩ
Logic 1 voltage threshold
u 11 VDC
Making current at logic state 1
u 1 mA
Logic 0 voltage threshold
y 9 VDC
Release current at logic state 1
y 0.7 mA
Response time
1 to 2 cycle times
Sensor type
Contact or 3-wire PNP
Conforming to IEC/EN 61131-2
Type 1
Input type
Resistive
Isolation between power supply and inputs
None
Isolation between inputs
None
Protection against polarity inversions
Yes
Status indicator
On LCD screen
Cable length
y 100 m
I em4
I 04
I www.em4-remote-plc.com
Input used as analog input
Measuring range
0 10 V or 0 V power supply
Input impedance
11.6 kΩ
Maximum value without destruction
28.8 VDC max
Input type
Common mode
Resolution
12 bit at maximum input voltage (10.5 bit at 10V)
Value of LSB
7.03 mV
Conversion time
Controller cycle time
Maximum error in 0-10V mode
+/- 1.1 % of full scale at 25°C (77°F)
+/- 1.6 % of full scale at 55°C (131°F)
Maximum error in 0-V power supply mode
+/- 2 % of full scale at 25°C (77°F)
+/- 3 % of full scale at 55°C (131°F)
Repeat accuracy at 55°C (131°F)
+/- 0.5 %
Isolation between analog channel and power supply
None
Protection against polarity inversions
Yes
Potentiometer control
2.2 kΩ / 0.5 W (recommended), 10 KΩ max.
Cable length
y 10 m with shielded twisted cable (sensor not isolated)
Digital 24 VDC and analog inputs 12 bits / 10 V & 11 bits / 0-20 mA- potentiometer - 4 inputs from ID to IG
Input used as digital input (power off state)
Input voltage
24 VDC (-15% / +20%)
Input current
1.5 mA @ 20.4 V
1.7 mA @ 24 V
2.1 mA @ 28.8 V
Input impedance
13.9 kΩ
Logic 1 voltage threshold
u 11 VDC
Making current at logic state 1
u 0.8 mA
Logic 0 voltage threshold
y 8 VDC
Release current at logic state 1
y 0.5 mA
Response time
1 to 2 cycle times
Sensor type
Contact or 3-wire PNP
Conforming to IEC/EN 61131-2
Type 1
Input type
Resistive
Isolation between power supply and inputs
None
Isolation between inputs
None
Protection against polarity inversions
Yes
Status indicator
On LCD screen
Cable length
y 100 m
Input used as 0-10 V analog input
Measuring range
0 10 V
Input impedance
13.9 kΩ
Maximum value without destruction
28.8 VDC max
Input type
Common mode
Resolution
12 bit / 10V
Value of LSB
2.45 mV
Conversion time
Controller cycle time
Maximum error at 25°C (77°F)
+/- 0.8 % of full scale
Maximum error at 55°C (131°F)
+/- 1.2 % of full scale
Repeat accuracy at 55°C (131°F)
+/- 0.5 %
Isolation between analog channel and power supply
None
Protection against polarity inversions
Yes for voltage y 10 V
Potentiometer control
2.2 kΩ / 0.5 W (recommended), 10 KΩ max.
Cable length
y 10 m with shielded twisted cable (sensor not isolated)
I em4
I 05
I www.em4-remote-plc.com
Input used as 0-20 mA analog input
Measuring range
0 20 mA (4 20 mA by the application)
Input impedance
245 Ω
Maximum value without destruction
30 mA max
Input type
Common mode
Resolution
11 bit (normalized at 0 - 2000) / 20 mA
Value of LSB
10 µA
Conversion time
Controller cycle time
Maximum error at 25°C (77°F)
+/- 1.2 % of full scale
Maximum error at 55°C (131°F)
+/- 1.7 % of full scale
Repeat accuracy at 55°C (131°F)
+/- 0.5 %
Isolation between analog channel and power supply
None
Protection against polarity inversions
Yes
Overvoltage protection
Yes If the input voltage is > 7 V, this one is automatically switched on 0-10V configuration.
Cable length
y 30 m with shielded twisted cable (sensor not isolated)
Outputs
Digital / PWM solid state output - 2 solid state outputs from O1 to O2
Output used as digital output
Breaking voltage
10 28.8 VDC
Nominal voltage
12 / 24 VDC
Nominal current
0.5 A on resistive load @ 25°C (77°F)
Max. breaking current
0.625 A
Non repetitive overload current
1A
Maximum breaking current in the common
1A
Voltage drop
< 1 V for I = 0.5 A
Response time
Make = 1 cycle time + 30 µs typical
Release = 1 cycle time + 40 µs typical
Built-in protections
Against overloads and short-circuits: Yes
Against over voltages (*): Yes
Against inversions of power supply: Yes
Minimum load
1 mA
Galvanic isolation
No (*) In the absence of a potential free contact between the output of the
programmable logic controller and the load
Cable length
Truth table of the default
y 10 m
Command Output
Fault
Normal condition
0
0
No
1
1
No
Overheating
0
0
No
1
0
Yes
Underpowered
0
0
X
1
0
X
Short circuit (current limit)
0 0 No
1
0
Yes
Output used as PWM output
PWM frequency
14.11 Hz ; 56.45 Hz ; 112.90 Hz ; 225.80 Hz ; 451.59 Hz ; 1758.24 Hz
PWM cyclic ratio
0 100 % 100 steps
PWM Max. error
y 2 % (from 10 % 90 %)
Status indicator
On LCD screen
Cable length
y 10 m with shielded twisted cable
Distance between the power source and the static outputs
y 30 m
I em4
I 06
I www.em4-remote-plc.com
6 A relay output - 2 outputs from O3 to O4
Breaking voltage
250 VAC max
Breaking current
6A
Maximum breaking current in the common
IEC @ 25°C (77°F): 12 A
IEC @ 60°C (140°F) or UL: 10 A
Mechanical life
5 000 000 operations (cycles)
Electrical durability for 50 000 operating cycles
24 VDC tau = 0 ms: 6 A, tau = 7 ms: 3 A, tau = 15 ms: 1.8 A
Usage category DC-12: 24 V, 6 A
Usage category DC-14: 24 V, 1.8 A
250 VAC cos phi = 1: 6 A, cos phi = 0.7: 5 A, cos phi = 0.4: 2.5 A
Usage category AC-12: 250 V, 6 A
Usage category AC-13: 250 V, 5 A
Usage category AC-15: 250 V, 2 A
Minimum switching capacity
100 mA (at minimum voltage of 12 V)
Maximum operating rate
Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks
In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time
Make = 8 ms max
Release = 4 ms max
Built-in protections
Against short-circuits: None
Against over voltages and overload: None
Status indicator
On LCD screen
Cable length
y 30 m
8 A relay output - 6 outputs from O5 to OA
Breaking voltage
250 VAC max
Breaking current
8 A, u 55°C: 6 A
Maximum breaking current in the common
IEC @ 25°C (77°F): C3, C6: 8 A ; C4, C5: 16 A
IEC @ 60°C (140°F) or UL: C3, C6: 8 A ; C4, C5: 10 A
Mechanical life
20 000 000 operations (cycles)
Electrical durability for 50 000 operating cycles
24 VDC tau = 0 ms: 8 A, tau = 7 ms: 3 A, tau = 15 ms: 1.5 A
Usage category DC-12: 24 V, 8 A
Usage category DC-14: 24 V, 1.5 A
250 VAC cos phi = 1: 8 A, cos phi = 0.7: 4.75 A, cos phi = 0.4: 3 A
Usage category AC-12: 250 V, 8 A
Usage category AC-13: 250 V, 4.3 A
Usage category AC-15: 250 V, 1.5 A
Minimum switching capacity
100 mA (at minimum voltage of 12 V)
Maximum operating rate
Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks
In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time
Make = 8 ms max
Release = 4 ms max
Built-in protections
Against short-circuits: None
Against over voltages and overload: None
Status indicator
On LCD screen
Cable length
y 30 m
I em4
I 07
I www.em4-remote-plc.com
Diagrams
Dimensions
B26 2GC Robust
90 / 3.54
108.1 / 4.25
90 / 3.54
108.1 / 4.25
48.7 / 1.91
62.6 / 2.46
80 / 3.15
99.4
3.91
45 / 1.77
124.6 / 4.90
87.6 / 3.45
43.2 / 1.70
mm
inch
64.8 / 2.55
B26 2GC Glossy
45 / 1.77
99.4
3.91
80 / 3.15
124.6 / 4.90
87.6 / 3.45
43.2 / 1.70
48.7 / 1.91
60.4 / 2.38
mm
inch
64.8 / 2.55
Connections
Inputs
I1 ... IG 0/1
+ 24 VDC
PNP
+
BL
I1 ... IG
(2)
24V
PNP
+ (1)
–
B26
-
BN
BK
+ –
I1 I2 I3 I4 I5 I6 I7 I8
I9 IA IB IC ID IE IF IG
100 m Max
3937 inches Max
–
30 V, NTC, LDR, R
I5 ... IC U
+ 24 VDC
LDR
NTC
2K2
0 - 30V
0 - 10V
+
0.5 W
10k max
24V
12 bits / 28,8V
–
(2)
I5 ... IC
B26
+ (1)
–
+ –
I1 I2 I3 I4 I5 I6 I7 I8
I9 IA IB IC ID IE IF IG
10 m Max
393.7 inches Max
I em4
I 08
I www.em4-remote-plc.com
ID ... IG U / I
20 mA, 10 V, R
+ 24 VDC
3K3
+
2K2
0.5 W
10k max
11 bits
0 - 20 mA
(2)
ID ... IG
24V
+ (1)
–
12 bits / 10V
0 - 10V
B26
-
20 mA
30 m Max
1181 inches Max
10 V, R
10 m Max
393.7 inches Max
+ –
I1 I2 I3 I4 I5 I6 I7 I8
I9 IA IB IC ID IE IF IG
+ –
I1 I2 I3 I4 I5 I6 I7 I8
I9 IA IB IC ID IE IF IG
3 m Max
118.1 inches Max
+ –
I1 I2 I3 I4 I5 I6 I7 I8
I9 IA IB IC ID IE IF IG
3 m Max
118.1 inches Max
I9 IA IB IC ID IE IF IG
3 m Max
118.1 inches Max
–
I1 ... I4
Hz
2604
+ 24 VDC
A
B
Z
A
+
+
I1
I2
I3
CNT 1
(2)
24V
+ (1)
–
B
I4
90°
Z
-
PNP
B26
-
–
I1 ... I4
Hz
2604
+ 24 VDC
+
I1
I2
A
B
CNT 1
+
24V
I3
I4
A
B
+
(2)
+ (1)
–
CNT 2
-
B26
–
I1 ... I4
2604
Hz, s, Rpm
+ 24 VDC
BL
BN
BK
+
(2)
I1 ... I4
24V
PNP
-
B26
+ (1)
–
+ –
I1 I2 I3 I4 I5 I6 I7 I8
–
(1) 1 A (UL248) quick-blowing fuse,
circuit-breaker or circuit protector (US)
(2) Isolating source
I em4
I 09
I www.em4-remote-plc.com
Outputs
O1 & O2
0.5 A
12 ...24V
+
30 m Max
1181 inches Max
(1)
C1 O1 O2
C2 O3 O4
C3 O5
C4 O6 O7
C5 O8 O9
C6 OAOA/
10 m Max
393.7 inches Max
C1
On
B26
(3)
12…24 V
U
–
+
(1)
–
C1 = 1 A max
12 ...24V
6 A, 8 A
O3 ... OA
12…240V 50/60Hz
12 ...24V
L
+
Cn
C1 O1 O2
6A
8A
8A
8A
C2 O3 O4
C3 O5
C4 O6 O7
C5 O8 O9
On
B26
(3)
(3)
12…240 V
50 / 60 Hz
or 12…24 V
U
U
–
N
Protection / Protection / Schutzschaltung / Protección / Protezione
L/+
N/–
L/+
N/–
C2 = 12 A max
C4, C5 = 16 A max
C3 ... C6 : Same polarity
(3) Inductive load
I/O installations
+ –
C1 O1 O2
I1 I2 I3 I4 I5 I6 I7 I8
C2 O3 O4
C3 O5
I9 IA IB IC ID IE IF IG
C4 O6 O7
C5 O8 O9
C6 OAOA/
C3 = 8 A max
C6 = 8 A max
8A
C6 OAOA/
30 m Max
1181 inches Max
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Crouzet:
88981153 88981154 88981156 88981157